ECSS-3101D EUROPA | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 2
Technical content
It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation. All connections should be inspected periodically to ensure correct tightness. DO NOT USE POWER TOOLS ON THESE PRODUCTS Europa Helpline: 01582 692 444 / Email: technical@europacomponents.com Page 1 of 2 Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440 e-mail: sales@europacomponents.com website: www.europacomponents.comEDS1344-101 Part Number: ECSS-3101D IP67 Enclosed Prewired 3 Phase TT/TN Type 1/2 SPD inc.160A Fuses Features & Benefits
- IP6 7 ABS Enclosure
- Translucent lid
- Retro fit unit, no need to change existing boards
- For protecting installations and equipment rated above 160A SPD Part No. 941310 SPD according to EN 61643-11 type 1 + type 2 Energy coordination with terminal equipment ( ≤ 10m) type 1 + type 2 + type 3 Nominal a.c. voltage (UN) 230 / 400 V (50 / 60 Hz) Max. continuous operating a.c. voltage [L-N] (UC) 255 V (50 / 60 Hz) Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal) 50 kA Specific energy [L1+L2+L3+N-PE] (W/R) 625.00 kJ/ohms Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp) 12.5 / 50 kA Specific energy [L-N]/[N-PE] (W/R) 39.06 / 625.00 kJ/ohms Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In) 12.5 / 50 kA Voltage protection level [L-N]/[N-PE] (UP) ≤ 1.5 / ≤ 1.5 kV Follow current extinguishing capability [L-N]/[N-PE] (Ifi) 25 kArms / 100 Arms Response time (tA) ≤ 25 ns Max. mains-side overcurrent protection ≤ 100 ns Temporary overvoltage (TOV) [L-N] (UT) – Characteristic 440 V / 120 min. – withstand Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic 1200 V / 200 ms – withstand Operating temperature range (TU) -40 °C ... +80 °C Operating state / fault indication green / red Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) 1.5 mm2 solid / flexible Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) 35 mm2 stranded / 25 mm2 flexible SPD Specification Fuse Part No. Rated Current (A) Power loss (W) Pre-arcing l2t -value (A2s) Total l2t -value at 240V (A2s) Total l2t -value at 440V (A2s) 20-001-13/160A 160A 11.2 78,500 139,600 226,600 Fuse Specification 300mm 135mm 400mm
N To equipment/ installation to be protected Supply PE N 160A Fuse 160A Fuse 160A Fuse Neutral Terminal As per clause 534.4.8 in the IET Wiring Regulations, when connecting an SPD in parallel, the optimal connection is a "V-type" as below . Whenever this is not feasible, and SPD is connected as above, the maximum cable length to the SPD must not exceed 0.5m Connections from equipment/installation to be protected 160A Fuse 160A Fuse 160A Fuse Neutral Terminal L1 L2 L3 PE N SPD Indicators Green = OK Red = Replace Fuse Indicators Red = OK White = Replace All indicators must be checked on a regular basis Connections All connections ( including factory made) must be checked for the correct tightness (4Nm), prior to the commissioning of the electrical installation and on a regular basis Fuse holder M8 Neutral Terminal M8 Earth Stud M8 PE - SPD Tunnel 35mm