104103 PHOENIX | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 16
Technical content
Features
–S p a c e - s a v i n g The TRIO-UPS combines a power supply unit and electronic switch-over unit in the same housing – Flexible Rechargeable battery module with 1.3, 3.4, 7.2 or 12 Ah – Autonomous In the event of AC mains failure, the industrial PC continues operating without interruption –T i m e - s a v i n g When the supply voltage is reapplied, the industrial PC starts automatically – Parameterizable Can be parameterized with the PC or configuration stick DANGER Never carry out work when voltage is present. The device contains dangerous live elements and high levels of stored energy. Depending on the ambient temperature and load, the housing can become very hot. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/download This data sheet is valid for all products listed under "Ordering data" on page 3. Uninterruptible power supply with integrated power supply unit
104103_en_00 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
104103_en_00 PHOENIX CONTACT 3 3O r d e r i n g d a t a
4 Technical data
4.1 I/O data
Description Type Order No. Pcs./Pkt. Uninterruptible power supply with integrated power supply unit TRIO-UPS/1AC/24DC/5 2866611 1 The TRIO-UPS/1AC/24DC/5 is supplied without a rechargeable battery module. The rechargeable battery module must be ordered separately (see accessories). Accessories Description Type Order No. Pcs./Pkt. Rechargeable battery module, 24 V DC, 1.3 Ah MINI-BAT/24DC/1.3AH 2866417 1 Rechargeable battery module, 24 V DC, 3.4 Ah QUINT-BAT/24DC/3.4AH 2866349 1 Rechargeable battery module, 24 V DC, 7.2 Ah QUINT-BAT/24DC/7.2AH 2866352 1 Rechargeable battery module, 24 V DC, 12 Ah QUINT-BAT/24DC/12AH 2866365 1 Configuration and management software UPS-CONF 2320403 1 USB data link cable between the UPS and IPC IFS-USB-PROG-ADAPTER 2811271 1 Configuration stick for parameter transfer between various TRIO-UPS/1AC/24DC/5 devices IFS-CONFSTICK 2986122 1 Input data Nominal input voltage (wide-range input) 100 ... 240 V AC Input voltage range (nominal load) 85 ... 264 V AC (< 90 V AC derating: 2.5%/V) Frequency 45 ... 65 Hz Approximate current consumption (mains operation and battery charging/ maximum) At 230 V AC At 120 V AC 0.95 A/1.1 A 1.7 A/1.8 A Inrush current limiting / I²t at 25°C typical < 44 A / < 1.3 A²s Switch-on time after applying the mains voltage At 230 V AC At 120 V AC 150 ms 200 ms Transient surge protection Varistor Internal input fuse T 6.3 A Recommended backup fuse Circuit breaker 6 A/10 A/16 A (B characteristic) Discharge current to PE 0.8 mA Output data Rise time < 100 ms Residual ripple < 10 mVPP Switching peaks < 25 mV PP Parallel connection to increase the buffer time Yes, 2 Surge protection against internal surge voltages Yes, < 35 V DC Maximum resistance to return supply 35 V DC
104103_en_00 PHOENIX CONTACT 4
4.2 Battery management
Output data in mains operation (AC input voltage present) Nominal output voltage UN 24 V DC Nominal output current, > 24 V DC constant capacity (-25°C to +70°C) 5 A Derating (above 55°C) 2.5%/K Current limit 6 A, approximately Connection of capacitive loads Yes, unlimited Control deviation < 1% (static load change 10 ... 90%) Approximate efficiency (mains operation and battery charging) At 230 V AC At 120 V AC 88% 86% Approximate power dissipation (mains operation and battery charging) At 230 V AC At 120 V AC 16 W 20 W Output data in battery operation (AC input voltage not present) Nominal output voltage UN 24 V DC Nominal output current (-25°C to +70°C) 5 A Derating (above 55°C) 2.5%/K Current limit 6 A, approximately Connection of capacitive loads Yes, 3300 µF Efficiency > 86% Power dissipation Maximum no load Maximum nominal load 2 W 4 W Maximum buffer time (adjustable per minutes) 0.5; 1; 2; 3; 5; 10; 15; 20; PC mode Overload fuse (electronic) Yes Remote shutdown Yes Battery management Charging characteristic curve I/U Charging current 1 (preset/minimum/maximum) 1.0 A/0.2 A/1.5 A End-of-charge voltage 1 (preset/minimum/maximum) 27,6 V DC / 25 V DC / 30 V DC Temperature compensation 1 (preset/minimum/maximum) 42 mV/K / 0 mV/K / 200 mV/K Battery presence check/time interval 60 s Battery quality check 1 (preset/minimum/maximum) 12 h/4 h/200 h Protection against total discharge 1 (preset/minimum/maximum) 19.2 V DC / 18 V DC / 21 V DC "Battery almost flat" alarm signaling threshold 1 (preset/minimum/maximum) 20.4 V DC / 18 V DC / 30 V DC
1 Can be adjusted via UPS-CONF software
104103_en_00 PHOENIX CONTACT 5
4.3 Signaling and switching outputs
4.4 Ambient conditions
Mains voltage OK (Power in OK) Green LED, static ON Alarm LED indicator Switching output Current limit (internal) Red LED, static ON
24 V DC, active high
Battery operation (Battery Mode) LED indicator Switching output Current limit (internal) Signal options Yellow LED, static ON Bat.-Mode, Bat.-Mode Delayed Battery charging (Battery Charge) LED indicator Switching output Current limit (internal) Signal options Yellow LED, flashing Bat.-Charge, Bat.-Mode, Bat.-Mode Delayed, battery almost flat Climatic requirements Ambient temperature Operation (> 55°C derating) Storage/transport -25°C ... +70°C -40°C ... +80°C Humidity at +25°C, no condensation 95% Pollution degree according to EN 50178 2 Climatic class 3K3 Mechanical requirements Vibration (operation) < 15 Hz, amplitud e ±2.5 mm according to IEC 60068-2-6 Shock according to IEC 60068-2-27 30g in each direction General data Insulation voltage I/O (type/routine test) 4 kV AC/2 kV AC Input/PE (type/routine test) 2 kV AC/2 kV AC Output/PE (routine test) 500 V DC Mounting position according to EN 60715 Degree of protection IP20 Protection class (with PE connection) I MTBF according to IEC 61709 (SN 29500) > 500,000 h Material Aluminum (AlMg3)/zinc-plated sheet steel Dimensions (W/H/D) 60 mm x 130 mm x 118 mm Weight 1.1 kg
104103_en_00 PHOENIX CONTACT 6
4.5 Standards/approvals
Electrical equipment of machines (surge voltage category III) EN 60204 Safety transformers for switched-mode power supply units IEC 61558-2-17 Electrical safety (of information technology equipment) EN 60950/VDE 0805 UL/C-UL Recognized UL 60950 Industrial control equipment UL/C-UL Listed UL 508 Electronic equipment for use in power installations EN 50178 (VDE 0160) PELV/SELV PELV (EN 60204)/SELV (IEC 60950) Safe isolation VDE 0100-410 Protection against electric shock DIN 57100-410 Protection against electric shock, basic requirements for safe isolation in electrical equipment DIN VDE 0106-101 Limitation of mains harmonic currents EN 61000-3-2 u U Conformance with EMC Directive 2004/108/EC, noise immunity according to 2006/95/EC (electromagnetic compatibility) Noise immunity according to EN 61000-6-2 Electrostatic discharge according to EN 61000-4-2 Housing Contact discharge Air discharge Remark Level 3 6 kV 8 kV Criterion B Electromagnetic HF field according to EN 61000-4-3 Housing Frequency range Field strength Remark Level 3 80 MHz ... 2 GHz
10 V/m
Fast transients (burst) according to EN 61000-4-4 Input Output Signal Remark 4 kV (Level 4 - asymmetrical: Cable to ground) 2 kV (Level 4 - asymmetrical: Cable to ground) 1 kV (Level 4 - asymmetrical: Cable to ground) Criterion B Surge current loads (surge) according to EN 61000-4-5 Input Output Signal Remark 4 kV (Level 4 - asymmetrical: Cable to ground) 2 kV (Level 4 - asymmetrical: Cable to cable) 2 kV (Level 3 - asymmetrical) 1 kV (Level 3 - symmetrical) 2 kV (Level 3 - asymmetrical) Criterion B Conducted interference according to EN 61000-4-6 Input/output/signal Frequency range Voltage Remark Level 3 10 kHz ... 80 MHz 10 kV Criterion A Noise emission according to EN 61000-6-3 Radio interference voltage according to EN 55011 EN 55011 (EN 55022) Class B, industrial and residential
applications
104103_en_00 PHOENIX CONTACT 7 5S a f e t y r e g u l a t i o n s Installation notes Connection notes NOTE: –T h e d e v i c e m u s t o n l y be installed, operated, and maintained by qualified personnel. – Follow the installation instructions. – When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. – For the safety data, please refer to the package slip and certificates (conformity assessment, other approvals, if necessary). – Do not repair the device yourself, replace it with an equivalent device. – Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting from violation. – The IP20 degree of protection (IEC 60529/ EN 60529) of the device is intended for use in a clean and dry environment. – The device must not be subject to mechanical strain and/or thermal loads, which exceed the limits described. NOTE: Electrostatic discharge The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2.
104103_en_00 PHOENIX CONTACT 8
6 Connection, operating, and indication
Figure 1 TRIO-UPS/1AC/ 24DC/5 structure
6.1 Connection terminal blocks
Use a screwdriver with the correct blade width for wiring. For reliable and safe-to-touch connections, strip 8 mm off the cable ends. The following cable cross-sections can be connected: No. Description 1 100 ... 240 V AC input 2 24 V rechargeable battery module connection 3 24 V DC output, buffered
5 Active switching output: Alarm
6 Active switching output: Bat.-Mode 7 Active switching output: Bat.-Charge
8 Red LED indicator: Alarm
9 Yellow LED indicator: Bat.-Mode/Bat.-Charge
0 Green LED indicator: Power in OK/Overload
! Remote shutdown (R1, R2) " Buffer time setting 0.5 ... 20 minutes, PC mode, unlimited ∞ § Config.-Port $ "Confirm" button Bat.- M odeBat.- C harg eRemote Alarm Battery 1015 PC-M ode OFF ONRemote TRIO DC-UPS tmax min L N Alarm Adjust Output DC 24V 5A Input AC 100-240 V 22.5-29.5 V Bat.-Mode Bat.-Charge Power in OK Overload Config.-Port (Default 0.5) Custom UPS STICK DATA 1. Press Button and 2. Insert STICK within 4sec STICK UPS DATA 1. Insert STICK 2. Press Button > 6sec (+) (-) Terminal block Rigid Stranded AWG Tightening torque No. [mm²] [mm²] [Nm] [lb in] 1 - 3, 5 - 7, In order to comply with UL approval, use copper cables that are designed for operating temperatures >75°C.
104103_en_00 PHOENIX CONTACT 9
6.2 Block diagram
Figure 2 Block diagram for the TRIO-UPS/1AC/24DC/5
6.3 Input
The 100 ... 240 V AC connection is made using the L (+) and N (-) screw connections. Device installation must be carried out according to the regulations of EN 60950. It must be possible to switch off the device using a suitable disconnecting device outside the power supply. An internal fuse is provided for device protection. Additional device protection is not required. Network type The device can be connected to single-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or IT networks according to VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ... 240 V AC. Figure 3 Single-phase network systems t...[min] /c74/c74 Output DC 2 4V5A Remote On/Off 2x 12V Battery PS Alarm Bat.-Charge Bat.-Mode IFS Config.-Port Confirm L (+) N (-) For example, primary side line protection could be used. If an internal fuse is blown, this is due to a device fault. In this case, send the device to Phoenix Contact for inspection. For operation using two phase conductors of a three-phase system, an all-pole disconnecting device must be provided. TN-S L N PE LN TT LN L N TN-C L PEN+ LN iT L N
104103_en_00 PHOENIX CONTACT 10
6.4 Output
The 24 V DC connection is made using the "OUT DC 24 V, +, -" screw connections. The output voltage set upon delivery is 24 V DC. The output voltage can be set from 22.5 V DC to 29.5 V DC on the potentiometer. Figure 4 Connection
6.5 LED indicators
The signal outputs are connected via the "Alarm", "Bat.- Mode", and "Bat.-Charge" terminal blocks. There are three LED status indicators and three active switching outputs for function monitoring. No. Description 1 100 ... 240 V AC input 3 24 V DC output, buffered No. Description 9 Yellow LED indicator: Bat.-Mode/Bat.-Charge Bat.- Mode Bat.- Charge Remote Alarm Battery 1015 PC-M ode OFFONRemote TRIO DC-UPS tmax min L N Alarm Adjust Output DC 24V Input AC 100-240 V 22.5-29.5 V Bat.-Mode Bat.-Charge Power in OK Overload Config.-Port (Default 0.5) Custom UPS STICK DATA1. Press Button and 2. Insert STICK within 4sec STICK UPS DATA 1. Insert STICK 2. Press Button > 6sec (+) (-) Status Green Yellow Red
Description
The UPS is switched off or the UPS is operating in mains mode, battery mode is deactivated (remote), battery management is still active The UPS is starting mains operation, for the LED test all LEDs are switched on and off again once before the current operating state is indicated The UPS is operating in mains mode, the battery is OK and charged The UPS is operating in mains mode, the battery is OK and is charging (charge < 85% of nominal capacity) The UPS is operating in battery mode, the battery voltage U BAT is > 20.4 V The UPS is operating in battery mode, the battery is almost flat (battery voltage UBAT is < 20.4 V) UPS protection against total discharge has terminated battery mode (battery voltage U BAT = 19.2 V) and continues indication for a maximum of 10 hours
8 The UPS is operating in mains
mode, the battery is faulty The UPS has been overloaded in mains mode, the battery is OK and charged
10 The UPS has been overloaded in
mains mode, the battery is faulty Key LED OFF LED ON LED flashing
104103_en_00 PHOENIX CONTACT 11
7 Installation
A minimum spacing between other devices does not have to be observed in order to ensure correct device function.
7.1 Narrow mounting position
The power supply unit can be snapped onto all DIN rails according to EN 60715 and must be mounted horizontally (connection terminal blocks facing upwards and downwards). Mounting Position the module with the DIN rail guideway on the top edge of the DIN rail and then snap it downwards. Figure 6 Mounting the TRIO-UPS/1AC/24DC/5 Removal Release the snap-on catch using a screwdriver and then detach the module from the bottom edge of the DIN rail. Figure 7 Removing the TRIO-UPS/1AC/24DC/5
7.2 Flat mounting position
A flat mounting position can be achieved by mounting the module onto the DIN rail at a 90° angle. Mount the DIN rail adapter (UTA 107) as shown in the figure. The screws that were previously used to secure the UTA must be used: Torx Figure 8 Modification for flat mounting position BA A B
104103_en_00 PHOENIX CONTACT 12
8 Rechargeable battery module
The rechargeable battery module is connected to the power supply unit via the "Battery +" and "Battery -" terminal blocks The following rechargeable battery modules are recommended: Figure 9 Characteristic curves for the rechargeable battery modules Battery mode can be exited after a predefined time has elapsed or by means of external shutdown. If the device is to be shut down after a specific time has elapsed, the time can be set via the selector switch " on the front of the device. When the supply voltage is reapplied, the device can switch to battery mode again. NOTE: Risk of short circuit The fuse for the rechargeable battery module must be removed when installing or replacing the module. Rechargeable battery module Fuse Recom- mended charging current 1 MINI-BAT/24DC/1.3Ah 15 A 0.8 A 2 QUINT-BAT/24DC/3.4Ah 1
1 Connection via plug connector, 14 mm
25 A 1.0 A 2
2 Can be adjusted via UPS-CONF software
3 QUINT-BAT/24DC/7.2Ah1 2x2 5A 1 . 5A 2 4 QUINT-BAT/24DC/12Ah1 2x2 5A 1 . 5A 2 t [min] t [h] I[ A ] 0 0.5 2 4 1 1 1.5 2.5 3 3.5 4.5 5 = 1.3Ah = 3.4Ah = 7.2Ah = 12Ah 1 3 The batteries are sealed, maintenance-free lead AGM batteries, which are intended for operating temperatures of 0°C ... 40°C. They have a service life of six to nine years at an ambient temperature of 20°C. In order to ensure immediate availability, all batteries are supplied fully charged. Startup should be carried out at the latest after nine months at 20°C ... 30°C, or after six months at 30°C ... 40°C.
104103_en_00 PHOENIX CONTACT 13
9 Method of operation
9.1 Output voltage
In mains operation (AC input voltage present) the output voltage of the TRIO-UPS corresponds to the setting at the potentiometer 4. In the event of supply voltage failure, battery mode is activated without interruption. The output voltage is now directly dependent on the battery voltage and is UBAT - 0.5 V.
9.2 Remote shutdown
If the connected load cannot be supplied from the power storage device in the event that the AC voltage fails, the UPS can be disabled via R1/R2. This shutdown can be performed during mains operation or while battery mode is active. UPS active, remote shutdown deactivated, default upon delivery: – Terminal points "R1" and "R2" are short circuited (with plug-in bridges by default upon delivery) OR 24 V DC is present at terminal point "R2". – If the supply voltage fails, the TRIO-UPS switches to battery mode. UPS not active, remote shutdown activated: – Terminal points "R1" and "R2" are not short circuited AND 0 V DC is present at terminal point "R2". – All LEDs are OFF. – If the supply voltage fails, the TRIO-UPS does not switch to battery mode, the device shuts down. – The connected loads are supplied and the rechargeable battery module is charged as long as the supply voltage is present.
9.3 Buffer time setting
The time after which battery mode is exited is set via the " selector switch on the front of the device: – 0.5 to 20 minutes – Parameterizable time via software ("CUSTOM" switch position, default: 0.5 minutes) – Unlimited (buffering with the total stored energy) – PC mode (see Section 9.4 "PC mode" )
9.4 PC mode
In "PC mode", the UPS function follows a chronological sequence that can be parameterized via the software and individually optimized for the relevant IPC solution. Requirements: IFS-USB-PROG-ADAPTER data cable (Order No. 2811271) and UPS-CONF software (Order No. 2320403). To set the parameters, an Interface interface (IFS) is used for data exchange between the TRIO-UPS and a suitable user interface on the IPC. The user is supported by help texts and graphics for the individual parameters. As an option, parameterization can be carried out using an IFS-CONFSTICK. Here, a parameter record is transferred from the TRIO-UPS to the IFS-CONFSTICK. This parameter record can then be written to any other TRIO-UPS. In "PC mode", the UPS function follows a parameterizable chronological sequence of delay time, IPC shutdown, and IPC idle time. Delay time: If the mains voltage is not applied again within the first 60 seconds of battery mode, for example, "Bat.-Mode" is indicated in order to shut down an IPC with a delay. IPC shutdown: Shutdown is performed via a data cable to the IPC. The IPC must be connected to the UPS via a USB data cable. The IPC is supplied by the TRIO-UPS for a parameterizable period of time, e.g., 2 minutes.
104103_en_00 PHOENIX CONTACT 14
9.5 PC idle time
Once the "PC shutdown" time has elapsed, the output voltage is switched off, e.g., for 30 seconds (also when the mains voltage is applied again). Figure 10 Time diagrams 120/230V 24V 24V ON OFF ON OFF ON OFF AC input DC output LED green POWER IN OK LED gelb Bat.-Mode PC response Delay time PC shutdown Bat. mode delayed: Active switching output (can be parameterized) Power comes back on during set delay time AC input DC output LED green POWER IN OK LED yellow Bat. mode PC response Bat. mode delayed: Active switching output (can be parameterized) PC shutdown PC idle time Power comes back on during set time PC shutdown Delay time 120/230V 24V 24V ON OFF ON OFF ON OFF
104103_en_00 PHOENIX CONTACT 15
9.6 Battery management
Battery management of the TRIO-UPS is divided into two checks that are performed cyclically during normal operation. Battery presence check The battery presence check is used to detect a correctly installed battery. If this is not the case, the check is failed and the green 0 and red 8 LED indicators are controlled statically. Battery quality check The battery quality check is a lifecycle test. It enables conclusions to be drawn, e.g., regarding the maximum lifecycle of the battery if the maximum charging time has been exceeded. In this case, the green 0 and red 8 LED indicators are controlled statically.
10 Interfaces
10.1 Config.-Port The TRIO-UPS is connected to the USB connection on the service PC via the "Config.-Port" using the IFS-USB-PROG- ADAPTER data cable.
10.2 IFS-USB-PROG-ADAPTER
The programming adapter (Order No. 2811271) represents the interface between the service PC and the TRIO-UPS and is required in order to parameterize the TRIO-UPS. Figure 11 Programming adapter
10.3 IFS-CONFSTICK
The IFS-CONFSTICK is a multi-functional memory block for easy storage and back up of configuration and parameter data. Transferring parameters to the IFS-CONFSTICK To transfer parameters, proceed as follows: 1. Press and hold down the "Confirm" button. 2. You now have four seconds to carefully insert the IFS-CONFSTICK in the "Config.-Port" on the TRIO-UPS, taking care to observe the connection direction. 3. Parameter transfer is starte d and indicated by the cyclic control of the three LED indicators. Sequence: Red - Yellow - Green a) Error-free transfer: Green LED indicator ON b) Transfer error: Red LED indicator ON Transferring parameters to the TRIO-UPS To transfer parameters, proceed as follows: 1. Carefully insert the IFS- CONFSTICK in the "Config.- Port" on the TRIO-UPS, taking care to observe the connection direction. 1. Press and hold down the "Confirm" button for at least six seconds. 2. Parameter transfer is starte d and indicated by the cyclic control of the three LED indicators. Sequence: Green - Yellow - Red a) Error-free transfer: Green LED indicator ON b) Transfer error: Red LED indicator ON The following can be parameterized: –T i m e s – Switching outputs – Battery management Serial No. XXXXXXXXXX www.interface.phoenixcontact.com IFS-USB-PROG-ADAPTEROrd.-No.: 2 8 1127 1
32825 Blomberg, Germany
104103_en_00 16PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com
11 UPS-CONF configuration and
The Windows-based UPS-CONF configuration and management software (Order No. 2320403) is used to parameterize the TRIO-UPS. Various dialog boxes are available for parameterization. The current operating status of the TRIO-UPS is always displayed at the bottom of the dialog box. Figure 12 Example, TRIO-UPS status display A distinction is made between the following states: The UPS-CONF configuration and management software can be downloaded free of charge at www.phoenixcontact.net/download. Status Meaning Operation mode Preset operating mode at the selector switch " Power Source Power source that is currently active Battery Condition Current battery charging state Device Status Current state of the TRIO-UPS Connection to UPS Connectio n status between service PC and TRIO-UPS If an alarm is detected or an existing online connection between the IPC and TRIO-UPS is interrupted, the UPS-CONF dialog box is automatically displayed on screen. The status is queried cyclically.