CDO ATC | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 1

Technical content

DIMENSIONS (INCHES) The CDO Series is used to detect OVER CURRENT conditions. The internal relay energizes (Pick-up) when the monitored current exceeds the preset trip point for longer than the adjustable time delay. The delay is incorporated to prevent nuisance tripping caused by inrush currents. The CDO has an automatic reset feature. The internal relay de-energizes (Drop-out) when the current drops 5% below the preset trip for longer than 0.2 seconds. MODEL NUMBER CDO 120 A L E CONTROL VOLTAGE

120 Volts 120

FEATURES

0.2 to 1 amp adj. 1 0.5 to 2.5 amps adj. 2.5 1.0 to 5.0 amps adj. 5 2.0 to 10 amps adj. 10 4.0 to 20 amps adj. 20 SPECIFICATIONS CONTROL VOLTAGE 120 VAC, 50/60 Hz TRIP POINTS Over Current Pick-up See order information Drop-out 5% below Pick-up OUTPUT SPDT, 10 Amps @ 240 VAC Resistive HYSTERESIS 5% RESPONSE TIME Operate 0.2 to 10 SEC, Adjustable Release 0.2 SEC. INDICATORS Trip (Red) Glows On Over Current Relay (Green) Glows when Relay is energized RESET Automatic TEMPERATURE Operate 32° to 131°F (0° to +55°C) RATING Storage -49° to 185°F (-45° to +85°C) ENCLOSURE Lexan Surface Mounted; #8-32 Screw Terminals WEIGHT 17 oz. MODEL NUMBER CURRENT MONITORS