STL48-200L TYCONASYSTEMS | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 2

Technical content

Features

  • Solar Ready™
  • 48V MPPT Charge Controller with 7 Port GigE PoE Switch. Ports can be configured for 802.3at or 24V Passive PoE. Remote Monitoring and Control.
  • Weatherproof, UV resistant, outdoor enclosures
  • Powered from AC mains power and/or Solar
  • LFP (LiFePO4) Lithium Batteries
  • Interior space for customer electronics
  • Wall or Pole Mounting

Applications

  • Wireless Base Stations and Clients • Surveillance Cameras
  • Wireless Bridge and Repeaters • Remote Sensors
  • Mission critical outdoor power • Backup Power Systems

Description

The UPSPro® STL48-200L outdoor enclosures are designed for applications that require a flexible backup power source in order to maintain uninterrupted service to customers. The enclosure is powered from 120/240VAC. It is also solar ready (blocking diodes may be required) , so a solar panel can be a dded as an alternate power source or to extend backup time. Features include an advanced MPPT charge controller with 7 Port GigE PoE switch and built-in remote monitoring and management. The PoE switch ports can be configured as 802.3at or 24V Passive PoE . There is a configurable wire terminal aux port. The steel enclosure has multiple ports for CAT5 cable, antenna cables/connectors or other cabling. They have thermostatically controlled power ventilation which turns on automatically when inside temperature exceeds 45C. There is some space inside the enclosures for customer electronics such as controllers, wireless AP or CPE cards, sensors, inverters, etc. There is a 1U rack mount feature in the enclosure for rack mounting. Equipment runs on battery power which isolates it from power line surges which is a main cause of outdoor equipment failure. DATA SHEET UPSPro ® STL48-200L Series UPSPro® STL48-200L Steel Enclosure UPSTL48-200L-900 500W Charger 900W Charger

UPSPro® STL48-200L UPSPro® STL48-200L Series Spec Rev 1 25-May-23 Specifications Subject to Change Without Notice Page 2 Specifications System Ordering: Model # Enclosure Type Battery Voltage Battery Capacity Total Watt Hours Storage Capacity Backup Time at 50W Avg Load Charging Power System Weight UPS-STL48-200L-500 Powder Coat Steel 48VDC 200Ah 2400 38hrs 500W 137lb (62kg) UPS-STL48-200L-900 Powder Coat Steel 48VDC 200Ah 2400 38hrs 900W 138lb (63kg) Note: The Lithium batteries used in these systems do not have heaters. Batteries will continue to supply power but will not accept a charge if battery temperature drops below 0ºC (32ºF). These systems are only recommended for milder winter climates. For further information contact: UPS-STL48-200L-600 UPS-STL48-200L-900 Battery Voltage (DC) 48V Input Voltage (AC) 100/240VAC, 47/63Hz Battery Capacity 200Ah Avail Storage Capacity 2400Wh Charger Output Power 500W 900W Maximum MPPT Controller Load 150W 48V outputs, 72W 24V outputs (overall total 222W) Battery Type LFP (LiFePO4) Lithium without heater Battery Life 10+ Years Battery Cable Fuse 40A 250V Blade Fuse Controller Type 20A MPPT Solar Controller with 7 port GigE PoE Switch, 4 ports configurable as 802.3at or 24V Passive, 3 ports configurable as 24/48V Passive PoE, Aux port configurable as 24/48V 2.25A, Managed, Email Alerts, Data Logging, Remote Management Maximum Solar Panel Size 960W Bulk Charge 58.4V Over-discharge protection 51.2V Over-discharge recovery voltage 51.5V Controller Self Consumption <3.5W Enclosure Type Powder Coated Steel – Pole/Wall Mount – Padlock Closure Enclosure Internal Size 23.9 x 23.9 x 16.1" (608 x 608 x 409.5mm) Operating Temperature -0°C to +60°C (32°F to 140°F) System Weight (without batteries) 75lb (34kg) 76lb (34.4kg) Battery Weight 4 x 13.5lb (6kg) Certifications Individual components used have CE Certifications. Warranty 3 Years Tyconsystems.com

930 W 14600 S Suite 600

Bluffdale, UT 84065 PH: 801-432-0003 FAX: 801-618-4220 To calculate run time: Battery Capacity (Ah) / 1.25 / Load Amps = Estimated Run Time in Hours ---OR--- Storage Capacity (Wh) / 1.25 / Load Watts = Estimated Run Time in Hours. Example: Estimated load = 50W and Storage Capacity is 2400Wh. 2400 / 1.25 / 50 = 38hrs run time. Note: We divide by 1.25 because we don’t want to discharge the battery more than 75% in order to extend its life.