https://www.phoenixcontact.com/pi/products/2320416 09/12/2020 Page 1 / 6 Energy storage - UPS-BAT/VRLA-WTR/24DC/13AH - 2320416 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Energy storage device, lead AGM, VRLA technology, 24 V DC, 13 Ah, tool-free battery replacement, automatic detection, and communication with QUINT UPS-IQ Product Description For continuous monitoring and intelligent management, there is constant communication with the QUINT UPS. Thanks to automatic detection of the energy storage, and tool-free switching during operation, quick installation is possible. The QUINT UPS with IQ technology energy storage leaves the warehouse fully charged. Your advantages Maximum buffer times at extreme temperatures Pure lead AGM technology (Absorbent Glass Mat) Key Commercial Data Packing unit 1 pc GTIN GTIN 4046356707701 Technical data Dimensions Width 172 mm Height 177 mm Depth 178 mm Ambient conditions Degree of protection IP20 Ambient temperature (operation) -25 °C ... 60 °C Ambient temperature (storage/transport) -40 °C ... 60 °C Max. permissible relative humidity (operation) ≤ 95 % Degree of pollution 2 Input data

https://www.phoenixcontact.com/pi/products/2320416 09/12/2020 Page 2 / 6 Energy storage - UPS-BAT/VRLA-WTR/24DC/13AH - 2320416 Technical data Input data Nominal input voltage 24 V DC Buffer period 50 min. (10 A) 10 min. (40 A) Output data Nominal output voltage 24 V DC Output current Imax 45 A Connection in series No Output fuse 2x 25 A ATOF 32V General IQ technology Yes Disposal Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. They can also be returned to Phoenix Contact or the manufacturer. Net weight 10.8 kg Memory medium Pure lead AGM Degree of protection IP20 Protection class III Housing material Steel sheet, zinc-plated Mounting position horizontally, on a mounting plate Standards Standard - Electrical safety EN 60950-1/VDE 0805 (SELV) Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV) Conformance/approvals UL approvals UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950-1 Shipbuilding approval DNV GL (EMC A), ABS Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally Friendly Use Period = 15; For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” Drawings

https://www.phoenixcontact.com/pi/products/2320416 09/12/2020 Page 3 / 6 Energy storage - UPS-BAT/VRLA-WTR/24DC/13AH - 2320416 Block diagram Classifications eCl@ss eCl@ss 10.0.1 27050403 eCl@ss 4.0 27040600 eCl@ss 4.1 27040600 eCl@ss 5.0 27040600 eCl@ss 5.1 27040600 eCl@ss 6.0 27040600 eCl@ss 7.0 27050403 eCl@ss 8.0 27050403 eCl@ss 9.0 27050403 ETIM ETIM 2.0 EC000382 ETIM 3.0 EC000382 ETIM 4.0 EC000357 ETIM 5.0 EC000357 ETIM 6.0 EC000357 ETIM 7.0 EC000357 UNSPSC UNSPSC 6.01 30211510 UNSPSC 7.0901 39121011 UNSPSC 11 39121011 UNSPSC 12.01 39121011 UNSPSC 13.2 26111715 UNSPSC 18.0 26111715 UNSPSC 19.0 26111715

https://www.phoenixcontact.com/pi/products/2320416 09/12/2020 Page 4 / 6 Energy storage - UPS-BAT/VRLA-WTR/24DC/13AH - 2320416 Classifications UNSPSC UNSPSC 20.0 26111715 UNSPSC 21.0 26111715 Approvals Approvals Approvals DNV GL / PRS / BV / LR / ABS / UL Listed / UL Recognized / cUL Recognized / IECEE CB Scheme / cUL Listed / EAC / cULus Recognized / cULus Listed Ex Approvals UL Listed / cUL Listed / cULus Listed Approval details DNV GL https://approvalfinder.dnvgl.com/ TAA0000265 Nominal voltage UN 500 V Nominal current IN 41 A mm²/AWG/kcmil 6 PRS http://www.prs.pl/ TE/2103/880590/16 BV http://www.veristar.com/portal/veristarinfo/generalinfo/ approved/approvedProducts/equipmentAndMaterials 41516/A0 BV LR http://www.lr.org/en 17/20032 ABS http://www.eagle.org/eagleExternalPortalWEB/ 15-GD1438179-PDA UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528

https://www.phoenixcontact.com/pi/products/2320416 09/12/2020 Page 5 / 6 Energy storage - UPS-BAT/VRLA-WTR/24DC/13AH - 2320416 Approvals UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944 cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944 IECEE CB Scheme http://www.iecee.org/ DK-29680-A1-M1-UL cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528 EAC EAC-Zulassung cULus Recognized cULus Listed Accessories Accessories Battery unit Uninterruptible power supply replacement battery - UPS-BAT-KIT-WTR 2X12V/13AH - 2908368 Replacement battery for UPS-BAT/VRLA-WTR... energy storage Fuse

https://www.phoenixcontact.com/pi/products/2320416 09/12/2020 Page 6 / 6 Energy storage - UPS-BAT/VRLA-WTR/24DC/13AH - 2320416 Accessories Fuse - SI FORM C 25 A DIN 72581 - 0913757 Flat-type plug-in fuse, type C, color code: white, nominal current: 25 A Mounting material Mounting set for securing the batteries - BATTERY MOUNTING CASE M - 1134645 Used for mounting batteries that cannot be mounted on DIN rails. Mounting set for securing the batteries - BATTERY MOUNTING KIT - 2320788 Used for mounting batteries that cannot be mounted on DIN rails. Phoenix Contact 2020 © - all rights reserved http://www.phoenixcontact.com PHOENIX CONTACT GmbH & Co. KG Flachsmarktstr. 8