© PHOENIX CONTACT - 10/2005Data Sheet INTERFACE 101810_01_en 1PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg Germany Phone: +49 - 52 35 - 30 0 Fax: +49 - 52 35 - 34 12 00 www.phoenixcontact.com www.phoenixcontact.com/salesnetwork REL-MR-...21
Description
With the REL-MR-...21 plug-in miniature relay, the high end of the latest relay developments are made available to the innovative PLC range. Despite its compact dimensions, the device is rugged and equipped with features which are not normally found in plug-in relays: –5 m m w i d e – High level of operational safety – Cadmium-free, environmentally friendly power contacts up to 250 V AC/6 A – Available with gold plating for low power switching levels (mA) as an option –4 k V rms electrical isolation between input and output – Safe isolation according to EN 50178 – High degree of protection, up to IP67 depending on the type The miniature relays are not just designed to be used as components for the PLC range, but can also be used as PCB relays in industrial products of any kind, such as: – Interface technology, timer relays – Measuring and control technology – PLC and bus I/O modules Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at http://www.download.phoenixcontact.com/general/7000_en_00.pdf This data sheet is valid for the following products: Miniature Relays With PDT for Loads up to 6 A
REL-MR-...21 101810_01_en PHOENIX CONTACT 2 Ordering Data Technical Data Plug-In Miniature Relays With Power Contact Description Type Order No. Pcs./Pkt. Plug-in miniature relays with power contact, 4.5 V DC input voltage REL-MR- 4,5DC/21 29 61 36 7 10 Plug-in miniature relays with power contact, 12 V DC input voltage REL-MR- 12DC/21 29 61 15 0 10 Plug-in miniature relays with power contact, 18 V DC input voltage REL-MR- 18DC/21 29 61 38 3 10 Plug-in miniature relays with power contact, 24 V DC input voltage REL-MR- 24DC/21 29 61 10 5 10 Plug-in miniature relays with power contact, 60 V DC input voltage REL-MR- 60DC/21 29 61 11 8 10 Plug-In Miniature Relays With Multi-Layer Contact Description Type Order No. Pcs./Pkt. Plug-in miniature relays with multi-layer contact, 4.5 V DC input voltage REL-MR- 4,5DC/21AU 29 61 37 0 10 Plug-in miniature relays with multi-layer contact, 12 V DC input voltage REL-MR- 12DC/21AU 29 61 16 3 10 Plug-in miniature relays with multi-layer contact, 18 V DC input voltage REL-MR- 18DC/21AU 29 61 49 3 10 Plug-in miniature relays with multi-layer contact, 24 V DC input voltage REL-MR- 24DC/21AU 29 61 12 1 10 Plug-in miniature relays with multi-layer contact, 60 V DC input voltage REL-MR- 60DC/21AU 29 61 13 4 10 Nominal input voltage UN 4.5 V DC 12 V DC 18 V DC 24 V DC 60 V DC Permissible range (with reference to UN) See "Permissible Operating Voltage Range" on page 4 Typical input current at UN 38 mA 14 mA 9 mA 7 mA 3 mA Typical response time at UN 5 ms 5 ms 5 ms 5 ms 5 ms Coil resistance at 20°C 119 Ω ±10% 848 Ω ±10% 1906 Ω ±10% 3390 Ω ±10% 20500 Ω ±15% Contact type Single contact, 1 PDT Single contact, 1 PDT Contact material AgSnO Ag alloy, hard gold-plated1 Maximum switching voltage 250 V AC/DC 30 V AC/36 V DC (250 V AC/DC) Minimum switching voltage 12 V AC/DC 100 mV (12 V AC/DC) Limiting continuous current 6 A 50 mA (6 A) Maximum inrush current On request 50 mA Minimum switching current 10 mA 1 mA (10 mA) Maximum shutdown power (ohmic load), (see "Shutdown Power" on page 4)
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
250 V AC
1.2 W (140 W) (20 W) (18 W) (23 W) (40 W) (1500 VA) Minimum switching power 120 mW 100 µW (120 mW) 1 If the specified maximum values are exceeded, the gold coating will be damaged. In subsequent operation, the maximum values given in brackets will apply. This can then result in reduced service life compared to simple power contacts.
REL-MR-...21 101810_01_en PHOENIX CONTACT 4 Diagrams Permissible Operating Voltage Range A Maximum permissible continuous voltage Umax with limiting continuous current on the contact side B Minimum permissible relay operate voltage Uop following pre-excitation Service Life Reduction Factor (with varying cos ϕ) Electrical Service Life A 250 V AC, ohmic load B 250 V AC, cos ϕ = 0.4 C 24 V DC, ohmic load Shutdown Power A AC, ohmic load B DC, ohmic load © PHOENIX CONTACT 10/2005 2.5 1.5 0.5 0 10 20 30 40 50 60 70 80 90 100 101810A001 A B Ambient operating temperature [°C] Coil voltage U/UN 101810A004 1.0 0.9 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ Reduction factor 101810A002 12 3 4 5 6 A B C Switching current [A] Cycles 101810A003 0.1 AB Switching voltage [V] Switching current [A]