WM15 CARLOGAVAZZI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 17
Technical content
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Power analyzer for three-phase systems
Description
WM15 is a power analyzer for single-, two- and three-phase systems. Depending on the model, WM15 is equipped with a static output (pulse or alarm) or with a static output and a Modbus RTU communication port. The self-powered version can be installed on systems up to 415 V L-L (400 V L-L for MID models), while the version with auxiliary power supply can be installed on systems up to 600 V L-L. In combination with VMUBM2US1B1C, collected data can be transmitted via M-Bus. Benefits
- Enhanced readability. The backlit graphical display allows the size of the digits to be adapted to the displayed variable. The instantaneous values of the current are also shown by a bar graph to have the plant situation at a glance.
- Easy navigation. The setup and navigation of the pages are very intuitive thanks to the user interface with 4 mechanical push buttons. In addition, the slideshow function automatically displays the desired measurements in sequence without having to use the keypad.
- Quick setup. Wizard and wiring correction on first startup, UCS mobile app for setup via OptoProg and optical port are some of the advantages allowing a quick, guided and errorless installations and commissioning. UCS software is available for free download.
- Accurate measurement. It is compliant with the international accuracy standard IEC/EN62053-21, and the IEC/EN61557-12 performance requirements (active power and active energy).
- Fiscal metrology. WM15 configuration access can be locked and terminals can be sealed in case of a MID certified model for fiscal metering.
- Installation flexibility. WM15 is suitable for single- phase, two-phase, three-phase and wild-leg systems with different voltage levels and grid frequencies used worldwide.
Applications
WM15 can be installed in any switchboard to control energy consumption, main electrical variables and harmonic distortion. In panel boards, where typically three analogical ammeters are installed to give a visual feedback of the system status, WM15 provides the same information on the matrix display by means of the bar graphs. When used to monitor a single machine, WM15 relates the energy consumption with the operating hours to schedule maintenance and detect faults. Moreover, the reset of partial counters allows to monitor each machine cycle. Thanks to the MID certification, it can also be used for fiscal metrology. Main functions
- Measure main electrical variables and voltage and current harmonic distortions
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021
- Measure active and reactive energy
- Measure apparent energy
- Measure load operating hours
- Transmit data to other systems via Modbus RTU
- Manage a digital output for pulses or alarm transmission
- Visualize measured variables on display and current consumption via bar graph Main features
- System and phase variables (V L-L, V L-N, A, W/var, VA, PF, Hz)
- Current and power (kW/kVA) demand calculation
- Simplified 4 push buttons user interface
- Optical port for easy configuration and diagnostic via OptoProg
- Digital output for pulse transmission or alarm
- Optional RS485 Modbus RTU (100 ms data refresh)
- Continuous sampling of each voltage and current
- Backlit matrix LCD display
- MID certified version
- cULus approved (UL 61010)
- Compliant with IEC/EN61557-12 performance requirements (active power and active energy) UCS software and UCS Mobile application
- Free download: UCS desktop from Carlo Gavazzi website, UCS Mobile from Google Play Store
- Configuration via OptoProg (via Bluetooth) or RS485 from PC (via UCS desktop) or Android mobile device (via UCS Mobile)
- Setups can be saved offline for serial programming with a single command
- Real time data view for testing and diagnostics
- Notification of possible wiring errors and display of the corrective steps, reassignment of the correct association of the phases or the direction of the currents via software control.
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Structure Fig. 1 Front Area Description A Optical port for easy programming and diagnostic via Optoprog B Matrix LCD display C Mechanical push buttons D Grooves for lateral brackets
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Fig. 2 Back Area Description A Power supply: auxiliary version (non-MID models only) B 3-phase voltage input C RS485 + digital output D 3-phase current inputs
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021
Features
Material Housing: PC/ABS (UL94 V1) Transparent cover: PC (UL94 V2) Protection degree Front: IP51 Terminals: IP20 Terminals Screw fixed terminal block, min:0.05; max: 2.5 mm2 Overvoltage category Cat. III Pollution degree 2 Mounting Panel 96 x 96 Weight 280 g Environmental specifications Operating temperature From -25 to +55 °C/from -13 to +131 °F Storage temperature From -25 to +70 °C/from -13 to 158 °F Electromechanical environ- mental condition E2 Mechanical environmental condition M2 NOTE: R.H. < 90 % non-condensing @ 40 °C / 104 °F.
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Input and output insulation Type Power supply (H) [kV] Measurement inputs [kV] Digital output [kV] RS485 serial port [kV] Power supply (H) - Base (AV5 3H) Double/Reinforced Double/Reinforced Measurement inputs Base (AV5 3H) - Double/Reinforced Double/Reinforced Digital output Double/Reinforced Double/Reinforced - Functional (100 V ac/ dc) RS485 serial port Double/Reinforced Double/Reinforced Functional (100 V ac/ dc) - According to: EN 61010-1, EN 50470-1 (MID). Overvoltage category III. Pollution degree 2. Compatibility and conformity Directives 2014/32/EU (MID) 2014/35/EU (LVT - Low Voltage) 2014/30/EU (EMC - Electro Magnetic Compatibility) 2011/65/EU (Electric-electronic equipment hazardous substances) Standards Electromagnetic compatibility (EMC) - emissions and immunity: EN 62052-11; EN 50470-1 (MID) Electrical safety: EN 61010-1, EN 50470-1 (MID) Metrology: EN62053-21, EN62053-23, IEC61557-12, EN 50470-3 (MID), IEC/EN61557-12 (active power and active energy, MID models only) Pulse output: IEC 62053-31 Approvals Electrical specifications Electrical system Managed electrical system Single-phase (2-wire) Two-phase (3-wire) Three-phase with neutral (4-wire) Three-phase without neutral (3-wire) Wild leg system (three-phase, four-wire delta) MID managed electrical system Three-phase with neutral (4-wire) Three-phase without neutral (3-wire) (ARON) Voltage inputs - MID Voltage connection Direct Rated voltage L-N 230 V Rated voltage L-L 400 V Voltage tolerance From 0.8 to 1.15 Un Overload Continuous: 1.5 Un max Input impedance Refer to “Power supply” Frequency 50 Hz
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Voltage inputs Non MID models AV5 3X AV5 3H Voltage connection Direct Rated voltage L-N (from Un min to Un max) 120 to 240 V 120 to 347 V Rated voltage L-L (from Un min to Un max) 208 to 415 V 208 to 600 V Voltage tolerance From 0.8 to 1.15 Un Overload Continuous: 1.5 Un max Input impedance Refer to “Power supply” >1600 kΩ Frequency From 45 to 65 Hz Note: for MID versions the voltage range is limited to 3x230 (400) V, frequency to 50Hz. NOTE: WM15 can also be installed in a wild leg system (three phases, four delta wires), where one of the phase-neutral voltages is higher than the other two. Fig. 3 AV5 3H Fig. 4 AV5 3X, AV5 3H Current inputs Current connection Via CT CT transformation ratio 2000 max Rated current (In) 5 A Minimum current (lmin) 0.05 A Maximum current (lmax) 6 A Start-up current (lst) 10 mA Overload For 500 ms: 20 Imax (120 A) Input impedance < 0.2 VA Crest factor 3 Measurement type by means of internal shunts non mutually insulated (AV5 3X) by means of internal CT (AV5 3H) Power supply AV5 3X AV5 3H Type Self power supply Auxiliary power supply from 120 to 240 V ac/dc Frequency 50/60 Hz
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Measurements Method TRMS measurements of distorted waveforms Available measurements Active energy Unit System Phase Imported (+) Total kWh+ ● ● Imported (+) partial kWh+ ● - Exported (-) Total kWh- ● - Exported (-) partial kWh- ● - Reactive energy Unit System Phase Imported (+) Total kvarh+ ● - Imported (+) partial kvarh+ ● - Exported (-) Total kvarh- ● - Exported (-) partial kvarh- ● - Apparent energy Unit System Phase Total kVAh ● - Partial kVAh ● - Run hour meter Unit System Phase Total (kWh+) hh:mm ● - Partial (kWh+) hh:mm ● - Total (kWh-) hh:mm - ● - Partial (kWh-) hh:mm - ● - Electrical variable Unit System Phase Voltage L-N V ● ● Voltage L-L V ● ● Current A ● ● DMD A - ● DMD MAX A - ● Active power W ● ● DMD W ● - DMD MAX W ● - Apparent power VA ● ● DMD VA ● - DMD MAX VA ● - Reactive power Var ● ● Power factor PF ● ● Frequency Hz ● - THD Current* THD A % - ● THD Voltage L-N* THD L-N % - ● THD Voltage L-L* THD L-L % - ● * Up to 15th harmonic NOTE: the available variables depend on the type of system set. Total imported active energy (kWh TOT) is the only MID certified meter. Apparent energy, reactive energy and exported active energy are not MID certified. Partial meters are not MID certified. All the variables calculated by the meter are referred to the primary current of the current transformer.
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Energy metering For every measuring interval time, the energies of the single phases are summed; according to the sign of the result, the positive (kWh+) or negative totalizer (kWh-) is increased. Example: P L1= +2 kW, P L2= +2 kW, P L3= -3 kW Integration time = 1 hour +kWh=(+2+2-3)x1h=(+1)x1h=1 kWh -kWh=0 kWh Measurement accuracy Current From 0.1 In to Imax ± 0.5% rdg From 0.01 In to 0.05 In ± 1% rdg Phase-phase voltage From Un min -20% to Un max +15% ± 0.5% rdg Phase-neutral voltage From Un min -20% to Un max +15% ± 0.5% rdg Active and apparent power From 0.05 In to Imax (PF=0.5L - 1 - 0.8C) ± 1% rdg From 0.01 In to 0.05 In (PF=1) ± 1.5% rdg Reactive power From 0.1 In to Imax (sinϕ=0.5L - 0.5C) From 0.05 In to Imax (sinϕ=1) ± 2% rdg From 0.05 In to 0.1 In (sinϕ=0.5L - 0.5C) From 0.02 In to 0.05 In (PF=1) ± 2.5% rdg Active energy Class 1 EN62053-21, Class B EN50470-3 (MID) Reactive energy Class 2 (EN62053-23) Frequency From 45 to 65 Hz ± 0.1% rdg Measurement accuracy according to IEC/EN61557-12 (MID models) Active power Performance class 1 Active energy Performance class 2
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Measurement resolution Variable Display resolution Resolution by serial communication Energy 0.01 kWh/kvarh/kVAh 0.001 kWh/kvarh/kVAh Power 0.1 kW/kvar/kVA 0.1 W/var/VA Current* 0.1 A 0.001 A Voltage 0.1 V Frequency 0.1 Hz 0.001 Hz THD 0.01 % Power factor 0.01 *Note: value referred to CT ratio =1 Display Type Matrix 128x64 dots Refresh time 500 ms Description Backlit LCD Variable readout Instantaneous: 5+1 dgt Power factor: 1+2 dgt Energy: 8+2 dgt LED Front Red. Pulse weight: proportional to energy consumption and depending on the CT ratio (16 Hz maximum frequency): Weight (kWh per pulse) CT ratio 0.001 ≤ 7 0.01 From 7.1 to 70 0.1 From 70.1 to 700 1 From 700.1 to 2000
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Digital outputs Digital output Connection type Screw terminals Maximum number of outputs 1 Type Opto-mosfet Function Pulse output or alarm output Features VON 2.5 V ac/dc, max 100 mA VOFF 42 V ac/dc Configuration parameters Output function (pulse/alarm) Pulse weight (from 0.001 to 10 kWh per pulse) Pulse duration (30 or 100 ms) Output normal status (NO or NC) Configuration mode Via keypad or UCS software Communication ports RS485 port Protocol Modbus RTU Devices on the same bus Max 160 (1/5 unit load) Communication type Multidrop, bidirectional Connection type 2 wires Configuration parameters Modbus address (from 1 to 247) Baud rate (9.6 / 19.2 / 38.4 / 115.2 kbps) Parity (None/ Odd/ Even) Refresh time ≤ 100 ms Configuration mode Via keypad or UCS software Optical port Compatible accessories OptoProg Function Configuration and diagnostic via UCS Mobile app or UCS software
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Connection Diagrams Non MID models Fig. 5 Three-phase without neutral (3-wire) Fig. 6 Three-phase with neutral (4-wire) Fig. 7 Three-phase without neutral (3-wire) Fig. 8 Two-phase system with neutral (3-wire) Fig. 9 Single-phase (2-wire)
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 MID models Fig. 10 Three-phase with neutral (4-wire) Fig. 11 Three-phase without neu- tral (3-wire) - ARON Power supply (non MID models) Fig. 12 Auxiliary power supply (H) Output Fig. 13 Digital output
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 Communication Fig. 14 RS485 port Fig. 15 Last device on RS485
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 References Order code WM15 96 AV5 3 X Enter the code option instead of Code Options Description W - - M - - 1 - - 5 - - 9 - - 6 - - A - - V - - 5 - - 3 - - X - Self power supply. Voltage inputs 415 V LL OS Digital output and RS485 OX Digital output only X Non MID PFB MID (3P and 3P.n)
- PFB: only the total positive totalizer (kWh+) is certified according to MID. The negative energy totalizer is available but not certified according to MID. WM15 96 AV5 3 H OS X Code Options Description W - - M - - 1 - - 5 - - 9 - - 6 - - A - - V - - 5 - - 3 - - H - Auxiliary power supply, from 120 to 240 V ac/dc. Voltage inputs 600 V LL OS - Digital output and RS485 X - Non MID
Carlo Gavazzi Controls S.p.A. WM15 WM15 DS ENG 26/01/2021 CARLO GAVAZZI compatible components Purpose Component name/part number NOTES Quickly configure several analyzers via optical interface OptoProg See relevant datasheet Configure analyzer via desktop application UCS software Available for free download at: www.productselection.net Configure analyzer via Android application UCS Mobile Available for free download at: https://play.google.com/store Aggregate, store and transmit data to other sys - tems UWP 3.0 See relevant datasheet Transit data via M-Bus VMUBM2US1B1C See relevant datasheet COPYRIGHT ©2021 Content subject to change. Download the PDF: www.productselection.net