Diversified Electronics 800.727.5646 atcdiversified.com MOTOR PROTECTION MPA2 Series Diversified Electronics 800.727.5646 atcdiversified.com Motor Protection Analyzer MPA2 is a micro-controlled based three-phase Motor Protec- tion Analyzer Relay specifically designed to protect electric loads and motors from failure and damage due to common current and voltage faults. MPA2 constantly supervises current and voltage values. When any harmful condition occurs, the output connection is deactivated until the fault disappears, power line conditions return to an acceptable level and the motor has been totally cooled. Specific timing such as Start Up Delay (TC) and Trip Delay (TD) are incorporated to prevent nuisance tripping due to rapid power fluctuations. MPA2 provides LCD Display to indicate the output status voltage, current, unbalance, frequency and load status and failure conditions. It also provides four (4) push buttons (1 for START, 2 for ADJUST and 1 for SELECT) for operation and protection parameters adjustment. Besides these mentioned advantages, a Communication Port with MODBUS RTU proto- col is included with MPA2. An innovative mechanical design allows two (2) placement options:

  • Symmetrical Din-Rail mounting.
  • Flat Surface mounting, using an exclusive attachable mounting ear. MPA2 has been developed using the most advanced technol- ogy and designed in accordance with the IEEE, IEC and NEMA protection standards and developed in compliance with IEC electromagnetic compatibility standards, working safely under the hardest electrical environments. When you use a MPA2 Motor Protection Analyzer, you are working with the best solution to protect your most impor- tant investments. MEASUREMENT OF:
  • Current
  • Voltage
  • Frequency
  • Power Factor (PF)
  • Reactive Power (KVA)
  • Real Power (KW)
  • Energy Consumption (KWH) REPORTS:
  • Voltage & Current report
  • PF , KVA, KWH, KW report
  • Adjusted Values report
  • Total Motor Running Time report
  • Start Mode report
  • 20 Last Fault report
  • Power Frequency report
  • Motor Temperature report COMMUNICATIONS:
  • COM-LINK RS485@ 9600 baud output available (MODBUS RTU protocol) PHYSICAL FEATURES:
  • Din-Rail, Flat Surface or Flush mounting
  • 16x2 LCD Display with current values, voltage values, and load report information on screen
  • Four (4) push buttons for op- eration and protection param- eter adjustments (I for START, 2 for ADJUST and I for SELECT)
  • Enclosure material UL94V0 ADJUSTMENTS OF:
  • Overload
  • Undercurrent
  • Overvoltage
  • Undervoltage
  • Current Unbalance
  • Voltage Unbalance
  • Frequency
  • Trip Delay
  • Start Up Delay after Voltage
  • Fault Recovery
  • Motor Thermal Class
  • Clock Adjustment
  • Control of Motor High-Inertia Load
  • Schedule Timer
  • AUTO / MANUAL Restart Mode
  • Password PROTECTION AGAINST:
  • Overload / Undercurrent
  • Overvoltage / Undervoltage
  • Frequency Shift
  • Voltage Unbalance
  • Current Unbalance
  • Single Phasing
  • Phase Reversal
  • Locked Rotor OTHERS:
  • Thermal memory OVERVIEW

FEATURES

Standards (LVD and EMC): IEC 61010-1 IEC 60255-6 IEC 60255-8 IEC 60947-1 PRODUCT STANDARDS Designed according to: UL 60947-4-1 IEEE C37.112 DIMENSIONS (INCHES/MILLIMETERS) Eq. Co.Ind. 496Y

FUNCTIONS & RANGE OF APPLICATIONS The MPA2 provides electrical protection through general func- tions and setting ranges for intended use listed as follows: VOLTAGE Overvoltage: 5% up to 20% rated voltage DETECTION Undervoltage: -20% up to -5% rated voltage Unbalance: 2% up to 10% rated voltage Single Phasing: (IN 33% - OUT 28%) RECOVERY & Start Up Delay after Voltage fault: 0 to 600 sec DETECTION Voltage Fault detection time: 1 to 30 sec TIME Phase Reversal detection time: <1 sec FREQUENCY Frequency Shift: +/-2% up to +/-10% rated DETECTION frequency CURRENT Overcurrent: 5% up to 25% DETECTION Undercurrent: Adjustable by PF or by I nominal Unbalance: CUB > 48 % Single Phasing: CUB > 60 % POWER FACTOR Power Factor: 0.0 up to 1.0 DETECTION THERMAL CLASS Thermal Class: 5 to 30 (in step of one by one) IEC 60255-8 Diversified Electronics 800.727.5646 atcdiversified.com MOTOR PROTECTION MPA2 Series PHYSICAL FEATURES ATTENTION: Only qualified technicians with knowledge about overload protection relay and associated machinery should do the installation, starting up, and maintenance of the system. Failure to comply may result in equipment damage and/or personal injury. SAFETY INFORMATION NOTICE: This product has been designed for industrial environments. Use of this product in residential environments may cause unwanted electromagnetic disturbances in which case the user may be required to take adequate mitigation measures. Failure to comply may result in equipment damage and/or personal injury. CONSIDERATION REGARDING EMC MODEL NUMBER MODEL NUMBER MPA2 VOLTAGE 208/220/240 V~ 240 440/480 V~ 480 AMPERAGE 1-4 A 04 3.5-12.5 A 12 10-32 A 32 25-80 A 80 External Current Transformer CT ACCESSORIES Standard RS485 Communications Cable MPA2-COM Current Transformer 30/5 amp CT30/5 Current Transformer 50/5 amp CT50/5 Current Transformer 100/5 amp CT100/5 Current Transformer 200/5 amp CT200/5 Current Transformer 500/5 amp CT500/5 Current Transformer 1000/5 amp CT1000/5 STANDARD STOCK MPA2-240-CT MPA2-480-32 MPA2-480-80 MPA2-480-CT MPA2-COM Diversified Electronics 800.727.5646 atcdiversified.com