Technical data sheet CMB24-L-100D Technical Data Compact actuator with damper blade, for the control or isolation of volumetric air flows in air-conditioning plants, particularly where space is limited
- Pipe diameter 4” [DN 100]
- Torque motor 18 in-lb [2 Nm]
- Nominal voltage AC/DC 24 V
- Control On/Off, Floating point
- Fit into round air ducts in accordance with DIN EN 1506 Technical data Electrical Data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Power consumption in operation 0.5 W Power consumption in rest position 0.2 W Power consumption for wire sizing 1 VA Connection supply / control cable 3 ft. [1 m], 3 x 0.75 mm² Parallel operation Yes (note the performance data) Functional Data Torque motor 18 in-lb [2 Nm] Pipe diameter 4” [DN 100] Position feedback U note No Feedback Manual override disengage with magnet Angle of rotation 70° Running Time (Motor) 58 s / 70° Noise level, motor 35 dB(A) Position indication Mechanically, pluggable (with integrated magnet for gear disengagement) Airtightness Class 3 (DIN EN 1751) Resistance coefficient ζ 0.48 (in open position) Static differential pressure max. 1000 Pa via the damper (4” w.g) Safety Flame class Damper blade UL 94 HB Actuator UL 94 V-0 Fire behaviour group Damper blade RF3 (CH) Actuator RF2 (CH) Fire load 4.2 MJ Protection class IEC/EN III protective extra-low voltage (pelv) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2 Enclosure UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification UL cURus according to UL60730-1A, UL60730-2- 14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient humidity max. 95% r.H., non-condensing Servicing maintenance-free Weight Weight 0.49 lb [0.22 kg] Materials Housing material UL94-5VA www.belimo.us CMB24-L-100D Technical Data Sheet • en-us • 2020-05-04 • subject to changes 1
- The device must not be used outside the specified field of application, especially not in aircraft or in any other airborne means of transport.
- The device must not be used for safety applications, e.g. fire protection.
- As a rule, the device is resistant to a multitude of organic solvents and alkaline agents. Unusual ambient conditions will, however, require special clarifications. In particular, the damper may not be used in environments where it may be exposed to chemically aggressive substances, e.g. laboratory exhaust air or fume hood exhaust air (laboratory exhaust systems / fume hoods).
- Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied with during installation. ensure smooth operation.
- Adherence to the pipe geometry specified in accordance with DIN EN 1506 must be ensured (no damage).
- The device may only be opened at the manufacturer’s site. It does not contain any parts that can be replaced or repaired by the user.
- Cables must not be removed from the device.
- The device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed.
- †Rated Impulse Voltage 800V, Type action 1, Control Pollution Degree 3. Product features Fields of application - Air flow through the building shell - Air distribution / comfort ventilation - Air outlets - Zone controls - Devices with outside air: Facade devices / fan coils / fan-powered boxes / cabin units etc. - Exhaust air systems, e.g. sanitary facilities Manual override Manual override with magnet possible (gear disengagement as long as the magnet adheres to the magnet symbol). The Z-MA magnet for the gear disengagement is enclosed. High functional reliability The actuator is overload protected, requires no limit switches and automatically stops when the end stop is reached. Flow noise The noise caused by the flow of air in the pipe section with a built-in air damper and passed along inside it. Below the sound power levels listed are A-evaluated in the duct as a function of dimension, volumetric flow and pressure loss. AIRFLOW AIRFLOWLWA CMB24-L-100D Technical Data Actuator with damper blade, 4” [DN 100], On/Off, Floating point, AC/DC 24 V, 2 Nm Safety Notes www.belimo.usCMB24-L-100D Technical Data Sheet • en-us • 2020-05-04 • subject to changes2
Sound power level LWA Sound power level with A-evaluation, including correction of the outlet reflection LWA Volumetric flow Air velocity v Pressure loss Δp 100 1000 1002 00 3004 00 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 70dB(A) 65dB(A) 60dB(A) 55dB(A) 50dB(A) 45dB(A) 40dB(A) v [m/s] /uniE001 [m³/h] ∆p [Pa] Accessories Description Type Mechanical accessories Gear disengagement magnet Z-MA Electrical installation Notes • Connection via safety isolating transformer.
- Parallel power connection of additional actuators is possible. Observe the transformer size and performance data. Wiring diagrams Floating Point 1 3 1124 VAC Transformer Blk (1) Common Red (2) + Hot Wht (3) Y Input Line Volts A On/Off Blk (1) Common Red (2) Hot + Wht (3) Y Input Line Volts 1 3 1124 VAC Transformer CMB24-L-100D Technical Data Actuator with damper blade, 4” [DN 100], On/Off, Floating point, AC/DC 24 V, 2 Nm Product features www.belimo.us CMB24-L-100D Technical Data Sheet • en-us • 2020-05-04 • subject to changes 3
Pipelines • Belimo recommends the use of round folded spiral-seam pipelines (spiro pipes) with 0.5 mm metal gauge (in accordance with DIN EN 1506) and with the fold on the outside of the pipe. Folded spiral-seam pipes are usually rounder than longitudinally- welded pipes. Leakages can be reduced as a result. The interior side of the folded spiral-seam pipes is smooth. The welding seam can inhibit the function of the damper blade with longitudinally welded pipes. If longitudinally welded pipes nevertheless need to be used, Belimo cannot guarantee the proper functioning of the actuator.
- No protruding longitudinal fold facing inward permitted
- Use only galvanised sheet steel or chrome steel. Installation in plastic pipelines is not recommended.
- Do not place the fastening holes of the actuator across from the welding seam. The damper blade could become damaged after a short time. The fastening holes should be drilled approximately 40 mm away from the welding seam. This will reduce the damper noise and damage to the damper blade to a minimum. 40 mm Installation situation For the pipe connection, take into account the pipe collar size (insertion depth L1) before the actuator fixing and after the damper blade. Observe correct direction of air flow: → Actuator → Damper blade → Special installation shapes require verification. The strain relief of the cable is guaranteed in the CM.. actuator. AIRFLOW AIRFLOW L L1L1 DN L 100 ≥235 125 ≥240 150 ≥250 160 ≥250 It requires the following alignment of the bore holes ø10ø 5 >60 20 AIRFLOW CMB24-L-100D Technical Data Actuator with damper blade, 4” [DN 100], On/Off, Floating point, AC/DC 24 V, 2 Nm Installation notes www.belimo.usCMB24-L-100D Technical Data Sheet • en-us • 2020-05-04 • subject to changes4
7.87" [200] 6.26" [159] 2.2" [56] 2.6" [66] 0.35" [9] 4.25" [108] 0.75" [20] 0.63" [16.1] CMB24-L-100D Technical Data Actuator with damper blade, 4” [DN 100], On/Off, Floating point, AC/DC 24 V, 2 Nm Operating Controls and Indicators www.belimo.us CMB24-L-100D Technical Data Sheet • en-us • 2020-05-04 • subject to changes 5