AFRBUP-S BELIMO | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

Technical data sheet AFRBUP-S www.belimo.com AFRBUP-S • en-us • 2020-09-22 • Subject to change 1 / 2 On/Off, Spring Return, AC 24...240 V Technical data Nominal voltage frequency 50/60 Hz Power consumption in operation 7 W Power consumption in rest position 3.5 W Transformer sizing 7 VA @ AC 24 V (class 2 power source), 8.5 VA @ AC 120 V, 18 VA @ AC 240 V Auxiliary switch 2 x SPDT, 3 A resistive (0.5 A inductive) @ AC 250 V, one set at 10°, one adjustable 10...90° Switching capacity auxiliary switch 3 A resistive (0.5 A inductive) @ AC 250 V Electrical Connection (2) 18 GA appliance cables with 1/2" conduit connectors, 3 ft [1 m], Overload Protection electronic throughout 0...95° rotation Functional data Torque motor 180 in-lb [20 Nm] Direction of motion motor selectable by ccw/cw mounting Direction of motion fail-safe reversible with cw/ccw mounting Manual override 5 mm hex crank (3/16" Allen), supplied Angle of rotation 90° Running Time (Motor) 75 s Running time fail-safe <20 s Noise level, motor 45 dB(A) Noise level, fail-safe 62 dB(A) Position indication Mechanical Safety data Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2 Enclosure UL Enclosure Type 2 Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU Quality Standard ISO 9001 Ambient humidity max. 95% r.H., non-condensing Servicing maintenance-free Weight Weight 5.7 lb [2.6 kg]

Technical data sheet AFRBUP-S www.belimo.com AFRBUP-S • en-us • 2020-09-22 • Subject to change 2 / 2 Electrical installation INSTALLATION NOTES Actuators with appliance cables are numbered. Universal Power Supply (UP) models can be supplied with 24 VAC up to 240 VAC, or 24 VDC up to 125 VDC. Provide overload protection and disconnect as required. Two built-in auxiliary switches (2x SPDT), for end position indication, interlock control, fan startup, etc. Actuators may be powered in parallel. Power consumption must be observed. Parallel wiring required for piggy-back applications. Meets cULus requirements without the need of an electrical ground connection. Warning! Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Apply only AC line voltage or only UL-Class 2 voltage to the terminals of auxiliary switches. Mixed or combined operation of line voltage/safety extra low voltage is not allowed. Wiring diagrams On/Off Auxiliary Switches