SC210W MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 13

Technical content

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 1/13 http://www.m-system.co.jp/ Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER (color LCD with touch-panel, MV output backup, Modbus/NestBus communication, expansion module function) 144 (5.67) (2.83) mm (inch) *Selectable with option code MODEL: SC210W-[1][2]-[3][4]

ORDERING INFORMATION

  • Code number: SC210W-[1][2]-[3][4] Specify a code from below for each of [1] through [4]. (e.g. SC210W-11-M2/3/M2/E/1/T/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01) [1] DISCRETE OUTPUT 1: Relay contact 2: Photo MOSFET relay [2] MODBUS 1: Modbus-RTU 2: Modbus/TCP [3] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [4] OPTIONS (multiple selections) Housing Depth (must be specified) /3: 300 mm /4: 400 mm Backup Module Power Supply blank: Single supply /M2: 100 – 240 V AC (dual supply) (Operational voltage range 85 – 264 V AC; 50/60 Hz) /R: 24 V DC (dual supply) (Operational voltage range 24 V DC ±10 %; ripple 10 %p-p max.) Control/Backup modules are powered from common terminals with 'single' supply type; powered from independent terminals with 'dual' supply type. Language blank: Japanese /E: English (Language (Japanese or English) can be chosen by front panel setting.) Configurator Interface (must be specified) /1: Stereo jack Terminal block (must be specified) /T: Separable terminal Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel FUNCTIONS & FEATURES Functions & Features
  • Color LCD with touch panel
  • Five Operation views (digital display, bargraph, dual-loop bargraph, short trend and user's parameter table views)
  • Enhanced Engineering views (configuration, programming, tuning, and backup views)
  • Universal input x 2 points, analog input x 4 points, discrete or pulse input x 6 points
  • Current output (4-20 mA) x 2 points, voltage output (1-5 V) x 2 points, relay or photo-MOSFET relay output x 5 points
  • RUN contact output (relay) x 1 point
  • Expandable I/O points by connecting remote I/O modules via NestBus peer-to-peer communication
  • Computation cycle selectable from 100 msec. to 3 sec. (control cycle selectable from 1 to 64 times of the computation cycle)
  • Two PID function blocks
  • Advanced computation and sequence control functions
  • Auto-tuning function for automatically setting PID parameters
  • Parameter input and change with touch panel

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 2/13 http://www.m-system.co.jp/

  • Loop Configuration Builder Software (model: SFEW3E) for function parameter setting, list printing and data downloading/uploading
  • PC Configurator Software (model: SCCFG) for exporting short trend data (CSV), and storing/transferring display parameter setting
  • Control and supervision by SCADA software via Modbus TCP/IP or RTU communication
  • Backup module (applicable to Mv2 only) is incorporated for manual loading: MV output is automatically switched to manual control in case of control module abnormality
  • Independently powered and controlled backup module
  • Easy extraction of control module at the front for replacement while MV output is maintained
  • Housing with selectable depth enabling use of existing wires at replacement: 300 mm and 400 mm
  • Separable terminal block
  • Expansion of operations blocks due to Expansion module Typical Applications
  • Replacement of conventional controllers
  • Panel operation for small-scale instrumentation

RELATED PRODUCTS

  • PC Configurator cable (model: COP-US)
  • Loop configuration builder software (model: SFEW3E Ver. 1.101 or later)
  • PC configurator software (model: SCCFG Ver.1.84 or later) Builder software and configurator software are downloadable at M-System’s web site. ACCESSORIES
  • Precision resistor module (model: REM4): 2 units
  • Cold junction compensation sensor: 2 pcs
  • Mounting brackets: 2 pcs
  • Connector adapter: 1 pce (The jack on the unit and the plug of PC Configurator cable (not included in the product) are different in size.) GENERAL SPECIFICATIONS Construction: Panel flush mounting Degree of protection: IP55; ensured for the front panel of the unit independently mounted to a panel Connection Terminal screws: M3.5 screw terminals (torque 1.0 N·m) Terminal fixing screws: M4 screw terminals (torque 1.2 N·m) Backup module power supply terminal (option /M2, /R): stripped length 10 mm) Ethernet: RJ-45 Modular Jack Screw terminal Terminal screws: Nickel-plated steel (standard) or stainless steel Terminal fixing screws: Chrome-plated steel Housing material: Flame-resistant resin (gray), steel Isolation: Pv1 to Pv2 to supply output to Ai1 or Ai2 or Ai3 or Ai4 to Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Mv2B to Ao1 or Ao2 to Do1 to Do2 to Do3 to Do4 to Do5 to Do6 to NestBus to Modbus-RTU to Modbus/TCP to power to backup module power to FG PID control: Single loop, cascade, advanced Proportional band (P): 1 to 1000 % Integral time (I): 0.01 to 100 minutes Derivative time (D): 0.01 to 10 minutes Auto-tuning: Limit cycle method Alarm: PV high & low, deviation, rate of change Computation: 48 functions blocks available for arithmetic operations, time functions, signal selection, limit, alarm and other functions Sequence operation: Logic sequence and step sequence (max. 1068 commands) Computation cycle: 100 msec. to 3 sec. (control cycle selectable among 1, 2, 4, 8, 16, 32 and 64 times of the computation cycle) MV output range: -15 - +115 % Parameter setting: With touch panel or PC (Loop Configuration Builder Software model: SFEW3E) Self diagnostics: CPU monitoring with a watchdog timer RUN contact: OFF in error detected by diagnostic (including NestBus) Short trend Storing interval: 1, 2, 5, 10, 20, 30 sec., 1, 2, 5, 10, 30, 60 min. Capacity: 400 points (display 200 points) ■ Display Display device: 4.3-inch TFT LCD Display colors: 256 Resolution: 480 × 272 pixels Pixel pitch: 0.198 × 0.198 mm (128 × 128 DPI) Backlight: LED Backlight life: Approx. 50 000 hours (at 50 % brightness) Note: The backlight can be replaced in M-System factory. The LCD must be replaced at the same time. Screen saver standby time: 1 to 99 minutes Scaling range: -32000 to +32000 Decimal point position: 10-1, 10-2, 10-3, 10-4, 10-5 or none Scale divisions: 2 to 10 Engineering unit indication: Max. 8 characters Auto/Man indicator: Green/Amber LED Backup mode MV output setting indicator: Blue LED

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 3/13 http://www.m-system.co.jp/ MV output setting indicator: Blue LED FACTORY DEFAULT CAS PID G02 1 – 5 V DC P : 100% I : No integral action D : No derivative action Mv 1Pv 1Ai 1 1 – 5 V DC *1. Factory default setting Use Loop Configuration Builder Software (model: SFEW3E) to modify setting. H L AL2AL1 SEQ G81 4 – 20 mA DC ■ LOOP 1 ■ LOOP 2 Reverse Action (PV /MV ) *1*1 CAS PID G03 1 – 5 V DC P : 100% I : No integral action D : No derivative action Mv 2Pv 2Ai 2 1 – 5 V DC H L AL4AL3 SEQ G81 4 – 20 mA DC *1*1 Reverse Action (PV /MV ) EXTERNAL INTERFACE ■ NestBus Configuration: Bus type multi-drop Standard: Conforms to TIA/EIA-485-A Transfer rate: 19.2 kbps Protocol: NestBus (M-System’s own protocol) Max. transmission distance: 1 kilometer Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.) Terminating resistor: incorporated Card No. setting: 0 - F (16 cards; 2 assigned for one unit) ■ Modbus-RTU Configuration: Half-duplex, asynchronous, no procedure Standard: Conforms to TIA/EIA-485-A Max. transmission distance: 500 meters Transfer rate: 4800, 9600, 19.2 k, 38.4 k bps Data bit: 8 Parity bit: Odd, even, none Max. node number: 15 (except the master) Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.) Terminating resistor: incorporated Node address setting: 1 - 247 ■ Modbus/TCP (Ethernet) Physical layer standard: IEEE 802.3u Data link layer: 10BASE-T / 100BASE-TX Transfer rate: 10 / 100 Mbps, Auto Negotiation Protocol: Modbus/TCP Data: RTU (binary) Connections: 2 Transmission media: 10BASE-T (STP cable, category 5) 100BASE-TX (STP cable, category 5e) Max. segment length: 100 meters Port number: 502 IP address: 192.168.0.1 (factory setting) SUPPLY OUTPUT Output voltage:

24 V DC ±10 % with no load

18 V DC min. at 20 mA Current rating: ≤ 22 mA DC ∙Shortcircuit protection Current limited: Approx. 30 mA INPUT SPECIFICATIONS ■ Pv1, Pv2 (universal input) ∙Current input: 4 – 20 mA DC with input resistance 250 Ω (REM4) ∙Voltage input: -10 – +10 V DC -1 – +1 V DC 0 – 10 V DC 1 – 5 V DC 0 – 1 V DC Input resistance: ≥ 1 MΩ ∙Thermocouple input: K, E, J, T, B, R, S, C, N, U, L, P, PR (See Table 1) Input resistance: ≥ 30 kΩ Burnout sensing: ≤ 0.3 µA Burnout indication: 115 % of the measuring range (upscale) ∙RTD input: Pt100 (JIS ’97, IEC), Pt100 (JIS ’89), JPt100 (JIS ’89), Pt50Ω (JIS ’81), Ni100 (See Table 2) Maximum lead wire resistance: 100 Ω per wire Burnout indication: 115 % of the measuring range (upscale) Sensing current: ≤ 1 mA ∙Potentiometer input: Total resistance 100 Ω to 10 kΩ Minimum span: 50 % of total resistance Excitation: ≤ 0.6 V DC ■ Ai1, Ai2, Ai3, Ai4 ∙Voltage input: 1 – 5 V DC Input resistance: ≥ 1 MΩ ■ Pi1, Pi2, Pi3, Pi4, Pi5: Dry contact (Di1 through Di5 are assigned to the same terminals respectively.) Maximum frequency: 20 Hz Minimum pulse width: 25 msec.

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 4/13 http://www.m-system.co.jp/ Common: Negative common per 5 points Sensing: Approx. 12 V DC, 6 mA ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ ■ Pi6: Dry contact (Di6 is assigned to the same terminal.) Maximum frequency: 10 kHz Minimum pulse width: 0.05 msec. Common: Negative common Sensing: Approx. 12 V DC, 12 mA ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ Excitation: 12 V DC ±10%, 15 mA Current limiting circuit: Approx. 30 mA ■ Di1, Di2, Di3, Di4, Di5: Dry contact (Pi1 through Pi5 are assigned to the same terminals respectively.) Common: Negative common per 5 points Sensing: Approx. 12 V DC, 6 mA ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ ■ Di6: Dry contact (Pi6 is assigned to the same terminal.) Common: Negative common Sensing: Approx. 12 V DC, 12 mA ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ [Table 1 (Thermocouple input)] T/C USABLE RANGE (°C) CONFORMANCE RANGE (°C) K (CA) -272 to +1472 -150 to +1370 E (CRC) -272 to +1100 -170 to +1000 J (IC) -260 to +1300 -180 to +1200 T (CC) -272 to +500 -170 to +400 B (RH) 24 to 1920 1000 to 1760 R -100 to +1860 380 to 1760 S -100 to +1860 400 to 1760 C (WRe 5-26) -52 to +2416 100 to 2315 N -272 to +1400 -130 to +1300 U -252 to +700 -200 to +600 L -252 to +1000 -200 to +900 P (Platinel II ) -52 to +1496 0 to 1395 (PR) -52 to +1860 300 to 1760 Overrange input (out of the usable range) is handled as burnout. [Table 2 (RTD input)] RTD USABLE RANGE (°C) CONFORMANCE RANGE (°C) Pt 100 (JIS ’97 , IEC) -240 to +900 -200 to +850 Pt 100 (JIS ’89) -240 to +900 -200 to +660 JPt 100 (JIS ’89) -236 to +560 -200 to +510 Pt 50Ω (JIS ’81) -236 to +700 -200 to +649 Ni 100 -100 to +252 -80 to +250 Overrange input (out of the usable range) is handled as burnout. OUTPUT SPECIFICATIONS ■ Mv1, Mv2, Mv2B ∙Current output: 4 – 20 mA DC Load resistance: ≤ 600 Ω (Mv2B is the output from backup unit.) ■ Ao1, Ao2 ∙Voltage output: 1 – 5 V DC Load resistance: ≥ 10 kΩ ■ Discrete Output ∙Do1, Do2, Do3, Do4, Do5, RUN contact (Do6): Relay contact Rated load: 250 V AC @1 A (cos ø = 1)

30 V DC @1 A (resistive load)

Maximum switching voltage: 250 V AC or 30 V DC Maximum switching power: 250 VA or 60 W Minimum load: 5 V DC @10 mA Mechanical life: 2 × 107 cycles ∙Do1, Do2, Do3, Do4, Do5: Photo MOSFET relay Rating: 200 V AC/DC @0.5 A (resistive load) ON resistance: 2.1 Ω Maximum frequency: 4 Hz @24 V, 10 mA ON delay time: ≤ 5.0 msec. OFF delay time: ≤ 3.0 msec. INSTALLATION Power input ∙AC: Control module ≤ 25 VA at 100 V AC ≤ 40 VA at 240 V AC Backup module ≤ 10 VA at 100 V AC ≤ 15 VA at 240 V AC

  • DC Control module: ≤ 650 mA Backup module: ≤ 150 mA Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 5 to 90 %RH (non-condensing) Mounting: Panel flush mounting (high-density mounting in horizontal direction) Weight: Approx. 2.0 kg (4.41 lb) for 300 mm depth type Approx. 2.5 kg (5.51 lb) for 400 mm depth type PERFORMANCE Accuracy DC input: ±0.1 % ±1 digit Thermocouple input: ±1℃ ±1 digit ±2℃ ±1 digit for B, R, S, C and PR RTD input: ±1℃ ±1 digit Potentiometer input: ±0.2 % ±1 digit

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 5/13 http://www.m-system.co.jp/ DC output: ±0.1 % Precision resistor module (REM4): ±0.1 % Cold junction compensation: ±2°C at 25°C ±10°C ±4°C for S, R and PR Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) DC input: ±0.015 %/°C (±0.008 %/°F) Thermocouple input: ±0.015 %/°C (±0.008 %/°F) RTD input: ±0.015 %/°C (±0.008 %/°F) Potentiometer input: ±0.015 %/°C (±0.008 %/°F) DC output: ±0.015 %/°C (±0.008 %/°F) Precision resistor module (REM4): ±0.015 %/°C (±0.008 %/°F) Line voltage effect: ±0.1 % over voltage range Calendar clock accuracy: Monthly deviation 3 minutes at 25°C RAM memory duration in power failure for hot start: 10 minutes assured Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength:

1500 V AC @ 1 minute

(Pv1 or supply output to Pv2 or Ai1 or Ai2 or Ai3 or Ai4 to Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Mv2B or Ao1 or Ao2 to Do1 to Do2 or Do3 or Do4 or Do5 or Do6 to NestBus to Modbus-RTU to Modbus/TCP to power to backup module power to FG)

500 V AC @ 1 minute (Pv2 to Ai1 or Ai2 or Ai3 or Ai4)

500 V AC @ 1 minute (Mv2 or Mv2B to Ao1 or Ao2)

500 V AC @ 1 minute (Do2 to Do3 to Do4 to Do5 to Do6)

500 V AC @ 1 minute (Pv1 to supply output)

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 6/13 http://www.m-system.co.jp/ EXTERNAL VIEW ■ CONTROL MODULE FRONT VIEW ■ BACKUP MODULE 4 5 6 7

3 Auto/Man

1 . TFT Color LCD with touch panel Provides operation and engineering views to facilitate monitoring and setting 2. MV output setting indicator LEDs for the backup mode 3. Configurator jack and cap Connects with a PC where Loop Configuration Builder Software (model: SFEW3E) or PC configurator software (model: SCCFG) is installed via a PC configurator cable (model: COP-US) and enables programming and parameter setting 4. MV value (DOWN) button 5. Acceleration button (Accelerates MV signal’s changing speed by pressing simultaneously with MV value button) 6. MV value (UP) button 7 . Auto / Man selector (changes the control mode for MV output) 8. MV output setting indicators 9. MV value (UP) button 10. Acceleration button (Accelerates MV signal’s changing speed by pressing simultaneously with MV value button) 11 . MV value (DOWN) button

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 7/13 http://www.m-system.co.jp/ COMMUNICATION CABLE CONNECTIONS SMLSMLSC210W *1 *1 FG ■ Modbus-RTU ■ NestBus R2K-1 SC210WSC210W CONNECTOR RS-232-C RS-485 *1 *1 *1. Internal terminating resistor is used when the device is at the end of a transmission line. *2. For noise protection, connect all shielded cables with each other and ground them at a single dedicated ground point within the system with grounding resistance of 100 Ω or less. Note that the most suitable ground point differs depending on the system. Also note that there may be cases where less noise is caused when the shields are left ungrounded. FG *2FG RS-485 FG FG

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 8/13 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 60 61 62 63 144 (5.67) 164 (6.46) MOUNTING BRACKETS BACKUP MODULE POWER INPUT TERMINAL TERMINAL COVER 72 (2.83) 80 (3.15) (.94) 210 (8.27) max. 175 (6.89) *3. Option /3: 300 mm (11.81”) Option /4: 400 mm (15.75”) *1. Option /M2, /R only *2. For Modbus/TCP only Jack cap 137.5 (5.41) 7.2 (.28) RJ-45 CONNECTOR *2 52–M3.5 SCREW 4–M4 SCREW FOR FIXING TERMINAL

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 9/13 http://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm 138 68 [68+72×(n - 1)] +0.7 Panel thickness 2.3 – 20 138 ■ PANEL CUTOUT unit: mm

  • Single mounting • Clustered mounting n = number of units ■ Caution
  • IP55 is ensured for the front panel of the unit independently mounted to a panel. Securely seal the mounting surface along the panel cutout once the unit is installed.
  • Set the unit on a vertical surface with its operation buttons at the lower side. Mounting in other directions may cause heat built up inside the unit and shorten its life span or degrade its performance.
  • Ensure that there is sufficient space for ventilation inside the panel. Do not install above the devices that generate high heat such as heaters, transformers or resistors. Leave at least 30 mm (1.2 inch) space above, below and behind the unit for maintenance purpose (e.g. wiring, removing or installing).

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 10/13 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM *1. Close across the terminals 27 – 28 when the unit is located at the end of a transmission line (= no cross-wiring). *2. Close across the terminals 14 – 15 when the unit is located at the end of a transmission line (= no cross-wiring). *3. Backup is applicable to Mv 2 only. Mv 2B is output of the backup module. *4. Connect input resistor module (model: REM4) for current input. *5. Connect CJC sensor for thermocouple input. *6. Connect input resistor module (model: REM4). ■ UNIVERSAL INPUT CONNECTION E.G. RTD A B A B C A B C A B C A B C T/C CJC SENSOR C POTENTIOMETER *5 *6 R A B C A B C R 2-Wire XMTR VOLT / CURRENT INPUT ■ DISCRETE INPUT PULSE INPUT CONNECTION E.G.: Dry contact A B B max. min. +12V 1 or 2kΩ Sensor Excitation Input Circuit A/D Converter A/D Converter A/D Converter Discrete Input Circuit Display / Setting Output Driver Isolation Isolation Isolation Isolation Isolation Digital Computation IsolationControl Module Backup Module Isolation 42 A1 Di 1 / Pi 1 Di 2 / Pi 2 Di 4 / Pi 4 Di 3 / Pi 3 Di 5 / Pi 5 Di 6 / Pi 6 Pv 1 UNIVERSAL INPUT Pv 2 UNIVERSAL INPUT Ai 1 Ai 2 Ai 3 Ai 4 SENSOR EXC INPUT COM Digital Computation Output Switch Backup Module Power Circuit OPERATION BUTTONS ■ BACKUP MODULE POWER SUPPLY: SINGLE SUPPLY MV SETTING INDICATORS Isolation Excitation Supply PC CONFIGURATOR/ BUILDER SOFTWARE Jack 2-WIRE TRANSMITTER Output Driver Output Driver Isolation Output Driver Isolation Output Driver Isolation 3 + 4 – U(+) V(–) Do 1 Do 2 Do 3 Do 4 Do 5 POWER Ao 2 Ao 1 Mv 1 Do 6 RUN CONTACT Modbus/TCPRJ-45 CONNECTOR Isolation Isolation Mv 2, Mv 2B *3 Jumper*1 Shielded Twisted-pair Cable To Other NestBus Devices SHLD Jumper*2 Shielded Twisted-pair Cable To Other Modbus-RTU Devices SHLD FG

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 11/13 http://www.m-system.co.jp/ Sensor Excitation Input Circuit A/D Converter A/D Converter A/D Converter Discrete Input Circuit Display / Setting Output Driver Isolation Isolation Isolation Isolation Isolation Digital Computation IsolationControl Module Backup Module 42 A1 Di 1 / Pi 1 Di 2 / Pi 2 Di 4 / Pi 4 Di 3 / Pi 3 Di 5 / Pi 5 Di 6 / Pi 6 Pv 1 UNIVERSAL INPUT Pv 2 UNIVERSAL INPUT Ai 1 Ai 2 Ai 3 Ai 4 SENSOR EXC INPUT COM Digital Computation Output Switch Backup Module Power Circuit OPERATION BUTTONS ■ BACKUP MODULE POWER SUPPLY: DUAL SUPPLY MV SETTING INDICATORS Isolation *1. Close across the terminals 27 – 28 when the unit is located at the end of a transmission line (= no cross-wiring). *2. Close across the terminals 14 – 15 when the unit is located at the end of a transmission line (= no cross-wiring). *3. Backup is applicable to Mv 2 only. Mv 2B is output of the backup module. U(+) V(–) FG *4. Connect input resistor module (model: REM4) for current input. *5. Connect CJC sensor for thermocouple input. *6. Connect input resistor module (model: REM4). ■ UNIVERSAL INPUT CONNECTION E.G. RTD A B A B C A B C A B C A B C T/C CJC SENSOR C POTENTIOMETER *5 *6 R A B C A B C R 2-Wire XMTR VOLT / CURRENT INPUT ■ DISCRETE INPUT PULSE INPUT CONNECTION E.G.: Dry contact A B B max. min. Excitation Supply Isolation PC CONFIGURATOR/ BUILDER SOFTWARE Jack 2-WIRE TRANSMITTER BACK UP POWER +12V 1 or 2kΩ Output Driver Output Driver Isolation Output Driver Isolation Output Driver Isolation 3 + 4 – U(+) V(–) Do 1 Do 2 Do 3 Do 4 Do 5 POWER Ao 2 Ao 1 Mv 1 Do 6 RUN CONTACT Modbus/TCPRJ-45 CONNECTOR Isolation Isolation Mv 2, Mv 2B *3 Jumper*1 Shielded Twisted-pair Cable To Other NestBus Devices SHLD Jumper*2 Shielded Twisted-pair Cable To Other Modbus-RTU Devices SHLD FG

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 12/13 http://www.m-system.co.jp/ SYSTEM CONFIGURATION EXAMPLES MV PV NestBus RUN PWR Modbus-RTU Modbus/TCP MV PV MV PV MV PV MV PV ■ SINGLE LOOP CONTROL ■ I/O EXPANDED VIA NESTBUS ■ CONTROL / SUPERVISION VIA MODBUS/TCP ■ CASCADE CONTROL Flow Level MV MV PV PV Ai Multi-Function PID Controller Model: SC210W Multi-Function PID Controller Model: SC210W Multi-Function PID Controller Model: SC210W Multi-Function PID Controller Model: SC210 Multi-Function PID Controller Model: SC210 Remote I/O Module Model: SML Ethernet Communication Adaptor Model: GR8-EM SCADA System Multi-Function PID Controller Model: SC210W Multi-Function PID Controller Model: SC210W

MODEL: SC210W SC210W SPECIFICATIONS ES-6347 Rev.0 Page 13/13 http://www.m-system.co.jp/ Modbus-RTU RS-485/RS-232-C Converter Model: R2K-1 1234 56 7 890 MV PV MV PV ■ CONTROL / SUPERVISION VIA MODUBS-RTU Multi-Function PID Controller Model: SC210 Multi-Function PID Controller Model: SC210W SCADA System Specifications are subject to change without notice.