Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Lightning current arrester / surge protective device for 2-pos. isolated and grounded 1,000 V DC PV voltage systems, for DIN rail mounting, 3-pos. base element, three pluggable temperature- monitored protective elements, status message at each plug. Your advantages Quality proven millions of times over in the widest range of applications• Rapid installation with bridges, thanks to industry-standard overall width of 1 HP Easy testing and insulation measurement, thanks to pluggable protection modules Commercial data Item number 2801160 Packing unit 1 pc Minimum order quantity 1 pc Sales key CL01 Product key CL1152 Catalog page Page 50 (C-4-2019) GTIN 4046356714334 Weight per piece (including packing) 401.2 g Weight per piece (excluding packing) 378.94 g Customs tariff number 85363030 Country of origin DE VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 1 (9)

Note The device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area. Product properties Product type PV arrester Product family VALVETRAB MS PV I / IIIEC test classification PV T1 / T2 EN type T1 / T2 IEC power supply system DC Type DIN rail module, two-section, divisible Distance between live and grounded parts 8 mm Installation location Indoor Installation location of the disconnect device Internal Accessibility Accessible Connection configuration Y configuration SPD failure behavior OCFM (Open-Circuit Failure Mode) Surge protection fault message optical Insulation characteristics Overvoltage category III Pollution degree 2 Connection data Connection method Screw connection Screw thread M5 3 Nm (1.5 mm² ... 16 mm²)Tightening torque 4.5 Nm (25 mm² ... 35 mm²) Stripping length 16 mm Conductor cross section flexible 1.5 mm² ... 25 mm² Conductor cross section rigid 1.5 mm² ... 35 mm² Conductor cross section AWG 15 ... 2 Connection method Fork-type cable lug Conductor cross section flexible 1.5 mm² ... 16 mm² Dimensions VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 2 (9)

Width 53.4 mm Height 89.8 mm Depth 65.7 mm (incl. DIN rail 7.5 mm) Horizontal pitch 3 Div. Material specifications Color black (RAL 9005) Flammability rating according to UL 94 V-0 CTI value of material 600 PA 6.6-FRInsulating material PBT-FR Material group I PA 6.6-FRHousing material PBT-FR Mechanical properties Mechanical data Open side panel No Protective circuit (L+) - (L-) (L+) - PE Mode of protection (L-) - PE Direction of action (L+)-PE & (L-)-PE & (L+)-(L-) Rated load current IL 80 A ≤ 20 µA DCResidual current IPE ≤ 350 µA AC Standby power consumption PC ≤ 25 mVA Nominal discharge current In (8/20) µs 15 kA Maximum discharge current Imax (8/20) µs 40 kA Impulse discharge current (10/350) µs, charge 2.5 As Impulse discharge current (10/350) µs, specific energy 6.25 kJ/Ω Impulse discharge current (10/350) µs, peak value limp 5 kA Total discharge current Itotal (8/20) µs 40 kA Total discharge current Itotal (10/350) µs 5 kA Voltage protection level Up ≤ 3.5 kV ≤ 3.5 kV (at In) ≤ 2.9 kV (at 5 kA) Residual voltage Ures VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 3 (9)

≤ 3.2 kV (at 10 kA) ≤ 3.7 kV (at 20 kA) ≤ 4.1 kV (at 30 kA) ≤ 4.6 kV (at 40 kA) Response time tA ≤ 25 ns PV protective circuit Connection configuration Y configuration SPD failure behavior OCFM (Open-Circuit Failure Mode) Protective circuit DC voltage side (DC) Open circuit voltage UOCSTC ≤ 975 V DC Maximum discharge current Imax (8/20) µs 40 kA Response time tA ≤ 25 ns Impulse discharge current (10/350) µs, charge 2.5 As Impulse discharge current (10/350) µs, specific energy 6.25 kJ/Ω Impulse discharge current (10/350) µs, peak value limp 5 kA Total discharge current Itotal (8/20) µs 40 kA Total discharge current Itotal (10/350) µs 5 kA Insulation resistance Riso > 5 GΩ (at 500 V DC) Nominal discharge current In (8/20) µs 15 kA Rated load current IL 80 A Continuous operating current ICPV < 20 µA Maximum continuous operating voltage UCPV 1170 V DC Short-circuit current rating ISCPV 2000 A ≤ 3.5 kV (at In) ≤ 2.9 kV (at 5 kA) ≤ 3.2 kV (at 10 kA) ≤ 3.7 kV (at 20 kA) ≤ 4.1 kV (at 30 kA) Residual voltage Ures ≤ 4.6 kV (at 40 kA) ≤ 20 µA DCResidual current IPE ≤ 350 µA AC Voltage protection level Up ≤ 3.5 kV Standby power consumption PC ≤ 25 mVA Environmental and real-life conditions Ambient conditions Degree of protection IP20 (only when all terminal points are used) Ambient temperature (operation) -40 °C ... 80 °C Ambient temperature (storage/transport) -40 °C ... 80 °C Altitude ≤ 2000 m (amsl) Permissible humidity (operation) 5 % ... 95 % VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 4 (9)

Shock (operation) 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation) 7.5g (5-500 Hz/2.5 h/XYZ) Approvals UL specifications Maximum continuous operating voltage MCOV 1170 V DC Short-circuit current rating (SCCR) 50 kA Voltage protection rating VPR 3 kV Nominal discharge current In 10 kA (L+) - (L-) (L+) - G Mode of protection (L-) - G Nominal voltage 1170 V DC Power distribution system DC PV SPD Type 1CA UL connection data Tightening torque 30 lbf-in. Conductor cross section AWG 14 ... 2 Standards and regulations Standards/specifications EN 61643-31 Note 2019 Standards/specifications IEC 61643-31 Note 2018 Mounting Mounting type DIN rail: 35 mm VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 5 (9)

4465,7 89,8 53,4 Circuit diagram L+ L– VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 6 (9)

To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/2801160  cUL Recognized Approval ID: FILE E 330181  UL Recognized Approval ID: FILE E 330181  EAC Approval ID: RU C-DE.*09.B.00169  KEMA-KEUR Approval ID: 71-123544 REV.2  IECEE CB Scheme Approval ID: NL-81006/A1 CCA Approval ID: NTR-NL 7937 UAE-RoHS Approval ID: 23-10-88705 VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 7 (9)

ECLASS-13.0 27171401 ETIM ETIM 9.0 EC000381 UNSPSC UNSPSC 21.0 39121620 VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 8 (9)

Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes, No exemptions China RoHS EFUP-EEnvironment friendly use period (EFUP) No hazardous substances above the limits EU REACH SVHC REACH candidate substance (CAS No.) No substance above 0.1 wt% Phoenix Contact 2025 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA

586 Fulling Mill Road

Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com VAL-MS-T1/T2 1000DC-PV/2+V - Lightning/surge arrester type 1/2 2801160 https://www.phoenixcontact.com/us/products/2801160 Mar 27, 2025, 7:49 AM Page 9 (9)