TF101 ZIEHL | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de General Pt100 Temperature Sensors Type TF101 1,5 2,3 10 Ø0,25 Ø 4,5 20 2000 ±10 LIYWYW 3x 0,25 mm² rt / RD rt / RD ws / WH Pt100-Temperature-Sensores Type TF Types / Description TF101 temperature sensors use EN 60751/IEC 60751 platinum resistance temperature detectors (RTD). For precise temperature measurement the Platinum Re- sistance Thermometer offers the best overall advantages in repeatability and stability over a long period. High accuracy allows replacement of a sensor without any need for re-adjust of the connected measuring devices or thermostats. Platinum resistance temperature sensor on ceramic substrate intended for installation into any housing depending to user’s re- quirements. Very small and quick sensor, only suitable for further treatment. Notice: do not cut the sensor leads. Thermal response time refer to manufacturer data: T 0,9 in the air 10 s, in water <1 s. Part number: 019061 Platinum resistance temperature sensor on ceramic substrate pro- tected by a heat-shrinkable sleeve and with PTFE isolated stranded wire. The TF101K version can be installed in motor or transformer windings. When build-in into windings do not pressure the sensor element. Precautions should be taken to protect sen- sor and extension leads against push and pull forces. Thermal response time T 0,9 in the air 100 s, in water 19 s. With 2-wire connection and cable-length of 2 m there is a temperature-failure of approx. 0.51 Ω = 1.32 K caused by the line resistance. Cable length: 2000 mm Weight: 10 g Part numbers: T223154 2-wire T223134 3-wire Sensors TF101U2 are encapsula- ted in a stainless-steel-shell V4A. They are suitable for measuring temperatures in fluids, at surfaces or for inside or outside applicati- ons. The protection class is IP 66. The version with PVC-insulated cable (3 x 0,25 mm 2 in one cable) can be easily wired. The maximum ambient temperature is 105 °C. The sensor with cable 30mm (PVC) can be mounted in ter- minals in switchgear cabinets to measure temperature in en- closure. The version with PTFE-insulation (3 x 0,14 mm 2 single wires) with- stands peak-temperatures up to 200 °C Weights: PVC: 2 m = 50 g, 10 m = 250 g, 30 mm = 15 g PTFE: 2 m = 20 g Part numbers: T223051 3-wire 2 m PVC -30...+105 °C T223058 3-wire 10 m PVC -30...+105 °C T223052 3-wire 2 m PTFE -50...+170 °C T223047 2-wire 30 mm PVC -30... +80 °C2018-01-17 rot rot weiß Ø 4,5 2000 ±10 10 TF101N -70°C...+500°C TF101K -50°C...+170°C TF101U2 -30°C...+105°C -50°C...+170°C -30°C...+80°C

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de Pt 100-Temperature-Sensors Type TF Technical Data Platinum resistance temperature sensor on ceramic substrate built into a M6 brass threaded bush, especially suitable for being screwed into metal, e.g. for monitoring temperature of heat sinks or heating plates. Please note that there will be a measuring error due to the design, as the sensor can loose heat via the connection strand. Cable length: 2000 mm Weight: 21 g. (Dimensions see Dimension illustrations) Part number: T223143 3-wire Platinum resistance temperature sensor built into steel tube V4A, 1/2 inch, suitable for installation in pipes. Thermal response time T 0,9 in the air 255 s, in water 45 s. Suitable for transmission in 2- or 3-wire technique. Weight 120 g (Dimensions see Dimension illustrations) Part number: T223137 110 mm depth of immersion Sensor for measuring ambient temperatures inside or outside. Protection class IP 54. Cabling can be connected in 2- or 3- wire technique. Housing W x H x D = 65 x 50 x 38 mm Weight: app. 70 g Part number: T223060 Nominal resistance Temperature coefficient Class B, DIN 43 760 Test voltage Extension leads Shrink sleeve max. temperature at sensors with max. 170°C 100 Ω at 0 °C 3,85 x 10 –3/K (see table) 2,5 kV AC (not 019061 and T223047) PTFE; silver-plated stranded copper wire 0,14 mm2 or PVC isolated copper wire Kynar 200 °C (max. 170 h) 2018-05-18 TF101G3 -50°C...+170°C mit Gewinde TF101ZG2 -50°C...+170°C TF101R -20...+70°C

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de RL /2 RL /2 RK = RL weißweiß weißrotrot weißrot Cabling Line-resistance Linecompensation With RTD sensors the resistance of the connecting cable should be considered, otherwise there is an measuring error. The resistance must be compensated. The resistance of a connecting cable can be calculated as follows: R [Ω] = 2 x l/(k x A), l = cable length [m], k = conductivity [S x m/mm 2] e.g. Cu = 56, A = cross sectional area [mm2] For example copper-wire: I = 50 m, cross sectional area 1 mm2: R = 2 x 50/(56 x 1) = 1,79 Ω, Resulting error = 1,79 Ω/0,385 Ω x K = 4,6 K. ZIEHL thermostats of TR series are generally insensitive to interference in the sensor line. Occasionally, however, undesirable switching is unavoidable, especially when temperature is near the switching point. For this reason it is highly recommended that cables are not laid parallel to power current lines over long distances. When appropriate, cables should be screened or twisted together. 2-wire technique With 2-wire connection the line resistance is compensated for by a potentiometer in the thermostat, by programming (e.g. TR122D, TR600) or via wiring an external resistor. The advantage of the possibly simpler and more economical running of just two wires is counter- acted by the disadvantage of the manual compensation required in the case of longer wiring. Differences in resistance caused by temperature changes cannot be compensated. 3-wire technique With 3-wire connection, a third wire (sense) connected to the sensor registers the drop in voltage in one line. For compensation of line resistance it is assumed that the voltage drop in the second line is identical (i.e. the same wire and same wire temperature). Compen - sation is then performed automatically. Possible changes of resistance in the line due to temperature changes are also compensated for. 4-wire technique With 4-wire connection, impressed current flows via two wires to the sensor. Via a two sensor line the drop in voltage is measured directly at the sensor. Possible differences in the sensor connection wiring can be disregarded. A disadvantage is the higher costs involved in running 4 wires. Kombination of 2- and 3-wire technique When connecting 2-wire-sensors to units with 3-wire input, the line resistance can be compensated by connecting a compensation resistor (Rk) between ground and sense- input. Rk must have the same value as the resistance of the line. The sensor then has to be connected to the + and the sense- input. Rk must be lower than the permitted resistance for 1 line of the 3-wire-input. Units requiring 3-wire configurations can also be operated by 2-wire sensors. The sensor input is simply shortened. The line resistance need not be compensated. 3-wire sensors can be used as 2-wire sensors, simply by omitting one wire. 2-wire sensors can be branched at any desired position in a 3 or 4-wire connection system. In this case though, the line resistance of the two wires from the branching point to the sensor is not compensated. ZIEHL thermostats, series TR are designed for use with 2 or 3-wire connection. Pt100-Temperature-Sensores Type TF red red red red red white white whitewhite

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de Pt100-Temperature-Sensors Type TF Pt100 resistance table °C Ω °C Ω °C Ω °C Ω °C Ω °C Ω -200 18,49 0 100,00 200 175,84 400 247,04 600 313,59 800 375,51 -190 22,80 10 103,90 210 179,51 410 250,48 610 316,80 810 378,48 -180 27,08 20 107,79 220 183,17 420 253,90 620 319,99 820 381,45 -170 31,32 30 111,67 230 186,82 430 257,32 630 323,18 830 384,40 -160 35,53 40 115,54 240 190,45 440 260,72 640 326,35 840 387,34 -150 39,71 50 119,40 250 194,07 450 264,11 650 329,51 850 390,26 -140 43,87 60 123,24 260 197,69 460 267,49 660 332,66 -130 48,00 70 127,07 270 201,29 470 270,86 670 335,79 -120 52,11 80 130,89 280 204,88 480 274,22 680 338,92 -110 56,19 90 134,70 290 208,45 490 277,56 690 342,03 -100 60,25 100 138,50 300 212,02 500 280,90 700 345,13 - 90 64,30 110 142,29 310 215,57 510 284,22 710 348,22 - 80 68,33 120 146,06 320 219,12 520 287,53 720 351,30 - 70 72,33 130 149,82 330 222,65 530 290,83 730 354,37 - 60 76,33 140 153,58 340 226,17 540 294,11 740 357,42 - 50 80,31 150 157,31 350 229,67 550 297,39 750 360,47 - 40 84,27 160 161,04 360 233,17 560 300,65 760 363,50 - 30 88,22 170 164,76 370 236,65 570 303,91 770 366,52 - 20 92,16 180 168,46 380 240,13 580 307,15 780 369,53 - 10 96,09 190 172,16 390 243,59 590 310,38 790 372,52 values see Pt100, multiplicated by the factor of 10. The Pt1000 sensor is the "big brother" of the Pt100 sensor. Its nominal resistance at 0°C is 1000 Ω. Resistance values of the whole series are higher by a factor of 10. The sensor is used in the same way as the Pt100 sensor. Its dimensions are slightly larger (4 x 5 un- insulated). Thermostats and sensors for Pt1000 on request. Pt1000 Temperature Sensor Pt1000 resistance table Basic values in Ω for measuring resistors Pt 100 according to DIN/ IEC 751