2805402 PHOENIX | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 8

Technical content

Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Surge arrester consisting of 2-channel base element with remote indication contact and protective plugs connected in series with a varistor and a gas-filled spark gap. Your advantages Quality proven millions of times over in the widest range of applications• Rapid installation with bridges, thanks to industry-standard overall width of 1 HP Easy testing and insulation measurement, thanks to pluggable protection modules Can be used in power electronics applications and wind turbine generators (rotor) due to application-specific response behavior Commercial data Item number 2805402 Packing unit 1 pc Minimum order quantity 1 pc Sales key CL18 Product key CL1321 Catalog page Page 65 (C-4-2019) GTIN 4046356498821 Weight per piece (including packing) 251.5 g Weight per piece (excluding packing) 244.2 g Customs tariff number 85363010 Country of origin DE VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 1 (8)

For use in all low-voltage systems between L-PEN. Only for use in IT systems between L-PE if the bodies of the equipment in the low-voltage system are connected to the grounding system of the transformer station. (common grounding of the HV transformer station and the bodies of the LV consumer's installation. RE = RA according to IEC 60364-4- 442/VDE 0100-442 Figure 44D/example a) Note Uagn ≥ 2500 V Product properties Product type Surge arrester Product family VALVETRAB MS IIIEC test classification EN type T2 TNIEC power supply system IT Type DIN rail module, two-section, divisible Distance between live and grounded parts 8 mm Number of positions 2 Surge protection fault message Optical, remote indicator contact Insulation characteristics Overvoltage category III Pollution degree 2 Electrical properties Nominal frequency fN 50 Hz (60 Hz) Indicator/remote signaling Connection name Remote fault indicator contact Switching function Changeover contact 5 V AC ... 250 V ACOperating voltage

30 V DC

5 mA AC ... 1.5 A ACOperating current

1 A DC

Connection method Screw connection Screw thread M5 3 Nm (1.5 mm² ... 16 mm²)Tightening torque 4.5 Nm (25 mm² ... 35 mm²) VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 2 (8)

Conductor cross section flexible 1.5 mm² ... 25 mm² Conductor cross section rigid 1.5 mm² ... 35 mm² Conductor cross section AWG 15 ... 2 Connection method Fork-type cable lug Conductor cross section flexible 1.5 mm² ... 16 mm² Remote fault indicator contact Connection method Plug-in/screw connection via COMBICON Screw thread M2 Tightening torque 0.25 Nm Stripping length 7 mm Conductor cross section AWG 28 ... 16 Dimensions Dimensional drawing Width 35.6 mm Height 96.8 mm Depth 65.7 mm (incl. DIN rail 7.5 mm) Horizontal pitch 2 Div. Material specifications Color black (RAL 9005) Flammability rating according to UL 94 V-0 CTI value of material 600 Insulating material PA 6.6/PBT Material group I PA 6.6Housing material PBT Protective circuit L-PEMode of protection L-PEN Direction of action 1L-GND 400/690 V AC (TN-C)Nominal voltage UN

690 V AC (IT)

Nominal frequency fN 50 Hz (60 Hz) Maximum continuous voltage UC 800 V AC VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 3 (8)

Rated load current IL 80 A Residual current IPE ≤ 3 µA Standby power consumption PC ≤ 3 mVA Nominal discharge current In (8/20) µs 15 kA Maximum discharge current Imax (8/20) µs 30 kA Short-circuit current rating ISCCR 25 kA Voltage protection level Up ≤ 5 kV ≤ 3 kV (at In) ≤ 2.6 kV (at 10 kA) ≤ 2.4 kV (at 5 kA) Residual voltage Ures ≤ 2.3 kV (at 3 kA) Front of wave sparkover voltage at 6 kV (1.2/50) µs ≤ 5 kV TOV behavior at UT 1550 V AC (5 s / withstand mode) Response time tA ≤ 100 ns Max. backup fuse with V-type through wiring 80 A (gG) Max. backup fuse with branch wiring 100 A (gG) Environmental and real-life conditions Ambient conditions Degree of protection IP20 (only when all terminal points are used) Ambient temperature (operation) -40 °C ... 80 °C Ambient temperature (storage/transport) -40 °C ... 80 °C Altitude ≤ 2000 m (amsl) Permissible humidity (operation) 5 % ... 95 % Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) Standards and regulations Standards/specifications IEC 61643-11 Note 2011 Standards/specifications EN 61643-11 Note 2012 Mounting Mounting type DIN rail: 35 mm VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 4 (8)

89,8 96,8 4465,7 35,6 Circuit diagram 12 14 11 FM L VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 5 (8)

To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/2805402  IECEE CB Scheme Approval ID: AT 2905/M1  EAC Approval ID: RU C-DE.*09.B.00169 CCA Approval ID: NTR-AT 1947-A  KEMA-KEUR Approval ID: 71-148002  DNV GL Approval ID: TAE000041M  ÖVE Approval ID: 18583-001-17 UAE-RoHS Approval ID: 22-09-51251 VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 6 (8)

ECLASS-13.0 27171202 ETIM ETIM 9.0 EC000941 UNSPSC UNSPSC 21.0 39121600 VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 7 (8)

Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes, No exemptions China RoHS EFUP-EEnvironment friendly use period (EFUP) No hazardous substances above the limits EU REACH SVHC REACH candidate substance (CAS No.) No substance above 0.1 wt% Phoenix Contact 2025 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA

586 Fulling Mill Road

Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com VAL-MS 800/30 VF/FM - Type 2 surge arrester 2805402 https://www.phoenixcontact.com/us/products/2805402 Mar 25, 2025, 8:23 AM Page 8 (8)