Features

– Contact extension block – Safety category 3 according to EN 954-1 – Plug-in screw or spring-cage connection terminal blocks – Single-channel wiring – Safe isolation – Housing width 22.5 mm – Four enable contacts, one alarm contact, and one confirmation contact Observe the safety instructions on page 4. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at This data sheet is valid for all products listed on the following page: Safety Relay as a Contact Extension Block With Off-Delay Contacts

PSR-...- 24DC/URD3/4X1/2X2/3 102862_04_en PHOENIX CONTACT 2 Ordering Data Technical Data Safety Relay Description Type Order No. Pcs./Pck. Safety relay as a contact extension block with off-delay contacts, with screw connection PSR-SCP- 24DC/URD3/4X1/2X2/3 2981732 1 Safety relay as a contact extension block with off-delay contacts, with spring- cage connection PSR-SPP- 24DC/URD3/4X1/2X2/3 2981745 1 Accessories Description Type Order No. Pcs./Pck. DIN rail connector, yellow, for PSR applications PSR-TBUS 2890425 50 Terminating connector PSR-TBUS-TP 2981716 50 Documentation Description Type Order No. Pcs./Pck. Application manual for PSR safety relays UM EN SAFETY RELAY APPLICATION 2888712 1 Input Data Nominal input voltage UN 24 V DC Permissible range 0.85 - 1.1 x UN Typical current consumption at UN 94 mA Typical response time (K1, K2) 20 ms Release time (K1, K2) 0.3 ... 3 seconds +50% Recovery time 1 s, approximately Surge protection Suppressor diode Status indicators (K1, K2, Power) Green LED Output Data Contact type: Positively driven contact assembly Class A according to EN 50205 4 enabling current paths, 1 signaling current path, 1 confirmation path Contact material Silver tin oxide (AgSnO2) Maximum switching voltage 250 V AC/DC Minimum switching voltage 15 V AC/DC Limiting continuous current N/O contact N/C contact (65-66) 6 A 3 A ITH 2 = I1 2 + I2 2 + ... IN 2 50 A2 Maximum inrush current N/O contact N/C contact (65-66) 6 A 3 A Minimum switching current 25 mA Maximum shutdown power

24 V DC

48 V DC

110 V DC

220 V DC

250 V AC

τ = 0 ms

144 W (72 W) 1

288 W (144 W) 1

1500 VA (750 VA)

Inductive load τ = 40 ms 48 W 40 W 35 W 33 W Minimum switching power 0.4 W

PSR-...- 24DC/URD3/4X1/2X2/3 102862_04_en PHOENIX CONTACT 3 Mechanical service life 10 7 cycles, approximately Switching capacity according to DIN EN 60947-5-1/VDE 0660-200 Cycles DC13 AC15 3600/h: 24 V DC 3 A –

230 V AC – 3 A

360/h: 24 V/6 A

230 V/5 A

Short-circuit protection of the output circuits, external Enabling current paths Signaling current path NEOZED 10 A gL/gG NEOZED 4 A gL/gG 1 The maximum values given in brackets apply to N/C contacts 65-66. Output Data (Continued) General Data Permissible ambient operating temperature -20°C ... +55°C Nominal operating mode 100% operating factor Degree of protection according to VDE 0470-1 Housing Connection terminal blocks Installation location IP20 IP20 IP54, minimum Mounting position Any Air and creepage distances between the circuits Basic insulation1 According to DIN EN 50178:1998-04 Impulse voltage withstand level 4 kV Pollution degree 2 Surge voltage category III Dimensions (W x H x D) Screw connection Spring-cage connection 22.5 mm x 114.5 mm x 99 mm 22.5 mm x 114.5 mm x 112 mm Conductor cross-section Screw connection Spring-cage connection Stripping length Screw connection Spring-cage connection 7 mm 8 mm Housing material Polyamide PA, not reinforced 1 Safe isolation, reinforced insulation, and 6 kV between the input circuit/N/C contacts and the enable contact current paths. Tests/Approvals BG/TÜV UL/CUL

PSR-...- 24DC/URD3/4X1/2X2/3 102862_04_en PHOENIX CONTACT 4 Block Diagram Figure 1 Block diagram Derating Curve Figure 2 Derating curve Safety Instructions POWER K1/K2 Y1 15 T-BUST-BUST-BUS T-BUST-BUST-BUS 57 65473727

5848382816 A1 A2

2 [A] Ambient operating temperature [°C] – During operation, parts of electrical sw itching devices carry hazardous voltages. – Before working on the device, disconnect the power. – Please observe the safety regulations of electrical engineering and industrial safety and liability associations. Disregarding these safety regulations may result in death, serious personal injury or damage to equipment. – Startup, assembly, modifications, and upgrades m ay only be carried out by a skilled electrical engineer. – For emergency stop applications, the machine must be prevented from restarting automatically by a higher-level control system. – Protective covers must not be removed when operating electrical switching devices. – In the event of an error, replace the device immediately. – Repairs, especially if the housing must be opened, may only be carried out by the manufacturer or authorized persons. Otherwise the warranty is invalidated. When operating relay modules, the operator must meet the requirements for noise emission for electrical and electronic equipment (EN 61000-6-4) on the contact side and, if required, take appropriate measures.

PSR-...- 24DC/URD3/4X1/2X2/3 102862_04_en PHOENIX CONTACT 5 Structure Figure 3 Structure

1 Metal lock for mounting on the DIN rail

2 COMBICON plug-in screw terminal blocks

3 COMBICON plug-in spring-cage terminal blocks

4 27-28, 37-38, 47-48, and 57-58: Enabling current paths

5 K1, K2: Input

6 Y1: Connection to the DIN rail connector

7 15-16: Confirmation contacts

8 Off delay setting

9 A1, A2: Supply voltage connection

10 65-66: Alarm contacts Function When the 24 V DC operating voltage is applied at terminal blocks A1-A2 or is led via the DIN rail connector, the "Power" LED lights up. When a 24 V DC voltage is applied at input K1-K2 (or via the DIN rail connector), both relays are activated. The LEDs light up and the contacts for enabling current paths 27-28, 37-38, 47-48, and 57-58 close. Alarm contacts 15-16 and 65-66 open. If the voltage is switched off at input K1-K2, the enable contacts open and the alarm contacts close after the set time has elapsed. For additional connection examples, see page 7. 23 24 57 58 Y1 16 15 A1 A2 65 66 PSR-SPP- 24DC/URD3/4X1/2X2/3Order No.: 29 81 74 APPROV AL Serial No. 37 47 16 28 38 48 58 66 A1 28 57 15 Power K1(t)K2(t) 0,5123 0,3PSR-URD3/3 Input: 24 V dcOutput: 240 V ac/24 V dc. 6A B300 Pilot duy R300 Pilot duty 57 58 47 48 Y1 16 15 /K2 PSR-SCP- 24DC/URD3/4X1/2X2/3Order No.: 29 81 73 2 APPROV AL Serial No. 16 28 38 48 58 66 A1 28 57 15 Power K1(t)K2(t) 0,5123 0,3PSR-URD3/3 Input: 24 V dcOutput: 240 V ac/24 V dc. 6A B300 Pilot duy R300 Pilot duty ET 01679 PSR-SCP- 24DC/URD3/4X1/2X2/3 PSR-SPP- 24DC/URD3/4X1/2X2/3 6 7 8 8