DATASHEET SEARCH SITE | WWW.ALLDATASHEET.COM

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 16

Technical content

IB ST (ZF) 24 PT 100 4/4 01/2000Data Sheet 5080C Figure 1 IB ST 24 PT 100 4/4 module This data sheet is intended to be used in conjunction with the IBS SYS PRO UM E User Manual. Ground the mounting rail. The module is grounded by installing it on the mounting rail. Terminal Assignment Local Diagnostic and Status Indicators FU SE INTER B US US UL CC BA 4 RTD Inputs , Module Ident.: 123 IB STME 24 PT 100 4/4 , Ord.No.: 2750138 00 01 02 03 04 05 06 07 08 09 10 5080C001 1 234 5678 9 10 11 12 13 14 15 16 3217 18 19 20 21 22 23 24 25 26 27 28 29 3130 6449 50 51 52 53 54 55 56 57 58 59 60 61 6362 4833 34 35 36 37 38 39 40 41 42 43 44 45 4746 Signal Terminal +24 V supply 33 and 36 Ground of the supply (^) 49 and 52 Functional earth ground (FE) 48 and 64 Channel 12 34 Sensor power 2 and and and and Sensor current 1 and and and and Shield 20 24 28 32 Not used; do not wire! 17 to 19, 21 to 23, 25 to 27, and 29 to 31 Des. Color Meaning UL Green Supply voltage for the electronics module CC Green Cable check BA Green Bus active US Green 24 V I/O supply voltage 5080C000 Analog Input Module with 4 Channels for the Connection of Resistance Temperature Detectors (RTDs)

IB ST (ZF) 24 PT 100 4/4 2 5080C Internal Circuit Diagram Figure 2 Internal wiring of the module terminals 33 36 49 52 D i f f er ent i al c hannel m u l t i p l e x e r F i l t er and pr ot ec t i v e c i r c ui t s S i gnal c ondi t i oni ng Di g i t a l out put to µ P +U B +U S U+ I+ P E pot ent i a l 50 80 C 0 0 4 +2 4 V D C +5 V D C 17 18 19 20 12 3 4 21 22 23 24 25 26 27 28 29 30 31 32 56 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 F U S E C o upl i ng net w or k ( i nt er nal ) C o upl i ng net w or k ( i nt er nal ) C o upl i ng net w or k ( i nt er nal ) C o upl i ng net w or k ( i nt er nal ) I1 - I 2 - I3 - I 4 - C h ann el 1

IB ST (ZF) 24 PT 100 4/4 5080C 3 Electrical Isolation of the Function Areas Figure 3 Electrical isolation of the function areas Connection Examples Connection of the Supply Voltage and Potential Jumpering Figure 4 Connection of the supply voltage Potential jumpering in the screw- clamp module: If you want to connect more module , an external jumper is required between the terminals 33 and 36 (Us), 49 and 52 (^). 24 V I / O i n t e r f ace B u s i n t e r f ace ( µ P a n d Su PI ) I N T E RBUS lo c a l b u s ( O U T )

24 V D C

A B E l e c t r ic a l is o l a t io n bet w een ar ea A and ar ea B I N T E RBUS l o cal b u s ( I N ) 5 V F U S E I NT E R B US UL CC BA I B S T M E 2 4 P T 10 0 4/ 4 , O r d. N o . : 27501 38 + _ To n e x t m o d u l e S c r e w - c l am p t e r m i n al m o dul e I B S T 24 P T 100 4/ 4 F U S E I NT E R B US UL CC BA 49 52 33 36 + _ S p r i ng- c l am p t e r m i n al m o dul e I B S T Z F 24 P T 100 4/ 4

24 V D C 24 V D C

S u p p l y v o l t a g e w i th s e p a r a te wi r e s f o r each m o d u l e I B S T M E 2 4 P T 10 0 4/ 4 , O r d. N o . : 27501 38

IB ST (ZF) 24 PT 100 4/4 4 5080C Typical Sensor Connections Figure 5 Sensor connection in 2-, 3-, and 4-wire termination Always connect sensors using shielded, twisted-pair cables. Connect the shield directly to the terminals 20, 24, 28, or 32. Additional wiring is not necessary. Connect the shield of the sensor with PE potential. 4 anal og I nput , 0 - 10 V / 4. . . 20 m A M odul e I dent . : 126 I+ U+ U- I- I+ U+ U- I- I+ U+ U- I- I+ U+ U- I- 12 3 45 6 7 89 10 11 13 12 14 15 16 17 18 20 19 21 22 23 24 25 27 26 28 29 30 31 32 4 R T D I nput s , M odul e I dent . : 123 50 80C 0 0 5 00 01 02 03 04 05 06 07 08 09 10 JJ J 2- w i r e t e r m i nat i o n 3- w i r e t e r m i nat i o n ( w i t hout i n t e r nal c o m p ens at i o n of t he m eas ur i ng c o nduc t o r r e s i s t anc es ) 4- w i r e t e r m i nat i o n

IB ST (ZF) 24 PT 100 4/4 5080C 5 INTERBUS IN Process Data Word Figure 6 Sequence of the four INTERBUS IN process data words in the INTERBUS ring and representation of the bits of a process data word Bit Assignment of the INTERBUS IN Process Data Word The 16 bits of the calculated measured value (16-bit ADC resolution) are used according to the following table. Bit 15 is the sign bit (SB). Celsius Scale (Table on page 6) The permissible temperature ranges for the characteristic curves are marked in the table on page 6 in the first three columns. The temperatures range from -200°C to +850°C for Pt 100 sensors and Pt 1000 sensors. The sensor characteristic curves for Ni 100 and Ni 1000 sensors range from -60°C to +250°C (DIN characteristic) and from -60°C to +200°C (SAMA characteristic). Temperature values outside the permissible range cause the error code E004 hex of the corresponding channel to be indicated. Fahrenheit Scale (Table on page 7) The permissible temperature ranges for the characteristic curves are marked in the table on page 7 in the first three columns. The temperatures range from -328°F to +1562°F for Pt 100 sensors and Pt 1000 sensors. The sensor characteristic curves for Ni 100 and Ni 1000 sensors range from -76°F to +482°F (DIN characteristic) and from -76°F to +342°F (SAMA characteristic). Temperature values outside the permissible range cause the error code E004 hex of the corresponding channel to be indicated. C h annel 1 MS B LS B 0 14 13 12 11 10 9 8 7 6 5 4 3 2 1 C h annel 2 C h annel 3 Ch a n n e l 4 5080C 006 A D C m e as ur ed v a l u e ( 1 6 bi t s ) P r oc es s dat a w o r d 1 S i gn bi t P r oc es s dat a w o r d 4 P r oc es s dat a w o r d 2 P r o c e s s dat a w o r d 3

IB ST (ZF) 24 PT 100 4/4 6 5080C Celsius Scale Sensor Temperature Process Data Word Decimal Hexadecimal Binary +3276.7°C +32767 7FFF 0111 1111 1111 1111 +1000.0°C +10000 2710 0010 0111 0001 0000 Pt 100/Pt 1000 +850.0°C +8500 2134 0010 0001 0011 0100 Ni100/Ni 1000 DIN characteristic +250.0°C +2500 09C4 0000 1001 1100 0100 Ni 100/Ni 1000 SAMA characteristic +200.0°C +2000 07D0 0000 0111 1101 0000 +100.0°C +1000 03E8 0000 0011 1110 1000 +10.0°C +100 0064 0000 0000 0110 0100 +1.0°C 10 000A 0000 0000 0000 1010 +0.1°C 1 0001 0000 0000 0000 0001 0.0°C 0 0000 0000 0000 0000 0000 -0.1°C -1 FFFF 1111 1111 1111 1111 -1.0°C -10 FFF6 1111 1111 1111 0110 -10.0°C -100 FF9C 1111 1111 1001 1100 -60.0°C -600 FDA8 1111 1101 1010 1000 -100.0°C -1000 FC18 1111 1100 0001 1000 -200.0°C -2000 F830 1111 1000 0011 0000 -273.1°C -2731 F555 1111 0101 0101 0101

IB ST (ZF) 24 PT 100 4/4 5080C 7 Fahrenheit Scale Sensor Temperature Process Data Word Decimal Hexadecimal Binary +3276.7°F +32767 7FFF hex 0111 1111 1111 1111bin Pt 100/Pt 1000 +1562.0°F +15620 3D04 hex 0011 1101 0000 0100bin +1000.0°F +10000 2710 hex 0010 0111 0001 0000bin Ni100/Ni 1000 DIN characteristic +482.0°F +4820 12D4 hex 0001 0010 1101 0100bin Ni 100/Ni 1000 SAMA characteristic +392.0°F +3920 0F50 hex 0000 1111 0101 0000bin +100.0°F +1000 03E8 hex 0000 0011 1110 1000bin +10.0°F +100 0064 hex 0000 0000 0110 0100bin +1.0°F 10 000A hex 0000 0000 0000 1010bin +0.1°F 1 0001 hex 0000 0000 0000 0001bin 0.0°F 0 0000 hex 0000 0000 0000 0000bin -0.1°F -1 FFFF hex 1111 1111 1111 1111bin -1.0°F -10 FFF6 hex 1111 1111 1111 0110bin -10.0°F -100 FF9C hex 1111 1111 1001 1100bin -76.0°F -760 FD08 hex 1111 1101 0000 1000bin -100.0°F -1000 FC18 hex 1111 1100 0001 1000bin -328.0°F -3280 F330 hex 1111 0011 0011 0000bin -459.6°F -4596 EE0C hex 1110 1110 0000 1100bin +3276.7°F +32767 7FFF hex 0111 1111 1111 1111bin

IB ST (ZF) 24 PT 100 4/4 8 5080C Error Messages In normal mode, every process data input word contains the temperature value of the corresponding channel. When an error occurs on a channel or module, a code is written to the corresponding input word that indicates the error cause. If the value E0xxh occurs in the process data this is not a measured value but an error message. Figure 7 Bit assignment of the error code Checking the Supply Voltage The I/O supply voltage is permanently monitored. If the voltage value is outside the predefined range a module error message is released. The error code E008 hex is entered into the process data input words instead of the temperature values. Checking the Data in the Non-Volatile Memory The configuration is not stored in the volatile memory of the EEPROM. If the configuration of the EEPROM is invalid, a module error message is released and the error code E002 hex is written to all process data input words. Monitoring Converter Activities A timeout function checks the analog to digital converter (ADC). If the ADC fails, a module error message is released and the error code E010 hex is entered in all process data input words. 15 14 13 12 11 10 9 87 65 4 3 2 10 Bi t Op e n c i r c u i t 50 80C 009 E0 hex R e a d e rro r i n E E P R O M O u t of m e as ur i ng r ange S uppl y v o l t age U S not pr es ent A D C def ec t i v e I n v a l i d c o nf i gur at i o n Re s e r v e d

IB ST (ZF) 24 PT 100 4/4 5080C 9 INTERBUS OUT Process Data Word HIGH and LOW Byte of the First Process Data Output Word Figure 8 HIGH and LOW byte of the first process data output word The module can be configured with the INTERBUS master. For this, only the LOW byte of the first process data output word is used. The configuration is valid for all four channels. The process data output words of channels 2, 3, and 4 are not evaluated. During configuration, the measured temperature values continue to be entered in the process data input words of channels 2, 3, and 4 (for channel 1 see note below). The format changes with every new configuration. Possible Configurations in the LOW Byte Figure 9 Possible configurations in the LOW byte The configuration is stored in the non-volatile memory of the EEPROM and is saved when the supply voltage is disconnected. After the configuration is read/written, the 0000 hex value must be written to the first process data output word. This causes the first channel to be reset to measuring operation. In the first process data input word, the measured temperature value is transmitted. The default upon module delivery is that all bits of the configuration bytes are set to zero. This leads to the following configuration: Process data format: °C, standard of the characteristic curve: DIN IEC 60751, sensor type: Pt 100, filter frequency: 50 Hz 15 14 13 12 11 10 9 87 65 4 3 2 10 Bi t HI G H b y t e LO W by t e 50 80C 0 0 7 7 6 5 4 3 2 1 0 Bi t S ens or t y pe 5080C 008 000 - P t 100 001 - P t 1000 010 - N i 100 011 - N i 1000 100 - N i 1000 ( L a n d i s & G y r ) S t andar d 0 - D I N I E C 751 ( P t ) DI N 4 3 7 6 0 ( N i ) 1 - SAM A

00 Un i t

( s uppr es s i on) 0 - 50 H z 1 - 16 2 3 Hz

IB ST (ZF) 24 PT 100 4/4 10 5080C Assignment of the HIGH and LOW Byte in the First Process Data Output Word The control system transmits a request to the module to read or write the configuration through a corresponding process data output word. The module confirms this process through a corresponding process data input word. Read configuration Write configuration Adresses for Error Messages and Configuration Programming Data HIGH Byte LOW Byte Output word 80 hex 00hex Input word Result OK 80 hex Previous configuration Result error 88 hex Previous configuration HIGH Byte LOW Byte Output word 81 hex New configuration Input word Result OK 81 hex New configuration Result error 89 hex Previous configuration Status Process Data Word Decimal Hexadecimal Binary Error messages -7937 E0FF 1110 0000 1111 1111 -8192 E000 1110 0000 0000 0000 Configuration -32257 81FF 1000 0001 1111 1111 -32768 8000 1000 0000 0000 0000 ID code 7B hex (123dec) Output address area 8 bytes Length code 4 hex Parameter channel (PCP) 0 bytes Input address area 8 bytes Register length 8 bytes

IB ST (ZF) 24 PT 100 4/4 5080C 11 Assignment of the Module Terminals to the INTERBUS Reference INTERBUS reference Word Word x B i t 1 5 1 4 1 3 1 2 1 1 1 0 9876543210 Byte Byte 0 Byte 1 B i t 7654321076543210 Module terminals channel 1 Sensor current (+) Sign bit Terminal 1 Sensor power (+) Terminal 2 Sensor power (-) Terminal 3 Sensor current (-) Terminal 4 Shield Terminal 20 Module terminals channel 2 Sensor current (+) Sign bit Terminal 5 Sensor power (+) Terminal 6 Sensor power (-) Terminal 7 Sensor current (-) Terminal 8 Shield Terminal 24 Module terminals channel 3 Sensor current (+) Sign bit Terminal 9 Sensor power (+) Terminal 10 Sensor power (-) Terminal 11 Sensor current (-) Terminal 12 Shield Terminal 28 Module terminals channel 4 Sensor current (+) Sign bit Terminal 13 Sensor power (+) Terminal 14 Sensor power (-) Terminal 15 Sensor current (-) Terminal 16 Shield Terminal 32

IB ST (ZF) 24 PT 100 4/4 12 5080C Technical Data General Housing dimensions (width x height x depth) 118 mm x 116 mm x 117 mm Operating mode Process data operation with 4 words Connection type of the sensors 2-, 3-, or/and 4-wire technology Total power consumption 2.4 W, typical Permissible operating temperature -25°C to 55°C (-13°F to +131°F) Permissible storage temperature -25°C to +75°C (-13°F to +167°F) Degree of protection IP 20, DIN 40050, IEC 60529 Class of protection Class 3 VDE 0106, IEC 60536 Humidity 75% on average, 85% occasionally, no condensation Air pressure (operation) 80 kPa to 106 kPa, 2000 m (6562 ft.) above sea level Electrical isolation Test voltage Bus/inputs 500 V AC, 1 min., 50 Hz Supply voltage/inputs 500 V AC, 1 min., 50 Hz Supply voltage/protective conductor 500 V AC, 1 min., 50 Hz I/O voltage/protective conductor 500 V AC, 1 min., 50 Hz Emitted interference EN 50081-2, Class A Processor monitoring Watchdog circuit Preferred installation position Panel mounting Protective ground Via DIN rail Weight 540 g, typical Interface INTERBUS ST interface ST cable (supplied with the module)

IB ST (ZF) 24 PT 100 4/4 5080C 13 Power Consumption Communications power 9 V Current consumption from the local bus 85 mA, typical; 100 mA, maximum Power consumption from the local bus 800 mW, typical I/O supply voltage U S 24 V DC Current consumption of US 65 mA, typical; 85 mA, maximum Power consumption from power pack and application side (24 V supply)

1.5 W, typical

2.0 W, maximum

I/O Supply Voltage (US) Nominal value 24 V DC Permissible ripple 3.6 V pp within the permissible voltage range Permissible voltage range (including ripple) 18.5 V DC to 30.5 V DC Current consumption of US 65 mA, typical Electrical isolation With DC/DC converter Test voltage 500 V AC, 50 Hz, 1 min. Protection against polarity reversal Via diode connected in series Surge voltage protection Fuses in the terminal block base IBS TR5 0,4 AT Transient protection Yes Failure detection Yes Power consumption from power supply unit and application side (24 V supply)

IB ST (ZF) 24 PT 100 4/4 14 5080C Analog Inputs for Temperature Sensors (RTD) Number 4 Available sensor types Pt 100, Pt 1000 Ni 100, Ni 1000 Standards for characteristic curves DIN IEC 60751 (Pt 100, Pt 1000) DIN 43760 (Ni 100, Ni 1000) SAMA RC 21-4-1966 (Pt 100, Ni 100 corresponds to Type I) Landis & Gyr (Ni 1000) Temperature measuring unit Celsius or Fahrenheit scale Temperature measuring range (value range)-273,1°C to 3276.7°C on Celsius scale -459.6°F to 3276.7°F on Fahrenheit scale Resolution of the measured values 0.1°C corresponds to 0.1 K on the Celsius scale 0.1°F corresponds to 0.056K on the Fahrenheit scale Temperature-proportional, linearized Resolution of the ADC 16 bits Measuring principle Sigma-delta method Representation of output value 16-bit two's complement Sensor current 0.2 mA Basic error limit ±0.003% of the value range (±0.1°C) Temperature drift ±0.009% of the value range (±0.3°C) Typical duration of a measuring cycle depending on the number of channels connected with 50 Hz suppression 1 channel: 258 ms 2 channels: 444 ms 3 channels: 630 ms 4 channels: 816 ms Typical duration of a measuring cycle depending on the number of channels connected with

16.67 Hz suppression

1 channel: 618 ms 2 channels: 1164 ms 3 channels: 1710 ms 4 channels: 2256 ms

IB ST (ZF) 24 PT 100 4/4 5080C 15 All percentage data refers to the entire value range of the module ranging from -273.1°C to +3276.7°C. Module Error Messages Failure of the internal I/O supply voltage (+5 V DC) Yes Breakdown of fuse F1 for the I/O supply voltage Yes Breakdown of the external I/O supply voltage US of 24 V DC Yes Analog/digital converter defective Yes Content of the EEPROM invalid Yes Configuration invalid Yes Open circuit detection No (error message in the process data input word) Tolerances Influenced by Electromagnetic Fields Type of electromagnetic interference Deviation of the measured temperature value Relative Absolute Radiated-noise immunity according to IEC 60801-3: 1984 (field strength 10 V/m) < ±0.3% < ±10.0°C Radiated-noise immunity according to IEC 60801-3: 1984 (field strength 3 V/m) < ±0.005% < ±0.2°C Conducted high-frequency interference (0.15 MHz to

80 MHz) according to IEC 60801-6, Class 3

(ENV 50141: 1993) < ±0.015% < ±0.5°C Transient interferences (burst) according to IEC 60801-4 Class 4 up to 1000 V No deviation No deviation Transient interferences (burst) according to IEC 60801-4 Class 4 from 1000 V to 2000 V < ±0.5% < ±18.0°C

IB ST (ZF) 24 PT 100 4/4 16 5080C © Phoenix Contact 01/2000 TNR 92 65 82 0 Ordering Data Description Order Designation Order No. Analog input module (screw-clamp terminals) IB ST 24 PT 100 4/4 27 52 76 7 Analog input module (spring-clamp terminals) IB ST ZF 24 PT 100 4/4 27 50 95 0 Electronics module IB STME 24 PT 100 4/4 27 50 13 8 Replacement terminal block (screw-clamp terminals) IB STTB 24 PT 100 4/4 27 51 78 4 Replacement terminal block (spring-clamp terminals) IB STTB ZF 24 PT 100 4/4 27 19 15 3 Fuses (0.4 AT) IBS TR5 0,4 AT 27 53 47 8