407C ATC | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 3
Technical content
Automatic Timing & Controls 800.727.5646 atcdiversified.com 407C Series MULTIPLE TIMING MODES: The 407 is available with selectable On- Delay, Off-Delay or Interval timing modes. These timing modes energize a set of DPDT output contacts. When in the On-Delay mode, the 407 be- gins timing when the timer is energized. In On-Delay mode, the contacts transfer at time out. When in the Off-Delay mode, the 407 begins timing when the Start input is de-energized. In Off-Delay mode, the contacts transfer at time out. When in the Interval mode, the contacts transfer when the timer is energized. In Interval mode, the contacts release at time out. UNIVERSAL POWER SUPPLY: All 407 timers can be powered using 24-240 VAC or 24 VDC power, greatly simplifying ordering and inventory management of replacement units. HIGH ACCURACY: The 407’s timing circuit is not a simple RC circuit. It utilizes the sophistication of a proprietary integrated circuit that includes counting technology along with a stable oscillator to provide repeatable time delays. 1/16 DIN HOUSING: The 48mm2 (1/16 DIN) housing is compact. The 407 is mounted in an 11-pin round socket. With an optional mounting clip, the 407 can be panel mounted. The Dial on the 407 is extra-large and is easy to read. When fractional ranges are selected, decimal points are clearly indicated. The Mode SELECT AND RANGE select switches are located on the side of the unit, so that when panel mounted, these switches are not acces - sible to the operator. This tamper proof feature prevents unauthorized or hazardous changes to the timing mode and range from being made. CYCLE PROGRESS INDICATION: The 407 LED indicator provides a unique and effective method of cycle progress indication. Off before timing, the LED blinks at an ever increasing rate as the cycle progresses; once every 3-1/2 seconds during the first 10% of the cycle, twice during the second 10%, and so on. At time out, the LED pulses at a high rate. (In the 1, 5, 10 and 50 second ranges, the LED is Off before timing, steady On during timing, and pulsing On after time-out). Timing begins when the start switch is closed (ON-delay and INT modes) or opened (OFF-delay mode). This starts an oscillator which runs at a frequency determined by the time setting. A fixed number of counts from the oscillator determines the end of the timing cycle. The time required to accomplish this depends upon the oscillator frequency. During timing, An LED located on the dial face blinks. For the first 10% of the cycle, the LED repeatedly blinks once followed by a pause. For the second 10%, it blinks twice and so on indicating he cycle progress. The LED flashes rapidly and continuously after time out. ON-DELAY MODE: At time out, the DPDT relay transfers its contacts. These contacts remain transferred until the start switch is opened or power is removed by some other means. INTERVAL MODE: When the start switch is closed, the DPDT relay transfers its contacts. The contacts remain transferred until time out. The timer will not start again until the start switch is opened or power is removed by some other means. The 407B then resets and is ready for another cycle. OFF-DELAY MODE: Power must be applied to the timer before and during timing (terminals #10 & 2). Upon closure of the start switch, the DPDT relay transfers its contacts. The timing begins when the start switch is opened. The relay remains energized during timing. At time out, the relay de-energizes. OPERATIONS 1/16 DIN Multi-Mode Timer
- Selectable ON-Delay/OFF-Delay/Interval Timing Modes
- Separate Start Input
- Output Contacts rated 10A at 120/240 VAC and 30 VDC
- Six Timing Ranges in a single unit
- 1 and 10 SEC, MIN, and HRS 5 and 50 SEC, MIN, and HRS
- Universal Power Supply; 24-240 VAC and 24 VDC
- 48mm 2 DIN Standard housing
- Large and easy to read dial shows decimal points
- Round (octal) socket mount or mount in panel cutout
- Range and Mode select are tamper proof when panel mounted
- Unique flashing cycle progress indication E48329 Automatic Timing & Controls 800.727.5646 atcdiversified.com Special note for Off-Delay operation: When operated from AC, the start switch must be of a dry contact type such as a relay contact or mechanical switch. When operated from DC, the start switch can be a dry contact type such as a relay contact or mechanical switch. In addition, a solid-state device may be used as long as its saturation voltage drop is less than 1.5 VDC at 50mA. The 407C Directly Replaces 407B and 407A 1/16 DIN TIMERS
SPECIFICATIONS SPECIFICATIONS (CONTINUED) WIRING MODEL NUMBER MINIMUM 2% of range, with the exception of SETTING 50 mSEC on the 1 second range SETTING ACCURACY ±5% of range RESET a 0 to 20 mSEC power interruption: guaranteed no reset. b 20 to 65 mSEC; it may reset (40 mSEC typical reset). c Over 65 mSEC guaranteed to reset. The TDR will reset properly and not start timing when subjected to an open start switch leakage of 1.5 mA or less. (Prox switch & Triac drive applications) TERMINAL #6 DC Minimum Current Rating - 50mA (START SWITCH Maximum saturated voltage drop - REQUIREMENTS 1.5 VDC OFF-DELAY) AC Minimum Current Rating - 1.5 A WEIGHT 5 oz. (140 g) MODEL 407C 3 NUMBER RANGE Six dial-selected ranges 100 (1 or 10 SEC/MIN/HRS) Six dial-selected ranges 500 (5 or 50 SEC/MIN/HRS) VOLTAGE & FREQUENCY
12 VDC E
24 to 240 VAC (50/60 Hz) F and 24 VDC
24 VDC (low inrush current for N
short-circuit protected sensors) ARRANGEMENT 11-pin ON -Delay, OFF-Delay, 3 Interval Timing Modes
FEATURES
11-Pin surface/DIN rail socket 000-825-86-00 Hold down for above socket 405-025-07-00 (Requires 2 per unit) Panel mounting bracket 405-320-02-00 Plug-in socket kit (11-pin) 314-260-07-00 MODEL 407C...F3X LED Indicator TERMINAL WIRING CAUTION: Do NOT connect terminal 6 to L1 (AC Hot or DC+). Damage to unit will result. Terminal 6 is a dry contact only! MODELS 407C100F3X ON-Delay, OFF-Delay, Interval Timing with (1) DPDT relay (1 or 10 SEC/MIN/HRS) 407C500F3X ON-Delay, OFF-Delay, Interval Timing with (1) DPDT relay (5 or 50 SEC/MIN/HRS) Both models available in 6 ranges from 1 SEC to
10 HRS or 5 SEC to 50 HRS
CONTACT Rated 10 AMPS resistive at 30 VDC or 250 VAC RATING (or less) 1/8 HP @120 VAC 1/4 HP @ 240 VAC,
240 VA @ 240 VAC
LIFE: 10 million operation with no load 100,000 operations with:
10 AMPS at 30 VDC (or less) or
10 AMPS at 250 VAC (or less)
TEMPERATURE 0° to 122°F (-18°C to 50°C) RATING MOUNTING Plug-in 11-Pin round base Options: Surface mounting socket DIN rail mounting socket Panel-mounting adapter kit Plug-on socket kit POWER Universal power supply - reverse polarity protected REQUIREMENTS Unit will accept power from 24 to 240 VAC, 50 or AC Inrush - 1.5 Amps Power required - 1.2 watts DC Maximum ripple @ 100 Hz - 5% Current required - 50mA Power required - 1.2 watts F option - Peak inrush current = 2 AMPS @ 24 VDC N option - Peak inrush current = 150 mA @ 24 VDC REPEAT Varies as a function of temperature. ACCURACY Any voltage (constant temperature): –0.5%* Any voltage (0 F to 140 F): –2.0%* *Variation from average actual time. 1/16 DIN TIMERS
Automatic Timing & Controls 800.727.5646 atcdiversified.com 407C Series DIMENSIONS (INCHES/MILLIMETERS) TYPICAL CIRCUITS Optional 11-pin Socket Part Number 000-825-86-00 *in off-delay mode, start switch must be isolated. Do NOT connect any load in parallel BEFORE START TIMING TIMED OUT O O X O = LOAD OFF X = LOAD ON ON-DELAY (MODE SWITCH IN ON-DELAY POSITION) INTERVAL (MODE SWITCH IN INTERVAL POSITION) OFF-DELAY (MODE SWITCH IN OFF-DELAY POSITION) *START/RESET Automatic Timing & Controls 800.727.5646 atcdiversified.com 1/16 DIN TIMERS