Technical content
Features
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 2 2T a b l e o f c o n t e n t s
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 3 Description Type Order No. Pcs. / Pkt. DC/DC converter, primary-switched, slim design, input: 12 - 24 V DC, output: 48 V DC/0.7 A MINI-PS- 12- 24DC/48DC/0.7 2320021 1 Input data Input nominal voltage range 12 V DC ... 24 V DC DC input voltage range 10 V DC ... 32 V DC (> 10.5 V DC start) DC frequency range 0 Hz Current consumption Approx. 3.2 A (12 V DC) Approx. 1.6 A (24 V DC) Inrush current limitation < 10 A (typical) I2t 0.3 A2s Power failure bypass > 2 ms (12 V DC) > 12 ms (24 V DC) Typical response time < 0.5 s Input fuse, integrated 6.3 A (slow-blow, internal) Output data Nominal output voltage 48 V DC ±1% Setting range of the output voltage 30 V DC ... 56 V DC (> 48 V constant capacity) Output current 0.7 A (-25 °C ... 60 °C) Derating from 60°C to 70°C: 2.5% per Kelvin Efficiency > 87 % (at 24 V DC and nominal values) Residual ripple < 20 mVPP (20 MHz) Peak switching voltages < 10 mV PP (20 MHz) Connection in parallel Yes, for assembling redundant systems and increasing efficiency Connection in series Yes Surge protection against internal surge voltages yes, limited to approx. 60 V DC Resistance to reverse feed 60 V DC Power consumption Maximum power dissipation idling 1.5 W Power loss nominal load max. 4.5 W DC OK active Output description U OUT > 0.9 x UN: High signal Status display "DC OK" LED green / UOUT > 0.9 x UN: LED ON General data Insulation voltage input/output 1 kV (routine test) 1.5 kV (type test) Degree of protection IP20 Class of protection III MTBF > 500 000 h in acc. with IEC 61709 (SN 29500) Type of housing Polyamide PA, color: green Housing material Polyamide (PA) Dimensions W / H / D (state of delivery) 22.5 mm / 99 mm / 107 mm Weight 0.2 kg 3O r d e r i n g d a t a
4 Technical data
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 4 Ambient conditions Ambient temperature (operation) -25 °C ... 70 °C (> +60°C derating) Ambient temperature (storage/transport) -40 °C ... 85 °C Max. permissible relative humidity (operation) ≤ 95 % (At +25°C, no condensation) Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6 15 Hz ...150 Hz, 2.3 g Shock 30g in all directions in acc. with IEC 60068-2-27 Pollution degree in acc. with EN 50178 2 Climatic class 3K3 (in acc. with EN 60721) Approvals UL approvals UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950 Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC Noise immunity according to EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Housing > Level 3 Contact discharge 8 kV (Contact discharge) Discharge in air 8 kV (Air discharge) Comments Criterion B Electromagnetic HF field EN 61000-4-3 Housing Level 3 Frequency range 80 MHz ... 3 GHz Field intensity 10 V/m Comments Criterion A Fast transients (burst) EN 61000-4-4 Input 4 kV (level 4 - asymmetrical: conductor to ground) Output 2 kV (level 3 - asymmetrical: conductor to ground) Signal 1 kV (Level 2 - asymmetrical cable to ground) Comments Criterion B Surge current loads (surge) EN 61000-4-5 Input 2 kV (Level 3) 1 kV (Level 3) Conducted interference EN 61000-4-6 Input/output Level 3 Frequency range 0.15 MHz ... 80 MHz (10 V) Voltage dips EN 61000-4-11 Input (> 10 ms) Comments Criterion B Emitted interference in acc. with EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 5 5022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Current approvals can be found for the product in the download area.
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 5 5S t r u c t u r e OUT DC 48V 0.7A DC OK DC OK 30- VDC IN DC 12 - 24V NC NC
1 AC input
2 DC output
3 Green LED: DC OK
4 Potentiometer: 30 V DC ... 56 V DC
5 Active switching output: DC OK
6 Universal DIN rail adapter UTA 107/30
[mm2] AWG [Nm] solid stranded Torque Input data Input nominal voltage range 12 V DC ... 24 V DC DC input voltage range 10 V DC ... 32 V DC (> 10.5 V DC start) DC frequency range 0 Hz Input fuse, integrated 6.3 A (slow-blow, internal) Type of connection Pluggable screw connection Stripping length 7 mm Output data Nominal output voltage 48 V DC ±1% Setting range of the output voltage 30 V DC ... 56 V DC (> 48 V constant capacity) Output current 0.7 A (-25 °C ... 60 °C) Type of connection Pluggable screw connection Stripping length 7 mm
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 6 6B l o c k d i a g r a m NC NC DC OK 7S a f e t y n o t e s DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. DANGER Components with dangerously high voltage and high stored energy are located in the device! Never carry out work on live parts! Depending on the ambient temperature and the load, the housing can become very hot! CAUTION Before startup please ensure: The mains connection has been carried out by a competent person and protection against electric shock is guaranteed! The device can be disconnected outside the power supply unit in accordance with the regulations as in EN 60950 (e.g. through primary side line protection)! All feed lines are sufficiently protected and dimensioned! All output lines are dimensioned according to the maximum output current of the device or separately protected! Sufficient convection must be guaranteed. ATTENTION: Danger if used improperly The power supply units are built-in devices. The device may only be installed and put into operation by qualified personnel. The corresponding national regulations must be observed.
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 7
8 Installation
ATTENTION: Module can become damaged To ensure sufficient convection, we recommend the following minimum spacing be used between modules: 5 cm above and below The power supply unit can be snapped onto all DIN rails in acc. with EN 60715.
9 Installation position
113,5 22,5 129 159 OUT DC MINI POWER DC OK DC OK VDC -- + IN DC NC NC Mounting position: Installation depth 107 mm (+ DIN rail)
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 8 A B Assembly Position the module with the DIN rail guide on the upper edge of the DIN rail, and snap it in with a downward motion. Removing Pull the snap lever open with the aid of a screwdriver and slide the module out at the lower edge of the DIN rail.
10 Input
The 12 V DC ... 24 V DC connection is established using the "+" and "-" screw connections. Protection of the primary side The device must be installed in acc. with the regulations as in EN 60950. An internal fuse is provided for device protection. Additional device protection is not required. ATTENTION: Module can become damaged If an internal fuse is triggered, there is a device malfunction. In this case, the device must be inspected in the factory.
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 9
11 Output
The connection is established via screw connection terminal blocks "+" and "-" of the DC output. The output voltage can be adjusted on the potentiometer from 30 V DC ... 56 V DC. Protection of the secondary side The device is electronically protected against short circuit and idling. In the event of a malfunction, the output voltage is limited to 60 V DC. Make sure that all output lines are dimensioned according to the maximum output current or are separately protected! The cables on the secondary side should have large cross sections in order to keep the voltage drops on the lines to a minimum. ATTENTION: Module can become damaged Make sure that all output lines are dimensioned according to the maximum output current or are separately protected. The cables on the secondary side must have sufficiently large cross sections in order to keep the voltage drops on the lines as low as possible.
12 Signaling
For function monitoring, there is the active DC OK switching output and the DC OK LED. State 1 State 2 "DC OK" LED ON OFF Active DC OK switching output U OUT (with reference to "–") U = 0 V (in reference to "–") Meaning Normal operation of the power supply unit. UOUT > 0.9 x UN UOUT ≤ 0.9 x UN Secondary load short-circuit or overload No mains voltage or device defective
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 PHOENIX CONTACT 10 DC OK DC OK+- - Active signal output The DC output signal in normal operation of the power supply unit (UOUT > 0.9 x UN ) is between the "DC OK" and "-" connection terminal blocks and can carry a maximum of 20mA. By switching from "active high" to "low", the DC OK signal output signalizes when the output voltage is fallen short of by more than 10%. The DC OK signal is decoupled from the power output. It is thus not possible for devices connected in parallel to act as an external power supply.
13 Function
-25 IN 20 40 60 Ambient temperature [°C] Output current [A] Thermal behavior The device can supply a nominal output current of 0.7 A with ambient temperatures of up to 60°C. For ambient temperatures above 60°C, the output current must be reduced by 2.5% per Kelvin increase in temperature. From 70°C onwards or in the case of thermal overload, the device reduces the output capacity for its own protection, and returns to normal operation when it has cooled down. Parallel operation Devices of the same type can be connected in parallel to increase both redundancy and power. By default upon delivery, no further adjustments are required. If the output voltage is adjusted, a uniform distribution of power is guaranteed by setting all parallel operated power supply units to exactly the same output voltage. To ensure symmetrical current distribution we recommend that all cable connections from the power supply unit to the busbar are the same length and have the same cross section. Depending on the system, for parallel connection of more than two power supplies a protective circuit should be installed at each individual device output (e.g., decoupling diode, DC fuse or circuit breaker). This prevents high return currents in the event of a secondary device fault.
MINI-PS- 12- 24DC/48DC/0.7 104349_en_00 11PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com IN − + IN Σ =I N Redundant operation Redundant circuits are suitable for supplying systems, which place particularly high demands on operational safety. If a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the complete power supply without interruption, and vice versa. For this purpose, the power supply units to be connected in parallel must be large enough that the total current requirements of all loads can be fully met by one power supply unit. External decoupling diodes are required for 100% redundancy (ST 4-QUATTRO-DIO 1N 5408/L-R, Order No. 3037782, ST 4-QUATTRO-DIO 1N 5408/R-L, Order No. 3037795). IN − + IN Σ = 2 xI N Increased performance For n parallel connected devices, the output current can be increased to n x IN. Parallel connection for increasing power is used when extending existing systems. A parallel connection is recommended if the power supply unit does not cover the current consumption of the most powerful load. Otherwise, the load should be divided between individual devices that are independent from one another.