TR800WEB ZIEHL | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

Features

Web-IO Universal Relay with

8 Inputs for Temperature-

Signals. The TR800Web can be connec- ted to the internet or an intranet and operated via TCP/IP from a normal PC with a suitable brow- ser. No special software and no special instruction is necessary. The Universal-Relay TR800Web monitors and logs signals from up to 8 inputs. Up to 8 limits (one per input) can be programmed for each of the 4 output-relays. Thus e.g. alarm 1 can be acti- vated when the temperature at a sensor (e.g. Pt100) at input 1 exceeds a limit or when the signal of a transmitter for pressure (e.g. 4-20 mA) at input 5 falls below a limit. It can also send an email when a limit is exceeded and/or when the signals falls short of the limit again. A day/night switchover allows to vary limits depending on daytime. In addition the device has an interface RS485 with the protocols Modbus and ZIEHL-standard. Applications: The TR800Web is used where one or more of the following features a required: measuring of up to 8 analog signals and transmit the data via TCP/IP reading of measured values and teleservice via internet/intranet signalling of alarms via email when limits are ex- ceeded monitoring of filling levels (water, oil) with ZIEHL filling level probe NS6123-6 logging of measured values and remote inquiry e.g. for monitoring temperatures at engines and in plants Universal-Relay Type TR800Web

8 Inputs, Operation with Browser via TCP/IP

8 Measuring Inputs (each pro-

grammable): Pt100 (RTD), Pt1000 in 2- or 3-wire KTY83 or KTY84 thermocouples types B, E, J, K, L, N, R, S, T DC 0-10 V, DC 0/4-20 mA, display can be scaled resistance 0-500 Ohm, 0-30 kOhm Difference of 2 signals

4 Alarms

4 relays, potential-free change-over contacts Remote switching of relays via Ethernet for every alarm separately programmable one limit per input (limit and switching-back-value) second set of values switchable day/night switching-delay and switching-back delay remote operation of relays (on/off) with browser interlocked switching email at alarm Pt100-Temperature Relays Type TR 2018-03-14 TR800Web Part number: T224164 AC/DC 24-240 V

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de UDP- and Modbus protocol to read data (port can be selected) AJAX for data-readout in html SNMP RS485 interface to readout data with modbus (RTU) and ZIEHL-protocol Displays and Operating elements:

8 LEDs for inputs

4 LEDs for alarms, 4 LEDs for state of relays

4 digit display for measuring values 3 buttons for reading measured values at the device and for setting of IP-adress switch IP 10.10.10.10 / user reset-button LEDs for activity of interfaces Programmable via internet in web- browser display of measured values, min- and max-values with date/ time-stamp simulation of measured values state of alarms configuration of inputs (name, compensation, scaling and measuring-unit) configuration of alarms (limits, function of relays, ...) time-depending day/night chan- ging of limits logging of up to 150.000 values per input, alarms with date/time-stamp logging-interval adjustable 2 se- conds to 24 hours Pt100-Temperature Relays Type TR 2016-11-09 configuration of network settings of system administration of users and code-protection real-time clock with synchroni- zing with time-server, reserve 7 days Interfaces: Ethernet interface (http, https, UDP and Modbus) http (port can be selected and switched off) and https ftp-upload for automatic (inter- val adjustable) storage of logged data on ftp- server

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de Operating and Programming with Web-Browser: Pt100-Temperature Relays Type TR 2016-11-09

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de Technical Data TR800Web Tolerance Type of contact Measuring cycle/measuring time Inputs for voltage and current Measuring of resistance: dimensions (w x h x d) protection housing/terminals attachment weight AC/DC 24-240 V, 0/50/60 Hz < 4 W < 13 VA 4 x 1 change-over contact (CO)Typ 2 type 2 (see "general technical informations") see "general technical informations" 10/100 MBit Auto-MDIX < 3 s design V8, switchgear-mount 140 x 90 x 58 mm, mounting height 55 mm IP 30/ IP 20 DIN-rail 35 mm according to EN 60715 oder screws M4 (with 2 extra bars) app. 370 g Measuring range °C Accuracy Typ Min Max B 0 1820 ≤ ± 2 °C T > 300 °C E -270 1000 ≤ ± 1 °C J -210 1200 ≤ ± 1 °C K -200 1372 ≤ ± 2 °C L -200 900 ≤ ± 1 °C N -270 1300 ≤ ± 2 °C R -50 1770 ≤ ± 2 °C S -50 1770 ≤ ± 2 °C T -270 400 ≤ ± 1 °C Thermal drift < 0,01 % /K Measuring-error of sensor-line + 0,25 µV / Ω Accuracy of summing point < ± 5 °C Resistance of max. Accuracy input Inputsignal from Full Scale 0 - 10 V 12 k Ω 27 V < 0,1 % 0/4...20 mA 18 Ω 100 mA < 0,5 % Thermal drift < 0,02 %/ K Accuracy 0,0...500,0 Ω < 0,2 % of measured value ± 0,5 Ω Accuracy 0...30,00 kΩ < 0,5 % measured value ± 2 Ω Measuring current ≤ 0,6 mA Thermocouples according to EN 60 584, DIN 43710 Pt100, Pt1000 according to EN 60 751 Pt100-Temperature Relays Type TR Rated supply voltage Us Inputs Relay output Testing conditions Network-connection Housing Measuring Short-circuit Interruption Resistance sensor range °C Ohm Ohm + resistance line Ohm Sensor min max < > max Pt100 -199 860 15 400 500 Pt1000 -199 860 150 4000 4100 KTY83 -55 175 150 4000 4100 KTY84 -40 150 150 4000 4100 Accuracy < ± 0,5 % of measured value ± 0,5 K (KTY ±5K) Sensor-current ≤ ± 0,6 mA Thermal drift < 0,04 °C/K 2016-11-09