DATASHEET SEARCH SITE | WWW.ALLDATASHEET.COM

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 18

Technical content

Features

– Automatic detection of the transmission speed in INTERBUS (500 kbps or 2 Mbps) – Up to 63 INTERBUS devices can be connected – Diagnostic and status indicators NOTE: Device defect due to impermissible firmware version The Inline adapter terminal is designed to be aligned to the right of PLCnext controllers with specific firmware versions. If you align the Inline adapter terminal next to a PLCnext controller with a firmware version that is not permitted, this can cause a device defect to the PLCnext controller. Make sure that the Inline adapter terminal is only aligned next to a PLCnext controller with a firmware version that is permitted. AXC F ... PLCnext controllers with the following firmware versions are permitted: –A X C F 2152 with firmware Version  1.2 Please note: Align the Inline adapter terminal directly on the controller. Axioline F modules may not be aligned on the controller. This data sheet is only valid in association with the Axioline F system manual and the user manual for the Axioline F controller being used. Make sure you always use the latest documentation. It can be downloaded at: phoenixcontact.net/product/1020304 108629_en_00 2018-10-05

108629_en_00 PHOENIX CONTACT 2 / 18 2T a b l e o f c o n t e n t s

108629_en_00 PHOENIX CONTACT 3 / 18 Description Ty pe Order No. Pcs./Pkt. Right-alignable Inline adapter terminal (INTERBUS master) for a PLCnext controller for setting up a PLCnext Inline station AXC F IL ADAPT 1020304 1 3O r d e r i n g d a t a Documentation Ty pe Order No. Pcs./Pkt. User manual, English, Axioline F: System and installation UM EN AXL F SYS INST - - User manual, English, Axioline F: Diagnostic registers, and error messages UM EN AXL F SYS DIAG - - User Manual, English, for diagnosis in Generation 4 controller boards IBS SYS DIAG DSC UM E 2747293 1 User manual, English, for the Peripherals Communication Protocol (PCP), only available as a download. IBS PCP UM E 2753931 1 User manual, English, for the Peripherals Communication Protocol (PCP), only available as a download. IBS SYS PCP G4 UM E 2745169 1

108629_en_00 PHOENIX CONTACT 4 / 18 Dimensions (nominal sizes in mm) Width 12.2 mm Height 119.8 mm Depth 71.5 mm

4 Technical data

119,8 71,5 General data Weight 66 g Ambient temperature (operation) -25 °C ... 55 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 10 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Mounting type DIN rail mounting Connection data: Inline connector Connection method Spring-cage connection Conductor cross section [AWG] 28 ... 16 Stripping length 8 mm System limits Amount of process data max. 4096 Bit (INTERBUS) Number of local bus devices that can be connected max. 63 (observe current consumption) Number of devices with parameter channel max. 62

24 V supply UILC

Supply voltage 24 V DC -15 % / +20 % (acc. to EN 61131-2) Current draw 20 mA

108629_en_00 PHOENIX CONTACT 5 / 18

7.5 V communications power UL (potential jumper)

Supply voltage 7.5 V DC ±5 % Power supply unit max. 0.8 A DC (observe derating)

24 V analog supply UANA (potential jumper)

Supply voltage 24 V DC -15 % / +20 % Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Power supply unit 0.5 A DC (observe derating)

24 V main supply UM

Supply voltage 24 V DC -15 % / +20 % (acc. to EN 61131-2) Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Power supply unit max. 8 A DC (sum of U M + US)

24 V segment supply US

Supply voltage 24 V DC -15 % / +20 % (in accordance with EN 61131) Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Power supply unit max. 8 A (sum of U M + US) Protective circuit Polarity reversal protection of the supply voltage Polarity protection diode Transient protection Suppressor diode Protection NOTE: Damage to the electronics Provide external protection for the module to protect it against polarity reversal. The power supply unit and the external fuse must be coordinated so that safe tripping is ensured in the event of an error. Error messages to the higher level control or computer system Bus error in INTERBUS Yes Peripheral fault in INTERBUS Yes Mechanical tests Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse Continuous shock according to EN 60068-2-27/ IEC 60068-2-27 10g Vibration resistance in acc. with EN 60068-2-6/ IEC 60068-2-6 Conformance with EMC Directive 2014/30/EU Noise immunity test in accordance with EN 61000-6-2 EN 61000-4-2 (ESD) Electrostatic discharge (ESD) EN 61000-4-2/ IEC 61000-4-2 Criterion B, 4 kV contact discharge, 8 kV air discharge EN 61000-4-3 (electromagnetic fields) Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m EN 61000-4-4 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV

108629_en_00 PHOENIX CONTACT 6 / 18 EN 61000-4-5 (surge) Transient overvoltage (surge) EN 61000-4-5/ IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/ asymmetrical) EN 61000-4-6 (line noise immunity) Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V Noise emission test as per EN 61000-6-4 Class A Conformance with EMC Directive 2014/30/EU Approvals For the latest approvals, please visit phoenixcontact.net/products.

108629_en_00 PHOENIX CONTACT 7 / 18

5 Module components

Figure 1 Module components

1 Bus base module

2 Electronics module

3 Inline connector

4 Terminal points

5 Diagnostic and status indicators

108629_en_00 PHOENIX CONTACT 8 / 18

6 Internal circuit diagram

Figure 2 Basic circuit diagram Key: 7,5V 24V 24V 24V 3,3V IB P S PWR RDY FAIL BSA PF Local bus U+L UANA U-L US UM U US UM UL Power supply unit Protocol chip LED AND gates Parallel-to-serial converters IB P S

108629_en_00 PHOENIX CONTACT 9 / 18

7 Design of a PLCnext Inline station

Figure 3 Design of a PLCnext Inline station 1 End clamp (e.g., CLIPFIX 35-5, Order No. 3022276)

2 PLCnext controller for Axioline F (in the example: AXC F 2152)

3 Inline adapter terminal

4 Inline terminals corresponding to the application

5 End plate (snap onto the DIN rail as station end)

R AXC F 2152 BSA U PF RDY FAIL 3 4 5

108629_en_00 PHOENIX CONTACT 10 / 18 8M o u n t i n g 8.1 Removing the controller The controller must be removed in order to mount the bus base module of the Inline adapter terminal. Figure 4 Removing the controller

  • Insert a suitable tool (e.g., bladed screwdriver) into the upper and lower snap-on mechanisms (base latches) of the controller one after the other and release it (A). The base latches are latched in place in the open position.
  • Remove the controller perpendicular to the DIN rail (B).

8.2 Mount bus base module

Figure 5 Mounting the bus base module

  • Place the bus base module of the Inline adapter terminal on the DIN rail (A).
  • Push the bus base module of the Inline adapter terminal into the connection of the bus base module on the controller (B). Please note: On a controller for Axioline F, only one Inline adapter terminal may be aligned to the right. Please note: Mount all the necessary modules before supplying power to the PLCnext Inline station. Modules to which power is only supplied following the controller boot process are not detected or may result in a malfunction. To ensure that the Inline adapter terminal is detected correctly, proceed as follows: - Switch on the power to the Inline adapter terminal before switching on the power to the controller or - Switch on the power to the Inline adapter terminal and the controller simultaneously. NOTE: Device defect due to impermissible firmware version The Inline adapter terminal is designed to be aligned to the right of PLCnext controllers with specific firmware versions. If you align the Inline adapter terminal next to a PLCnext controller with a firmware version that is not permitted, this can cause a device defect to the PLCnext controller. Make sure that the Inline adapter terminal is only aligned next to a PLCnext controller with a firmware version that is permitted. AXC F ... PLCnext controllers with the following firmware versions are permitted: –A X C F 2152 with firmware Version  1.2 Please note: Align the Inline adapter terminal directly on the controller. Axioline F modules may not be aligned on the controller. A SD-CARD R Ord.No.24042 67AXC F 2152 MAC A A B A B

108629_en_00 PHOENIX CONTACT 11 / 18

8.3 Snapping on the controller

Figure 6 Snapping on the controller

  • Place the controller vertically on the first bus base module and the DIN rail until it snaps into place with a click.
  • Make sure that the device connector for the bus base connection is situated above the corresponding socket on the bus base module.

8.4 Snapping on electronics modules

Figure 7 Snapping on the electronics module of the Inline adapter terminal

  • Place the electronics module of the Inline adapter terminal vertically on the corresponding bus base module and on the DIN rail until it snaps into place with a click.
  • Make sure that the device connector for the bus base connection is situated above the corresponding socket on the bus base module.
  • Mount the electronics modules of all necessary Inline terminals. Note the assembly instructions in the device- specific packing slip.

8.5 Mount Inline connector

Figure 8 Insert Inline connector

  • Insert the Inline connectors in the specified order (A, B). SD-CARD R Ord.No. 2404267 AXC F 2152 B A

108629_en_00 PHOENIX CONTACT 12 / 18

9 Connecting the supply voltage

Figure 9 Connecting cables

  • Strip 8 mm off the cables.
  • Release the spring by pressing with the screwdriver.
  • Insert the cable into the terminal point.
  • Secure the cable by removing the screwdriver. Recommended: flat-bladed screwdriver with blade dimensions of 0.6 mm x 3.5 mm x 100 mm (e. g., SZF 1-0,6X3,5, Order No. 1204517) Terminal point assignment Figure 10 Terminal point assignment Key: NOTE: Device defect due to impermissible firmware version The Inline adapter terminal is designed to be aligned to the right of PLCnext controllers with specific firmware versions. If you align the Inline adapter terminal next to a PLCnext controller with a firmware version that is not permitted, this can cause a device defect to the PLCnext controller. Make sure that the Inline adapter terminal is only aligned next to a PLCnext controller with a firmware version that is permitted. AXC F ... PLCnext controllers with the following firmware versions are permitted: –A X C F 2152 with firmware Version  1.2 B A C Terminal point Assignment

1.1 U S (24 V DC)

1.2 U ILC (24 V DC)

1.3 GND UILC

1.4 FE

2.1 U M (24 V DC)

2.2 U M (24 V DC)

2.3 GND U M/US

2.4 FE US (24 V DC) 24 V supply for segment circuit UM (24 V DC) 24 V supply for main circuit UILC (24 V DC) 24 V main voltage / 7.5 V logic supply /

24 V analog supply

FE Functional earth ground 1.12 .1 1.22 .2 1.3 2.3 1.42 .4 1.1 1.2 1.3 1.4 2.1 2.3 2.4 2.2

108629_en_00 PHOENIX CONTACT 13 / 18

10 Connection example

Figure 11 Connection example Key: AXC F ... I/O I/O I/O AXC F IL AD APT AXC F IL ADAPT Inline adapter terminal I/O Inline terminals corresponding to your application INTERBUS INTERBUS devices according to your application

108629_en_00 PHOENIX CONTACT 14 / 18

11 Diagnostics and status indicators

Figure 12 Diagnostic and status indicators FAIL RDY BSA PF U Designa- tion Color Meaning State Description RDY Green INTERBUS master On INTERB US master in the RUN state Flashing INTERBUS master in the READY or ACTIVE state OFF INTERBUS master is not ready to operate FAIL Red Error On Bus, controller or user error OFF No error BSA Yellow Bus segment On At least one bus segment aborted OFF No bus segment aborted PF Yellow Peripheral fault On Peripheral faul t on at least one device in INTERBUS OFF No peripheral fault U Green Supply voltages U S, UM, UL On Supply voltages U S, UM, UL present OFF At least one of th e supply voltages US, UM or UL is not present

108629_en_00 PHOENIX CONTACT 15 / 18

12 Supported INTERBUS master services

Firmware services are used to carry out the configuration, parameterization, and diagnostics of INTERBUS. The Inline adapter terminal (INTERBUS master) supports the following INTERBUS G4 services (some of which have a limited scope of functions): For more detailed information on the INTERBUS G4 services, please refer to the IBS SYS FW G4 UM E user manual. The user manual can be downloaded at phoenixcontact.net/products. The following restrictions apply for the INTERBUS master: - Support for INTERBUS devices with slave protocol chip SUPI3 or higher - No FO diagnostics - No single-channel diagnostics - No support for LPC1 or LPC2 - No isolated disconnection possible Code (hex) Service Description

0306 Initiate_Load_Configuration Create configuration frame for data transmission

  • Max. 127 characters - Can only be set when New_Config = 1

0307 Load_Configuration Transmit the device data for a configuration

Used_Attributes: Bit 0: device number Bit 1: device code Bit 2: reserved Bit 3: device level Bit 4: logical group number (always FFFF hex) Bits 5 ... 13: reserved Bit 14: extended device information Bit 15: reserved

0308 Terminate_Load_Configuration Terminate the transmission of configuration data (only for au-

tomatic parameterization) Default_Parameter: The PCP channel is always parameterized automatically. The process data channel is only parameterized automati- cally if bit 0 is set.

0309 Read_Configuration Read various entries of the configuration directory

Used_Attributes: Bit 0: device number Bit 1: device code Bit 2: reserved Bit 3: device level Bit 4: logical group number Bits 5 ... 7: reserved Bit 8: global_bus_error Bit 9: separate_bus_error (Reconf and Watchdog not sup- ported) Bit 10: device status Bits 11 ... 13: reserved Bit 14: extended device information Bit 15: reserved

108629_en_00 PHOENIX CONTACT 16 / 18 030A Complete_Load_Configuration Transmit a ll the device data for a configuration Used_Attributes: Bit 0: device number Bit 1: device code Bit 2: reserved Bit 3: device level Bit 4: logical group number (always FFFF hex) Bits 5 ... 13: reserved Bit 14: extended device information Bit 15: reserved 030B Complete_Read_Configuration Read all the device data for a configuration Used_Attributes: Bit 0: device number Bit 1: device code Bit 2: reserved Bit 3: device level Bit 4: logical group number (always FFFF hex) Bits 5 ... 13: reserved Bit 14: extended device information Bit 15: reserved 030C Delete_Configuration Delete inactive configuration frames from the configuration directory 030E Control_Parameterization Start or end the parameterization phase 030F Control_Statistics Control statistical diagnostics

0314 Control_Device_Function_Not_Exclusive Se nd control commands to local bus device

Device_Function: 0003hex: Conf_Dev_Err 0004hex: Conf_Dev_Err_All

0315 Read_Device_State Read status of local bus devices

Device_State_Mask: Bits 0 ... 10: reserved Bit 11: peripheral fault Bits 12 ... 15: reserved

0316 Get_Error_Info Request additional error information

0328 Compact_Load_Process_Data_Refer-

ence_List Configure controller board without software support - Permitted addresses: 0000hex ... 03FFhex - No overlapping or duplication possible - Modules up to max. 8 bits with Byte-Cons at every address, modules > 8 bits only at even addresses

0329 Compact_Read_Pr ocess_Data_Refer-

ence_List Read address lists of the control or computer system that were configured using the “Compact_Load_Process_- Data_Reference_List” service (3028hex) 032A Get_Version_Info Read version information 032B Get_Diag_Info Read local bus counter

0351 Read_Value Read system parameter

Supported values for the Variable_ID parameter: see next table

0701 Start_Data_Transfer Start data transfer

0702 Stop_Data_Transfer Stop data transfer

Code (hex) Service Description

108629_en_00 PHOENIX CONTACT 17 / 18 Supported values for the Variable_ID parameter

0710 Create_Configuration R ead the connected bus

0711 Activate_Configuration Check the config uration frame matches the connected bus

and whether addresses overlap

0712 Deactivate_Configuration Dea ctivate configuration frame

0713 Control_Active_Configuration Swi tch INTERBUS device on or off. Only Switch_Codes 0004hex (Device_Disable) and 0005hex (Device_Enable) are supported. Switching or bridging has no influence on the position of the process data in the memory or the CR assignment of the PCP devices.

0714 Control_Device_Function Send co ntrol commands to local bus device

Device_Function: 0003hex: Conf_Dev_Err 0004hex: Conf_Dev_Err_All

0750 Set_Value Assign new values to system parameters

Supported values for the Variable_ID parameter: see next table

0760 Confirm_Diagnostics Update diagnostic display and diagnostic register

1303 Alarm_Stop Reset local bus

Code (hex) Service Description Variable_ID (hex) System parameter Value/note

0101 State of the system management Read access only

0104 Contents of the diagnostic status register Read access only

0105 Contents of the diagnostic parameter register Read access only

010D Contents of the extended diagnostic parameter regis- ter Read access only

2200 Operating mode 0000 0000

hex: asynchronous 0600 0000hex: asynchronous with synchronization pulse

2204 Control the behavior of the input data in the event of a

0: input data in the MPM is frozen (default setting) 1: input data in the MPM is set to zero

2210 Specified process data cycle time in s (32-bit value) Permissible value range:

0000 0000hex: off 0000 0100hex ... 0001 FB00hex

2211 Bus timeout in s (32-bit value)

Default setting: 200 ms Permissible value: 0000 0000hex: (default setting)

2212 Bus warning time in s (32-bit value)

Default setting: 0 (not activated) Permissible value range: 0000 00100hex ... 000F FF00hex

2216 Actual process data cycle time in s (32-bit value) Read access only

2218 Data cycle time in s (32-bit value) Read access only

A228 Read baud rate Read access only 0: 2 Mbaud 1: 500 kBaud

108629_en_00 18 / 18PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany phoenixcontact.com

13 PCP communication

The Inline adapter terminal (INTERBUS master) supports the Peripherals Communication Protocol (PCP) Version 2.0 with Peripherals Message Specification (PMS). Peripherals Network Management 7 (PNM7) services are not supported. For information on PCP communication, please refer to the PCP user manuals (see Ordering data). Code (hex) Service

0081 Read_Request

4081 Read_Indication

C081 Read_Response

8081 Read_Confirmation

0082 Write_Request

4082 Write_Indication

C082 Write_Response

8082 Write_Confirmation

0885 Information_Report_Request

4885 Information_Report_Indication

0086 Status_Request

8086 Status_Confirmation

0087 Identify_Request

8087 Identify_Confirmation

008B Initiate_Request 408B Initiate_Indication C08B Initiate_Response 808B Initiate_Confirmation 088D Abort_Request 488D Abort_Indication 488E Reject_Indication

0264 Load_CRL_Attribute_Loc_Request

8264 Load_CRL_Attribute_Loc_Confirmation