Technical content

Technical data sheet 22MT-52.. www.belimo.com 22MT-52.. • en-us • 2020-10-01 • Subject to change 1 / 4 Average Temperature Sensor Active sensor (0...10 V) for measuring the averaging temperature in duct applications. IP65 / NEMA 4X rated enclosure. Supplied with one continuous sensing element across the whole length of the probe to ensure optimum accuracy and eliminate air stratification problems. Type Overview Tyyppi Lähtöviesti lämpötila aktiivinen Anturiputken pituus Technical Data Electrical Data Nominal voltage AC/DC 24 V Power consumption AC 0.8 VA Power consumption DC 0.4 W Electrical connection Removable spring loaded terminal block max. 2.5 mm² Cable entry Cable gland with strain relief Ø6...8 mm (1/2" NPT conduit adapter included) Functional Data Sensor Technology based on Pt1000 1/3 DIN Multirange 8 measuring ranges selectable Output signal active note output 0...5/10 V with jumper adjustable Voltage output: min. 5 kΩ load Application air Measuring Data Measuring values Temperature Measuring range temperature Active sensor: range selectable Attention: max. measuring temperature is restricted by max. fluid temperature (see Safety data) Asetus alue [°C] alue [°F] Tehdasasetus Accuracy temperature active ±0.9°F @ 70°F [±0.5°C @ 21°C] Time constant τ (63%) in air duct typical 100 s @ 0 m/s Materials Cable gland PA6, black Housing cover: lexan, orange base: lexan, orange seal: 0467 NBR70, black UV resistant

Technical data sheet 22MT-52.. www.belimo.com 22MT-52.. • en-us • 2020-10-01 • Subject to change 2 / 4 Safety Data Ambient humidity max. 95% r.H., non-condensing Housing surface temperature max. 160°F [70°C] Protection class IEC/EN III Protective extra-low voltage (PELV) Protection class UL UL Class 2 Supply EU Conformity CE Marking Certification IEC/EN IEC/EN 60730-1 Certification UL cULus acc. to UL60730-1A/-2-9, CAN/CSA E60730-1:02/-2-9 Degree of protection IEC/EN IP65 Degree of protection NEMA/UL NEMA 4X Quality Standard ISO 9001 Safety Notes This device has been designed for use in stationary heating, ventilation and air-conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten humans, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment. Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation. The device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed. Remarks When using lengthy connection wires (depending on the cross section used) the measuring result might be falsified due to a voltage drop at the common GND-wire (caused by the voltage current and the line resistance). In this case, 2 GND-wires must be wired to the sensor - one for supply voltage and one for the measuring current. Sensing devices with a transducer should always be operated in the middle of the measuring range to avoid deviations at the measuring end points. The ambient temperature of the transducer electronics should be kept constant. The transducers must be operated at a constant supply voltage (±0.2 V). When switching the supply voltage on/off, onsite power surges must be avoided. Temperature sensors with electronic components always have a dissipative power which affects the temperature measurement of the ambient air. The dissipation in active temperature sensors shows a linear increase with rising operating voltage. This dissipative power should be taken into account when measuring temperature. As Belimo transducers work with a variable operating voltage, only one operating voltage can be taken into consideration, for reasons of production engineering. Transducers voltage, the expected measuring error of the output signal will be the least. For other operating voltages, the offset error will be increased by a changing power loss of the sensor electronics. If a re-calibration should become necessary later directly on the sensor, this can be done by means of a trimming potentiometer on the sensor board. Scope of delivery Scope of delivery Description Type Mounting kit, with mounting brackets A-22D-A08 Mounting plate S housing A-22D-A09 1/2" NPT conduit adapter General Remarks Concerning Sensors Build-up of Self-Heating by Electrical Dissipative Power

Technical data sheet 22MT-52.. www.belimo.com 22MT-52.. • en-us • 2020-10-01 • Subject to change 3 / 4 Wiring Diagram The adjustment of the measuring ranges is made by changing the bonding jumpers. The output value in the new measuring range is available after 2 seconds. Asetus alue [°C] alue [°F] Tehdasasetus Dimensions L = Probe length

Technical data sheet 22MT-52.. www.belimo.com 22MT-52.. • en-us • 2020-10-01 • Subject to change 4 / 4 Tyyppi Anturiputken pituus Paino 22MT-524 10 ft [3 m] 0.49 lb [0.22 kg] 22MT-525 20 ft [6 m] 0.62 lb [0.28 kg]