w .moxa.com TCC-120/120I Series Industrial RS-422/485 converters/repeaters with optional 2 kV isolation Features and Benefits

  • Boosts serial signal to extend transmission distance
  • Wall mounting or DIN-rail mounting
  • Terminal block for easy wiring
  • Power input from terminal block
  • DIP switch setting for built-in terminator (120 ohm)
  • Boosts RS-422 or RS-485 signal, or converts RS-422 to RS-485
  • 2 kV isolation protection (TCC-120I) Certifications Introduction The TCC-120 and TCC-120I are RS-422/485 converters/repeaters designed to extend RS-422/485 transmission distance. Both products have a superior industrial-grade design that includes DIN-rail mounting, terminal block wiring, and an external terminal block for power. In addition, the TCC-120I supports optical isolation for system protection. The TCC-120 and TCC-120I are ideal RS-422/485 converters/repeaters for critical industrial environments. Specifications Serial Interface Connector Terminal block No. of Ports 2 Serial Standards RS-422, RS-485 Baudrate 50 bps to 921.6 kbps (supports non-standard baudrates) Isolation TCC-120I: 2 kV Pull High/Low Resistor for RS-485 1 kilo-ohm, 150 kilo-ohms RS-485 Data Direction Control ADDC® (automatic data direction control) Terminator for RS-485 N/A, 120 ohms, 120 kilo-ohms Serial Signals RS-422 Tx+, Tx-, Rx+, Rx-, GND RS-485-4w Tx+, Tx-, Rx+, Rx-, GND RS-485-2w Data+, Data-, GND Power Parameters Input Current TCC-120: 65 mA @ 12 VDC TCC-120I: 180 mA @ 12 VDC Input Voltage 12 to 48 VDC

w .moxa.com No. of Power Inputs 1 Overload Current Protection Supported Power Connector Terminal block (for DC models) Power Consumption TCC-120: 65 mA @ 12 VDC TCC-120I: 180 mA @ 12 VDC Physical Characteristics Housing Metal IP Rating IP30 Dimensions 67 x 100.4 x 22 mm (2.64 x 3.93 x 0.87 in) Weight 148 g (0.33 lb) Installation DIN-rail mounting (with optional kit), Wall mounting Environmental Limits Operating Temperature Standard Models: -20 to 60°C (-4 to 140°F) Storage Temperature (package included) -40 to 85°C (-40 to 185°F) Ambient Relative Humidity 5 to 95% (non-condensing) Standards and Certifications EMC EN 55032/24 EMI CISPR 32, FCC Part 15B Class A EMS IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 1 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 3 V/m; Signal: 3 V/m IEC 61000-4-8 PFMF Environmental Testing IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-3 Safety EN 60950-1, IEC 60950-1 Vibration IEC 60068-2-6 MTBF Time 1,949,025 hrs Standards Telcordia (Bellcore), GB Warranty Warranty Period 5 years Details See www.moxa.com/warranty Package Contents Device 1 x TCC-120/120I Series isolator Cable 1 x terminal block to power jack converter

w .moxa.com Installation Kit 1 x DIN-rail kit 1 x rubber stand Documentation 1 x quick installation guide 1 x warranty card Dimensions

Ordering Information

Model Name Isolation Operating Temp. TCC-120 – -20 to 60°C TCC-120I ✓ -20 to 60°C Accessories (sold separately) DIN-Rail Mounting Kits DK35A DIN-rail mounting kit, 35 mm Power Cords CBL-PJTB-10 Non-locking barrel plug to bare-wire cable © Moxa Inc. All rights reserved. Updated Apr 14, 2020. This document and any portion thereof may not be reproduced or used in any manner whatsoever without the express written permission of Moxa Inc. Product specifications subject to change without notice. Visit our website for the most up-to-date product information.