Technical data sheet 22DT-52.. www.belimo.com 22DT-52.. • en-us • 2019-08-20 • Subject to change 1 / 6 Duct / Immersion Temperature Sensor Active sensor (0...5/10 V) for measuring temperature in duct applications. In combination with a stainless steel or brass thermowell which is also applicable for pipe applications. IP65 / NEMA 4X rated enclosure. Type Overview Type Output signal active temperature Probe length Probe diameter 22DT-52H DC 0...5 V, DC 0...10 V 22DT-52L DC 0...5 V, DC 0...10 V 22DT-52N DC 0...5 V, DC 0...10 V 22DT-52P DC 0...5 V, DC 0...10 V 22DT-52R DC 0...5 V, DC 0...10 V 22DT-52T DC 0...5 V, DC 0...10 V Technical Data Electrical Data Power supply DC 15...24 V, ±10%, 0.35 W Power supply AC 24 V, , ±10%, 0.82 VA Electrical connection Removable spring loaded terminal block max. 2.5 mm² Cable entry Cable gland with strain relief Ø6...8 mm (1/2" NPT conduit adapter included) Functional Data Multirange 8 measuring ranges selectable Output signal active note output DC 0...5/10 V with jumper adjustable voltage output: min. 5 kΩ load Application air water
Technical data sheet 22DT-52.. www.belimo.com 22DT-52.. • en-us • 2019-08-20 • Subject to change 2 / 6 Measuring Data Measuring values temperature Measuring range temperature Active sensor: range selectable Attention: max. measuring temperature is restricted by max. fluid temperature (see Safety data) Setting range [°C] range [°F] Factory setting Accuracy temperature active ±0.9°F @ 70°F [±0.5°C @ 21°C] Time constant t (63%) in the air duct typical 46 s @ 3 m/s typical 210 s @ 0 m/s Time constant t (63%) in water pipe typical 7 s with thermowell brass typical 9 s with thermowell stainless steel Materials Cable gland PA6, black Housing cover: lexan, orange base: lexan, orange seal: 0467 NBR70, black UV resistant Safety Data Ambient humidity max. 95% r.H., non-condensing Housing surface temperature max. 160°F [70°C] Protection class IEC/EN III protective extra-low voltage (pelv) Protection class UL UL Class 2 Supply EU Conformity CE Marking Certification IEC/EN IEC/EN 60730-1 Certification UL cULus acc. to UL60730-1A/-2-9, CAN/CSA E60730-1:02/-2-9 Degree of protection IEC/EN IP65 Quality Standard ISO 9001 Safety Notes This device has been designed for use in stationary heating, ventilation and air-conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten humans, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment. Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation. The device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed.
Technical data sheet 22DT-52.. www.belimo.com 22DT-52.. • en-us • 2019-08-20 • Subject to change 3 / 6 Remarks When using lengthy connection wires (depending on the cross section used) the measuring result might be falsified due to a voltage drop at the common GND-wire (caused by the voltage current and the line resistance). In this case, 2 GND-wires must be wired to the sensor - one for supply voltage and one for the measuring current. Sensing devices with a transducer should always be operated in the middle of the measuring range to avoid deviations at the measuring end points. The ambient temperature of the transducer electronics should be kept constant. The transducers must be operated at a constant supply voltage (±0.2 V). When switching the supply voltage on/off, onsite power surges must be avoided. Temperature sensors with electronic components always have a dissipative power which affects the temperature measurement of the ambient air. The dissipation in active temperature sensors shows a linear increase with rising operating voltage. This dissipative power should be taken into account when measuring temperature. As Belimo transducers work with a variable operating voltage, only one operating voltage can be taken into a standard setting at an operating voltage of DC 24 V. That means, that at this voltage, the expected measuring error of the output signal will be the least. For other operating voltages, the offset error will be increased by a changing power loss of the sensor electronics. If a re- calibration should become necessary later directly on the sensor, this can be done by means of a trimming potentiometer on the sensor board. Scope of delivery Scope of delivery Description Type Mounting clip, with screws and adhesive foil A-22D-A11 1/2" NPT conduit adapter General Remarks Concerning Sensors Build-up of Self-Heating by Electrical Dissipative Power
Technical data sheet 22DT-52.. www.belimo.com 22DT-52.. • en-us • 2019-08-20 • Subject to change 4 / 6 Accessories Optional accessories Description Type Mounting plate S housing A-22D-A09 Cold barrier, Plastic, L 50 mm, for thermowell pocket A-22P-A.. A-22P-A51 Connection adapter, M20, for cable 1 x 6 mm, Multipack 10 pcs. A-22G-A01.1 Optional accessories air Description Type Mounting flange for sensor probe 6 mm, up to max. 80°C, Plastic A-22D-A03 Mounting flange for sensor probe 6 mm, up to max. 260°C, Brass A-22D-A05 Recommended accessories water Description Type Thermowell pocket (fabricated) Stainless steel, 2" [50 mm], 1/2" NPT, wrench size 3/4" A-22P-A05 Thermowell pocket (fabricated) Brass, 2" [50 mm], 1/2" NPT, wrench size 3/4" A-22P-A17 Thermowell pocket (machined) Stainless steel, 2" [50 mm], 1/2" NPT, wrench size 3/4" A-22P-A36 Thermowell pocket (fabricated) Stainless steel, 4" [100 mm], 1/2" NPT, wrench size 3/4" A-22P-A07 Thermowell pocket (fabricated) Brass, 4" [100 mm], 1/2" NPT, wrench size 3/4" A-22P-A19 Thermowell pocket (machined) Stainless steel, 4" [100 mm], 1/2" NPT, wrench size 3/4" A-22P-A37 Thermowell pocket (fabricated) Stainless steel, 6" [150 mm], 1/2" NPT, wrench size 3/4" A-22P-A09 Thermowell pocket (fabricated) Brass, 6" [150 mm], 1/2" NPT, wrench size 3/4" A-22P-A21 Thermowell pocket (machined) Stainless steel, 6" [150 mm], 1/2" NPT, wrench size 3/4" A-22P-A38 Thermowell pocket (fabricated) Stainless steel, 8" [200 mm], 1/2" NPT, wrench size 3/4" A-22P-A11 Thermowell pocket (fabricated) Brass, 8" [200 mm], 1/2" NPT, wrench size 3/4" A-22P-A23 Thermowell pocket (machined) Stainless steel, 8" [200 mm], 1/2" NPT, wrench size 3/4" A-22P-A39 Thermowell pocket (fabricated) Stainless steel, 12" [300 mm], 1/2" NPT, wrench size 3/4" A-22P-A13 Thermowell pocket (fabricated) Brass, 12" [300 mm], 1/2" NPT, wrench size 3/4" A-22P-A25 Thermowell pocket (fabricated) Stainless steel, 18" [450 mm], 1/2" NPT, wrench size 3/4" A-22P-A15 Thermowell pocket (fabricated) Brass, 18" [450 mm], 1/2" NPT, wrench size 3/4" A-22P-A27 Syringe with thermal paste A-22P-A44
Technical data sheet 22DT-52.. www.belimo.com 22DT-52.. • en-us • 2019-08-20 • Subject to change 5 / 6 Wiring Diagram The adjustment of the measuring ranges is made by changing the bonding jumpers. The output value in the new measuring range is available after 2 seconds. Setting range [°C] range [°F] Factory setting
Technical data sheet 22DT-52.. www.belimo.com 22DT-52.. • en-us • 2019-08-20 • Subject to change 6 / 6 Dimensions Dimensions L = Probe length Type Probe length Weight 22DT-52H 2" [50 mm] 0.26 lb [0.12 kg] 22DT-52L 4" [100 mm] 0.29 lb [0.13 kg] 22DT-52N 6" [150 mm] 0.29 lb [0.13 kg] 22DT-52P 8" [200 mm] 0.31 lb [0.14 kg] 22DT-52R 12" [300 mm] 0.33 lb [0.15 kg] 22DT-52T 18" [450 mm] 0.35 lb [0.16 kg]