Features

LED flashing beacon element for 24 V DC Colors: red, yellow, blue and plain Double flash Degree of protection: IP65, when installed or with cover

2 Ordering data

Description

Order No. Pcs. / Pkt. LED flashing beacon element, 24 V DC, double flash, red PSD-S OE LED FL RD 2700115 LED flashing beacon element, 24 V DC, double flash, yellow PSD-S OE LED FL YE 2700124 LED flashing beacon element, 24 V DC, double flash, clear PSD-S OE LED FL CL 2700129 LED flashing beacon element, 24 V DC, double flash, blue PSD-S OE LED FL BU 2700134

3 Technical data

Dimensions (in mm) Ø70 65,5 PSD-S OE LED FL ... 7951

00 PHOENIX CONTACT

Diameter 70.00 mm Height 65.50 mm Material Polycarbonate PC Calotte color: PSD-S OE LED FL RD red Calotte color: PSD-S OE LED FL YE yellow Calotte color: PSD-S OE LED FL CL clear Calotte color: PSD-S OE LED FL BU blue Weight 72 g Ambient temperature (operation) -20 °C ... 50 °C Degree of protection IP65, when installed or with cover Mounting position Any Connection Rubber seal pre-installed for each element Electrical data Input voltage

24 V DC

Max. 200 mA Current consumption 35 mA Optical signal type LED flashing beacon with double flash Signal frequency Approx. 1 Hz Service life, electrical max. 50,000 h Operating time 100 % Approvals / conformities Conformance with EMC directive 2004/108/EC For the latest approvals, please visit http://www.phoenixcontact.net/catalog PSD-S OE LED FL ... 7951 PHOENIX CONTACT

4 Example of a signal tower

Figure 1 Example of a signal tower Key:

1 Audible signal element

2 Optical signal element

3 Connection element

4 Assembly element

5 Assembly notes for a signal

You may use up to five signal elements in a sig- nal tower. Use only one audible element in a signal tower and position this element on top. When closing the bayonet locking system, observe the markings (see "Assembling the individual ele- ments").

6 Assembling the individual ele-

Figure 2 Assembling the individual elements " Select the elements for your application. " Connect the elements to be assembled so that the markings are aligned. " Turn the upper element in the direction of the ar- row. PSD-S OE LED FL ... 7951 PHOENIX CONTACT

7 Example for signal tower dimen-

The following figure shows the dimensions of a typical signal tower. 112 4□x□56□(=□224)408 Ø70 Figure 3 Dimensions of a signal tower (example) PSD-S OE LED FL ... 7951 00 PHOENIX CONTACT GmbH & Co. KG · 32823 Blomberg · Germany · Phone: +49-(0) 5235-3-00 PHOENIX CONTACT · P.O.Box 4100 · Harrisburg · PA 17111-0100 · USA · Phone: +717-944-130 http://www.phoenixcontact.com