304G ATC | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 2

Technical content

Automatic Timing & Controls 800.727.5646 atcdiversified.com OPERATION The 304G solid-state percentage timer comes standard in a 120 SEC range with 15 SEC, 30 SEC, 60 SEC user configurable ranges. Addition- ally, all second ranges can become minute ranges by changing jumper J11 . The 304G is easily panel mounted with 4 screws. It utilizes an integrated circuit technology for high accuracy timing. CONTACTS: The relay contact is capable of switching 10 A to a resistive 120 VAC or 30 VDC load. It is capable of driving a 1/3 HP load at 120 VAC. CYCLE PROGRESS INDICATION: The 304G has a pilot light that is on solid during the relay off time. It blinks at a faster rate during the relay on time: once every 3.5 seconds during the first 10% of the cycle, twice during the second 10% and so on. HIGH ACCURACY: The 304G’s timing circuit is not a simple RC circuit. It utilizes the sophistication of a proprietary integrated circuit that includes counting technology along with a stable oscillator to provide repeatable time delays. CONVENIENT ADJUSTMENT: Graduated in easily read 1% increments, the 304G provides continuous adjustment of on time between 5 and 95%. The 304G comes standard in the 120 SEC range but is user configurable for the 15 SEC, 30 SEC or MIN., 60 SEC or MIN. by changing jumpers on the PC board. Each of these ranges can also be made minutes range by changing a jumper. Its solid-state circuitry repeatedly closes the SPST load switch for a percentage of the time cycle, as set on the timer dial, and opens it for the remainder of the cycle. When the dial pointer is set below 3%, the load switch stays open for the full cycle; it remains closed when the pointer is set above 98%. This is true for all seconds ranges. Minute ranges have a 0.01% minimum. If power is interrupted to the timer it will reset. When power is restored, the timer will begin a new time cycle. MODEL NUMBER MODEL NUMBER 304G Q 00 RANGE Multi-range, Jumper Selectable* 400 15/30/60/120 SEC or MIN *Factory Set to 120 Sec Range

15 SEC 004

30 SEC 006

60 SEC 007

VOLTAGE & FREQUENCY

120 VAC, 50/60 Hz Q

FEATURES

Solid-State Percentage Timer SPECIFICATIONS MODEL 304G Non Plug-In CONTACT RATINGS (non-inductive) 10A at 120 VAC TEMPERATURE RATING 32° to 120°F (0° to 50°C) SETTING ACCURACY ±5% of range 5 to 95% on time, in 1% graduations. FULL ON, FULL OFF FEATURE. When pointer is set below 3%, load switch contacts are open continuously; above 98%, contacts are closed continuously in all seconds ranges. Minute ranges have a 0.01% minimum. RANGES Standard 120 SEC range three configurable ranges of 15 SEC,

30 SEC, 60 SEC, 15 MIN, 30 MIN,

60 MIN and 120 MIN. LOAD RELAY One SPST Relay 10 Amp @ 120 VAC POWER REQUIREMENTS 120V , 50/60 Hz; 50mA running current. TERMINALS 4 screw terminals accessible at rear; wiring diagram on housing WEIGHT Net: 5.6 oz. SHIPPING: 1 lb. PERCENTAGE TIMER 304G Series IND. CONT . EQ. 101F E48329 Automatic Timing & Controls 800.727.5646 atcdiversified.com

PERCENTAGE TIMER 304G Series DIMENSIONS (INCHES) WIRING USER CONFIGURATION CHART 1 *Range of Configuration Range JP12 JP13

15 SEC ON ON

30 SEC ON OFF

60 SEC OFF OFF

120 SEC OFF ON

*For same minute ranges, install JP11 Examples: 1. Jump JP13, No Jump JP11, JP12, make a 120 SEC range. 2. Jump JP11, No Jump JP12, JP13, make a 60 minute range. REAR VIEW OF TIMER L1 L1L2 L2 LOAD JP11 JP12 JP13 JP14 ON OFF