DH100LP SYSTEMSENSOR | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

100 to 4000 feet per minute (0.5 to 20.32 m/sec.) Patented telescopic sampling tube 12/24 VDC operation Built-in reset button Outside mounting tabs Easy and quick mounting to round or rectangular ducts from 1 ′–12′ (0.3–3.7 meters) wide Photoelectric models available Easy to clean UL recognized field-replaceable power and sensor boards Remote test station option Remote annunciator option Transparent cover for convenient visual inspection UL 268A listed 3-year warranty The System Sensor Innovair™ DH100LP is a 2-wire photoelectric air duct smoke detector capable of sensing smoke in air velocities from 100 to 4,000 feet per minute (0.5 to 20.32 m/sec). This Innovair features Low-Flow technology enabling duct smoke detection throughout a broad range of airflow environ - ments. Many difficult to solve HVAC applications occur in low airflow duct applications where reliable smoke detection is critical. Innovair with Low-Flow technology can detect smoke at air speed velocities of 100 feet per minute or greater, while continuing the same reliable performance to 4,000 feet per minute. The Innovair family is designed for simplified installation and easy maintenance. The modular construction allows for easy cleaning and uncomplicated field replacement of the UL recognized power and sensor boards. WARNING: Duct smoke detectors have specific limitations. DUCT SMOKE DETECTORS ARE: NOT a substitute for an open area smoke detector, NOT a substitute for early warning detection, and NOT a replacement for a building’s regular fire detection system. Refer to NFPA 72 and 90A for additional duct smoke detector application information. Model DH100LP 2-Wire Photoelectric Duct Smoke Detector with Low-Flow Technology Product Overview 2-Wire Low-Flow Duct Smoke Detector H V A C S y S t e m S m o n i t o r i n g

Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor Model DH100LP Series Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 m/sec.). It shall be capable of local testing via magnetic switch or remote testing using the RTS451KEY Remote Test Station. The unit shall be reset by local reset button or RTS451KEY. The duct detector housing shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. Sampling tubes shall either be plastic or be easily installed after the housing is mounted to the duct by passing through the duct housing. The enclosure shall meet all applicable NEC and NFPA standards regarding electrical junction boxes. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring. Size 143/8″ (37 cm) Length 51/2″ (14 cm) Width 23/4″ (7 cm) Depth Shipping Weight 31/4 lbs. (1.5 kg.) Operating Temperature Range 32° to 131° F (0° to 55° C) Storage Temperature Range Operating Humidity Range 10% to 93% relative humidity Air Duct Velocity 100 to 4000 ft./min. (0.5 to 20.32 m/sec.) Standard Specifications Electrical Ratings System Voltage 12/24 VDC Ripple Voltage

4 Volts peak to peak

0.02µF maximum Standby Ratings

8.5 VDC minimum

35 VDC maximum

120µA maximum Alarm Ratings

4.2 VDC minimum at 10mA

6.6 VDC maximum at 100mA

Alarm current must be limited to 100mA or less by the control panel. If used, the RA400Z remote lamp operates within the specified alarm currents. Reset Voltage:

2.50 VDC minimum

Reset Time: 0.3 Sec. maximum Start-up Time 34.0 Sec. maximum

System wiring diagram for 2-wire duct smoke detectors (detectors powered from initiating device circuit): Wiring diagram for the DH100LP to RTS451/RTS451KEY: 5Test + Test / Reset – Reset + Test ResetRA + RA – V Out + 2-Wire Wiring to RTS 451 KEY DH100LP RTS451/RTS451KEY

1 Alarm

4 (+) (+) (–) (–) IN (–) OUT 1ST DETECTOR IN LOOP DH100LP (–) RA400Z (OPTIONAL) REMOTE ALARM LED 2.8 VDC NOM. IN ALARM 4 (+) (+) (–) (–) IN (–) OUT LAST DETECTOR IN LOOP DH100LP (–) RA400Z (OPTIONAL) REMOTE ALARM LED 2.8 VDC NOM. IN ALARM E O L R STYLE D OPTIONAL WIRING UL LISTED COMPATIBLE 2-WIRE CONTROL PANEL ALARM INITIATION LOOP (+) (–) EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER DETECTOR BOARD 7 6 (+) IN (+) OUT DETECTOR BOARD 7 6 (+) IN (+) OUT H0263-00 Note: Terminal 6 of the RTS451KEY is not used when wired to a 2-wire detector. The RTS451 does not have a terminal 6. H0264-00

with Key (UL S2522) PA400W Mini-Alert Sounder (UL S3593) shown with PS24LOW add-on strobe (PS12/24SLENSW smoke lens option available) Device cannot be directly wired to 2-wire Innovair; must be operated independently by the panel. APA451 Piezo Annunciator (UL S4011) Device cannot be directly wired to 2-wire Innovair; must be operated independently by the panel. RTS451 Remote Test Station (UL S2522) RA400Z Remote Annunciator (UL S2522) © 2004 System Sensor. The company reserves the right to change product specifications without notice. A05-1043-002•1/04•#981

Ordering Information

DH100LP 2-wire photoelectric duct smoke detector with low-flow technology A5180 Replacement 2-wire photoelectric detector board A5061 Replacement 2-wire power board Accessories ST-1.5 Metal sampling tube duct widths 1′–2′ (0.3–0.6 m) ST-3 Metal sampling tube duct widths 2′–4′ (0.6–1.2 m) ST-5 Metal sampling tube duct widths 4′–8′ (1.2–2.4 m) ST-10 Metal sampling tube duct widths 8′–12′ (2.4–3.7 m) T80-71-00 Replacement telescoping sampling tube P48-55-00 Replacement end cap for T80-71-00 RTS451KEY Remote test station with key lock RTS451 Remote test station RA400Z Remote annunciator alarm LED APA451 Remote annunciator with piezo alarm MOD400R Sensitivity test module F36-09-11 Replacement air filters (two per package) M02-04-00 Test magnet P48-21-00 End cap for metal sampling tubes S08-39-01 Photo replacement screen PA400W Mini-Alert sounder PS24LOW Mini-Alert add-on strobe PS12/24SLENSW Wall-mount “SMOKE” lens Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations, and several different means of visible and audible system annunciation. As with our duct detectors, all duct smoke detector accessories are UL listed. ALARM P OWER S M O K E ALARM RESET ALARM ON RESET TEST System Sensor Sales and Service System Sensor Headquarters

3825 Ohio Avenue

St. Charles, IL 60174 Ph: 800/SENSOR2 Fx: 630/377-6495 www.systemsensor.com System Sensor Canada Ph: 905.812.0767 Fx: 905.812.0771 System Sensor Europe Ph: 44.1403.891920 Fx: 44.1403.891921 System Sensor in China Ph: 86.29.8832.0119 Fx: 86.29.8832.5110 System Sensor in Singapore Ph: 65.6273.2230 Fx: 65.6273.2610 System Sensor – Far East Ph: 85.22.191.9003 Fx: 85.22.736.6580 System Sensor – Australia Ph: 613.54.281.142 Fx: 613.54.281.172 System Sensor – India Ph: 91.124.637.1770 x.2700 Fx: 91.124.637.3118 System Sensor – Russia Ph: 70.95.937.7982 Fx: 70.95.937.7983