BATTERY BACK-UP POWER SUPPLIES 400 - 1000 WATTS APPLIED POWER CONVERSION Division of TECHNOLOGY DYNAMICS INC. AVAILABLE OPTIONS Design Excellence since 1976 SPECIFICATIONS ELECTRICAL MECHANICAL AND ENVIRONMENTAL AC Input V oltage : 90-264 V AC Standard AC Input Frequency: 47-63Hz Standard, 47-400Hz optional Regulation: Line ± .3% Load + 2% Ripple: 1% peak to peak, not to exceed 100mVpp Efficiency: 85% typical Output voltage adj: +10% on main output Overvoltage Protection: Set at 120% of main output, automatic recovery Overload Protection: Current limiting, automatic recovery Operating Temperature: 0°C to + 50°C standard Storage Temperature: -40°C to 85°C Cooling: Internal ball bearing DC fan Safety: Designed to meet UL 1950, CSA 1402 A Humidity: 90% non condensing Weight: Approx: 25lbs (deppending on battery type & size) The TCPBX Series satisfies an emerging market where "critical" continuous power is required. Designed as a complete system with power supply and on board batteries, the TCPBX Series is ideal for portable harsh Industrial and Communication applications where no downtime is critical. Portable DC power where and when you need it. STANDARD FEATURES

APPLICATIONS

  • Compact, light weight
  • Rugged Construction
  • OV/OL/OT Protected
  • Built-In On Board Premium Batteries
  • Input and battery circuit breakers
  • MS Connectors
  • Low V oltage Battery Disconnect
  • Portable or Bolt Down Models
  • Redudant Operation (N+1)
  • Premium Batteries
  • Low V oltage Battery Disconnect (LVBD) for Battery Back-Up operation
  • Conformal Coating
  • Additional EMI Filtering
  • Power Factor Correction
  • Ruggedized for Shock and Vibration
  • AC Line Cord

TECHNOLOGY DYNAMICS INC.

100 School Street, Bergenfield, NJ 07621

Phone: (201) 385-0500, Fax: (201) 385-0702 W ebsite: www .theallpower .com SPECIFICA TIONS ARE SUBJECT T O CHANGE WITHOUT NOTICE MODEL SELECTION MECHANICAL OUTLINE NOTE: MINIMUM QUANTITY PURCHASE REQUIRED ON MOST MODELS. OTHER VOLTAGES & CURRENTS ARE A V AILABLE CONTACT THE FACTORY FOR DETAILS. PREMIUM BATTERIES A V AILABLE FOR HARSH ENVIRONMENT OPERATION. MODEL OUTPUT MODEL OUTPUT MODEL OUTPUT MODEL OUTPUT TCP-BX-BBU-12-33 12V (13.5V) @ 33A TCP-BX-BBU-12-50 12V (13.5V) @ 50A TCP-BX-BBU-12-66 12V (13.5V) @ 66A TCP-BX-BBU-24-41 24V (27.6V) @ 41A TCP-BX-BBU-24-17 24V (27.6V) @ 17A TCP-BX-BBU-24-25 24V (27.6V) @ 25A TCP-BX-BBU-24-33 24V (27.6V) @ 33A TCP-BX-BBU-48-20 48V (54V) @ 20A TCP-BX-BBU-48-8 48V (54V) @ 8A TCP-BX-BBU-48-12 48V (54V) @ 12A TCP-BX-BBU-48-16 48V (54V) @ 16A

400 WATT POWER SUPPLY 600 WATT POWER SUPPLY 800 WATT POWER SUPPLY 1000 WATT POWER SUPPLY

400 WATTS BACK-UP FOR 30 MIN. 600 WATTS BACK-UP FOR 10 MIN. 800 WATTS BACK-UP FOR 5 MIN. 1000 WATTS BACK-UP FOR 3 MIN. Optional Line Cord or MS Connector for AC input