1012B SYSTEMSENSOR | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

Features

  • 12 VDC operation, 4-wire
  • Built-in 85dB electronic horn
  • Built-in relay can be connected to lights, bells, horns, remote annunciator, or control panel
  • Interconnectable up to 12 units
  • Visual alarm and power indicator
  • Ceiling white color
  • Built-in 8 second delay on relay output
  • Built-in test switch
  • Twist-on mounting bracket with tamper option for easy installation
  • Improved chamber design for greater stability
  • Same housing design for both ion and photo models
  • 3-year warranty Compact, attractive, and easy to install, System Sensor 1012B and 2012B detectors are designed to respond to a broad range of fires while providing maximum stability. Both units in this series feature low-voltage wiring, allowing you to choose the detector that best suits your application. Electrical Ratings Operating Voltage: 12 VDC (nominal) Relay Contact Rating: 1 Form A, .5 A @ 30 VDC Standby Current: 50 µA maximum average Alarm Current: 20 mA maximum average @ 12 VDC Temperature Range: 32 ° to 120°F (0° to 50°C) Specifications Size: 1.75 ″ h × 5.5″ dia. (44.5 mm h × 140 mm dia.) Weight: 5.3 oz. (150 grams) Humidity Range: 10% to 93% RH, noncondensing Smoke Detector Spacing: On smooth ceilings (as defined in NFPA 72), spacing of 30 feet (900 sq. ft.) may be used as a guideline. Other spacing may be used depending on ceiling height, high air movements, and other conditions or response requirements.

(–) (+) INTERCONNECT UP TO

12 DETECTORS

16 DETECTORS

1 UNIT

2 UNITS

3 UNITS

4 UNITS

5 UNITS

6 UNITS

MAXIMUM POWER BUS LENGTH IN FEET. GIVEN NUMBER OF UNITS (MAXIMUM PER BUS) AND WIRE SIZE. MAXIMUM INTERCONNECT BUS LENGTH: 5,000 FT. NO. 18AWG OR LARGER DUAL CONDUCTOR CABLE. ALL WIRING MUST CONFORM TO LOCAL ELECTRICAL CODES. RELAY CONTACTS RATING: 0.5A 30VDC; 0.5A 30VAC

7 UNITS

8 UNITS

9 UNITS

10 UNITS

11 UNITS

12 UNITS

(+) (–) POWER INPUT AUXILIARY GROUND SIGNAL (+) (–) POWER INPUT AUXILIARY GROUND SIGNAL (+) (–) POWER INPUT AUXILIARY GROUND SIGNAL (+) (–) POWER INPUT AUXILIARY GROUND SIGNAL (+) (–) POWER INPUT AUXILIARY GROUND SIGNAL (+) (–) POWER INPUT AUXILIARY 1012B/2012B Wiring Diagram General Description System Sensor 1012B ionization and 2012B photoelectronic detectors are designed primarily for applications where low-voltage Class 2 wiring may be used. These detectors are self-resetting and offer an 85dB alarm horn. An external push button provides a test of the detectors’ alarm function. Up to 12 units can be interconnected so that if one detector alarms, all detectors alarm. A normally open auxiliary alarm relay is available for controlling external functions. A visible LED indicator flashes once every 40 seconds in standby and rapidly in alarm when detecting smoke. The detectors offer low-voltage operation and a tamper-proof feature. Screw terminals and a mounting bracket are provided for easy installation.

Ordering Information

Part No. Description 1012B Ionization smoke detector with relay, 12 VDC, multiple station 2012B Photoelectronic smoke detector with relay, 12 VDC, multiple station A77-727-01 12 VDC power supply, mounts to a 4″ square box, 21/8″ deep System Sensor Worldwide Distribution In Canada: System Sensor Canada

6581 Kitimat Road, Unit #7

Mississauga, Ontario Canada L5N 3T5 Telephone: 905-812-0767 Fax: 905-812-0771 In the United Kingdom: System Sensor Europe, Ltd. Horsham Gates III, North St. Horsham, West Sussex RH13 5PJ, United Kingdom Telephone: 44-1403-276500 Fax: 44-1403-276501 In India: System Sensor India A-204 Maheshwari Nagar Orkay Mills Lane Andheri East, Mumbai 400093 Telefax: 91-022-8202564 In the Far East: System Sensor Pittway Far East, Ltd. Suite 706, New T&T Centre