B406B Plug-in Detector Base For use with the following smoke detectors: In US: 1451, 2451, 2451TH, 4451HT, 5451 In Canada: 1451A, 2451A, 2451THA, 4451HTA, 5451A In Europe: 1451E, 2451E, 4451E, 5451E INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue
St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Before Installing Please thoroughly read the System Sensor manual I56-407, Guide for Proper Use of System Smoke Detectors, which pro- vides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor. (For installations in Canada, please refer to CAN4-S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.) NOTICE: This manual should be left with the owner/user of this equipment. IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 require- Specifications Base Diameter: 6.2 inches (15.7 cm) Base Height: 1.1 inches (2.9 cm) Weight: 0.3 lb. (130 g) Mounting: 4-inch square box with or without plaster ring. Min. Depth–1.5 inches 4-inch octagon box. Min. Depth–1.5 inches 1⁄2-inch octagon box. Min. Depth–1.5 inches 50 mm box; 60 mm box; 70 mm box Operating Temperature Range: –10° to 60°C (14° to 140°F) Note: Do not install in locations where normal ambient temperature exceeds 50°C (120°F) Operating Humidity Range: 10% to 93% Relative Humidity Electrical Ratings – includes base and detector System Voltage: 24 VDC Maximum Ripple Voltage: 4 Volts peak to peak Start-up Capacitance: 0.02 µF Maximum Standby Ratings: 15 VDC Minimum
35 VDC Maximum
µA Maximum Alarm Ratings: 9 V Minimum at 18 mA
12 V Maximum at 100 mA
(Alarm current MUST be limited to 100 mA maximum by the control panel.) Relay Contact Ratings: Resistive or Inductive (60% power factor) Load Form C*: 2.0A @ 30 V AC/DC 0.6A @ 110 VDC 1.0A @ 125 V AC Reset Voltage: 1.4 VDC Minimum Reset Time: 0.3 Seconds Maximum Start-up Time: 34.0 Seconds Maximum *For Canadian installations relay contact ratings are 2.0A @ 30 V AC/DC. ments. The detector used with this base should be cleaned at least once a year. General Description The B406B plug-in detector base is used with a variety of System Sensor conventional detector heads. They are capa- ble of accepting a variety of detector heads, which makes them more versatile than equivalent direct-wired models. Refer to the System Sensor catalog for other available plug- in detector bases. The B406B base is intended for use in 2-wire systems, with screw terminals provided for power and relay contact con- nections. These bases MUST be current limited by the sys- tem control panel in the alarm state.
responding properly in the event of a fire. used before wiring the detector loops. system supervision of connections. through 5, and to terminals 12 through 14, respectively. Figure 1. Mounting base to box: available from System Sensor upon request. the base, completing the circuit.
tor without the use of a tool. detector base shown in Figure 3A, then install the detector. Figure 2. Typical wiring diagram:
14 COM CONTACT
©2001 System Sensor Three-Year Limited Warranty System Sensor warrants its enclosed smoke detector base to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector base. No agent, represen- tative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector base which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unrea- sonable use, modifications, or alterations occurring after the date of man- ufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Please refer to insert for the Limitations of Fire Alarm Systems