Switches & Pilot LightsSignaling LightsRelays & SocketsTimersContactorsTerminal BlocksCircuit Breakers RTE Timers 944 www.IDEC.com 1705151136 Timers RTE Series — Analog Timers Key features:

  • 20 time ranges and 10 timing functions
  • Time delays up to 600 hours
  • Space-saving package
  • High repeat accuracy of ± 0.2%
  • ON and timing OUT LED indicators
  • Standard 8- or 11-pin and 11-blade termination
  • 2 form C delayed output contacts
  • 10A Contact Rating Cert. No. E9950913332316 (EMC, RTE) Cert. No. BL960813332355 (LVD, RTE) UL Listed File No. E66043 General Specifications Contact Ratings Operation System Solid state CMOS Circuit Contact Configuration 2 Form C, DPDT (Delay output) Allowable Voltage / Allowable Current 240V AC, 30V DC / 10A Maximum Permissible Operating Frequency 1800 cycles per hour Rated Load Resistive 10A 240V AC, 30V DC Inductive 7A 240V AC, 30V DC Horse Power Rating 1/6 HP 120V AC, 1/3 HP 240V AC Life Electrical 500,000 op. minimum (Resistive) Mechanical 50,000,000 op. minimum Operation Type Multi-Mode Time Range 0.1sec to 600 hours Pollution Degree 2 (IE60664-1) Over voltage category III (IE60664-1) Rated Operational Voltage AF20 100-240V AC(50/60Hz) AD24 24V AC(50/60Hz)/24V DC D12 12V DC Voltage Tolerance AF20 85-264V AC(50/60Hz) AD24 20.4-26.4V AC(50/60Hz)/21.6-26.4V DC D12 10.8-13.2V DC Input off Voltage Rated Voltage x10% minimum Ambient Operating Temperature -20 to +65ºC (without freezing) Ambient Storage and Transport Temperature -30 to +75ºC (without freezing) Relative Humidity 35 to 85%RH (without condensation) Atmospheric Pressure 80kPa to 110kPa (Operating), 70kPa to 110kPa (Transport) Reset Time 100msec maximum Repeat Error ±0.2%, ±20msec* Voltage Error ±0.2%, ±20msec* Temperature Error ±0.5%, ±20msec* Setting Error ±10% maximum Insulation Resistance 100MΩ minimum (500V DC) Dielectric Strength Between power and output terminals: 2000V AC, 1 minute Between contacts of different poles: 2000V AC, 1 minute Between contacts of the same pole:1000V AC, 1 minute Vibration Resistance 10 to 55Hz amplitude 0.5mm2 hours in each of 3 axes Shock Resistance Operating extremes: 98m/sec2 (10G) Damage limits: 490m/sec2 (50G) 3 times in each of 3 axes Degree of Protection IP40 (enclosure) (IEC60529) Power Consumption (Approx.) TYPE RTE-P1, -B1 RTE-P2, -B2 *For the value of the error against a preset time, whichever the largest, applies. AF20 120V AC/60Hz 6.5VA 6.6VA 240V AC/60Hz 11.6VA 11.6VA 24V AC 60Hz/DC 3.4VA/1.7W 3.5VA/1.7W D12 1.6W 1.6W Mounting Position Free Dimensions RTE-P1, P2 40Hx 36W x 77.9D mm RTE-B1, B2 40Hx 36W x 74.9D mm Weight (Approx.) RTE-P1 RTE-P2 RTE-B1, -B2 87g 89g 85g

Switches & Pilot LightsSignaling LightsRelays & SocketsTimersContactorsTerminal BlocksCircuit Breakers 945 800-262-IDEC (4332) • USA & Canada RTE Timers 1705151136 Part Numbering Guide RTE series part numbers are composed of 4 part number codes. When ordering a RTE series part, select one code from each category. Example: RTE-P1AF20 RTE — P 1 AF20 j Series k Terminal Style l Function Group m Input Voltage Part Numbers: RTE Series Description Part Number Code Remarks j Series RTE series RTE For internal circuits, see next page. k Terminal Style Pin P Select one only. Blade B l Function Group ON-delay, interval, cycle OFF, cycle ON 1 Each function group has different timing functions. ON-delay, cycle OFF, cycle ON, signal ON/ OFF delay, OFF-delay, one-shot 2 See page 940. m Input Voltage 100 to 240V AC(50/60Hz) AF20 24V AC(50/60Hz)/24V DC AD24 12V DC D12 Part Numbers Voltage Power Triggered Start Input Triggered 8-Pin Blade 11-Pin Blade 12V DC RTE-P1D12 RTE-B1D12 RTE-P2D12 RTE-B2D12 24V AC/DC RTE-P1AD24 RTE-B1AD24 RTE-P2AD24 RTE-B2AD24 100-240V AC RTE-P1AF20 RTE-B1AF20 RTE-P2AF20 RTE-B2AF20 Time Range Determined by Time Range Selector and Dial Selector Dial 0 - 1 0 - 3 0 - 10 0 - 30 0 - 60 Range Minute 1.2 sec - 1 min 3.6 sec - 3 min 12 sec - 10 min 36 sec - 30 min 1.2 min - 60 min Hour 1.2 min - 1 hr 3.6 min - 3 hr 12 min - 10 hr 36 min - 30 hr 1.2 hr - 60 hr

10 Hours 12 min - 10 hr 36 min - 30 hr 2 hr - 100 hr 6 hr - 300 hr 12 hr - 600 hr

Switches & Pilot LightsSignaling LightsRelays & SocketsTimersContactorsTerminal BlocksCircuit Breakers RTE Timers 946 www.IDEC.com 1705151136 Timing Diagrams RTE-P1, -B1 RTE-P2 5 6 7 (~/-)(~/+) start RTE-B2 2 3 A B (~/-)(~/+) 4 5 6 7 8 2 3 A B (~/-)(~/+) 4 5 6 7 8 RTE-B1 4 5 (~/-)(~/+) RTE-P1 start external control signal external control signal RTE-P2 5 6 7 (~/-)(~/+) start RTE-B2 2 3 A B (~/-)(~/+) 4 5 6 7 8 2 3 A B (~/-)(~/+) 4 5 6 7 8 RTE-B1 4 5 (~/-)(~/+) RTE-P1 start external control signal external control signal 1. RTE-B1: Do not apply voltage to terminals #2, #5 & #8. 2. IDEC sockets are as follows: RTE-P1: SR2P-06* pin type socket, RTE-B1: SR3B-05* blade type socket, (*-may be followed by suffix letter A,B,C or U). A: ON-Delay 1 (power start) Set timer for desired delay, apply power to coil. Contacts transfer after preset time has elapsed, and remain in transferred position until timer is reset. Reset occurs with removal of power. Item Terminal Number Operation Power (1) 2 - 7 (2) A - B Delayed Contact (1) 1 - 4, 5 - 8 (1) 1 - 3, 6 - 8 Indicator PWR OUT Set Time T C: Cycle 1 (power start, OFF first) Set timer for desired delay, apply power to coil. First transfer of contacts occurs after preset delay has elapsed, after the next elapse of preset delay contacts return to original position. The timer now cycles between on and off as long as power is applied (duty ratio 1:1). Item Terminal Number Operation Power (1) 2 - 7 (2) A - B Delayed Contact (1) 1 - 4, 5 - 8 (1) 1 - 3, 6 - 8 Indicator PWR OUT Set Time T T B: Interval (power start) Set timer for desired delay, apply power to coil. Contacts transfer immediately, and return to original position after preset time has elapsed. Reset occurs with removal of power. Item Terminal Number Operation Power (1) 2 - 7 (2) A - B Delayed Contact (1) 1 - 4, 5 - 8 (1) 1 - 3, 6 - 8 Indicator PWR OUT Set Time T D: Cycle 3 (power start, ON first) Functions in same manner as Mode C, with the exception that first transfer of contacts occurs as soon as power is applies. The ratio is 1:1. Time On = Time Off Item Terminal Number Operation Power (1) 2 - 7 (2) A - B Delayed Contact (1) 1 - 4, 5 - 8 (1) 1 - 3, 6 - 8 Indicator PWR OUT Set Time T T

Switches & Pilot LightsSignaling LightsRelays & SocketsTimersContactorsTerminal BlocksCircuit Breakers 947 800-262-IDEC (4332) • USA & Canada RTE Timers 1705151136 Timing Diagrams con’t RTE-P2, -B2 RTE-P2 5 6 7 (~/-)(~/+) start RTE-B2 2 3 A B (~/-)(~/+) 4 5 6 7 8 2 3 A B (~/-)(~/+) 4 5 6 7 8 RTE-B1 4 5 (~/-)(~/+) RTE-P1 start external control signal external control signal RTE-P2 5 6 7 (~/-)(~/+) start RTE-B2 2 3 A B (~/-)(~/+) 4 5 6 7 8 2 3 A B (~/-)(~/+) 4 5 6 7 8 RTE-B1 4 5 (~/-)(~/+) RTE-P1 start external control signal external control signal 1. RTE-P2: Do not apply voltage to terminals #5, #6 & #7. 2. RTE-B2: Do not apply voltage to terminals #2, #5 & #8. 3. IDEC sockets are as follows: RTE-P2: SR3P-05* pin type socket, RTE-B2: SR3B-05* blade type socket, (*-may be followed by suffix letter A,B,C or U). A: ON-Delay 2 (signal start) When a preset time has elapsed after the start input turned on while power is on, the NO output contact goes on. Item Terminal Number Operation Power (A) 2 - 10 (B) A - B Start (A) 5 - 6 (B) 2 - 5 Delayed Contact (A) 1 - 4, 8 - 11 (A) 1 - 3, 9 - 11 Indicator PWR OUT Set Time T C: Cycle 4 (signal start, ON first) When the start input turns on while power is on, the NO contact goes on. The output oscillates at a preset cycle (duty ratio 1:1). Item Terminal Number Operation Power (A) 2 - 10 (B) A - B Start (A) 5 - 6 (B) 2 - 5 Delayed Contact (A) 1 - 4, 8 - 11 (A) 1 - 3, 9 - 11 Indicator PWR OUT Set Time T T T T T T T T Ta E: Signal OFF-Delay When power is turned on while the start input is on, the NO output contact goes on. When a preset time has elapsed after the start input turned off, the NO output contact goes off. Item Terminal Number Operation Power (A) 2 - 10 (B) A - B Start (A) 5 - 6 (B) 2 - 5 Delayed Contact (A) 1 - 4, 8 - 11 (A) 1 - 3, 9 - 11 Indicator PWR OUT Set Time T Ta T Ta B: Cycle 2 (signal start, OFF first) When the start input turns on while power is on, the output oscillates at a preset cycle (duty ratio 1:1), starting while the NO contact off. Item Terminal Number Operation Power (A) 2 - 10 (B) A - B Start (A) 5 - 6 (B) 2 - 5 Delayed Contact (A) 1 - 4, 8 - 11 (A) 1 - 3, 9 - 11 Indicator PWR OUT Set Time T T T T T T T T T Ta D: Signal ON/OFF-Delay When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed while the start input remains on, the output contact goes off. When the start input turns off, the NO contact goes on again. When a preset time has elapsed after the start input turned off, the NO contact goes off. Item Terminal Number Operation Power (A) 2 - 10 (B) A - B Start (A) 5 - 6 (B) 2 - 5 Delayed Contact (A) 1 - 4, 8 - 11 (A) 1 - 3, 9 - 11 Indicator PWR OUT Set Time T T Ta T T Ta F: One-Shot (signal start) When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed, the NO output contact goes off. Item Terminal Number Operation Power (A) 2 - 10 (B) A - B Start (A) 5 - 6 (B) 2 - 5 Delayed Contact (A) 1 - 4, 8 - 11 (A) 1 - 3, 9 - 11 Indicator PWR OUT Set Time

Switches & Pilot LightsSignaling LightsRelays & SocketsTimersContactorsTerminal BlocksCircuit Breakers RTE Timers 948 www.IDEC.com 1705151136 T emperature Derating Curves Mounting A 50ºC 65ºC 10A Ambient Temperature Allowable CurrentMounting A Derating Curve Mounting B 50ºC 65ºC Ambient Temperature Allowable Current Mounting B Derating Curve Instructions Installation of Hold-Down Springs DIN Rail Mount Socket Socket SR2P-06 Hold-down Spring (sold separately) SFA-202 (use two springs) Insert the springs into the outer slots with the projections facing inside. Socket SR2P-05 Insert the springs into the slots. Hold-down Spring (sold separately) SFA-203 (use two springs) Switch Settings jOperator Mode Selector kScale Selector lTime Range Selector j k l 1. Turn the selectors securely using a flat screw- driver 4mm wide (maximum). Note that incorrect setting may cause malfunc- tion. Do not turn the selectors beyond their limits. 2. Since changing the setting during timer operation may cause malfunction, turn power off before changing. Safety Precautions Special expertise is required to use Electronic Timers.

  • All Electronic Timers are manufactured under IDEC’s rigorous quality control system, but users must add a backup or fail safe provision to the control system when using the Electronic Timer in applications where heavy damage or personal injury may occur should the Electronic Timer fail.
  • Install the Electronic Timer according to instructions described in this catalog.
  • Make sure that the operating conditions are as described in the specifica- tions. If you are uncertain about the specifications, contact IDEC in advance.
  • In these directions, safety precautions are categorized in order of importance under Warning and Caution. Warnings Warning notices are used to emphasize that improper operation may cause severe personal injury or death.
  • Turn power off to the Electronic timer before starting installation, removal, wiring, maintenance, and inspection on the Electronic Timer.
  • Failure to turn power off may cause electrical shocks or fire hazard.
  • Do not use the Electronic Timer for an emergency stop circuit or inter- locking circuit. If the Electronic Timer should fail, a machine malfunction, breakdown, or accident may occur. Caution Caution notices are used where inattention might cause personal injury or dam- age to equipment.
  • The Electronic Timer is designed for installation in equipment. Do not install the Electronic Timer outside equipment.
  • Install the Electronic Timer in environments described in the specifications. If the Electronic Timer is used in places where it will be subjected to high-tem- perature, high-humidity, condensation, corrosive gases, excessive vibrations, or excessive shocks, then electrical shocks, fire hazard, or malfunction could result.
  • Use an IEC60127-approved fuse and circuit breaker on the power and output line outside the Electronic Timer.
  • Do not disassemble, repair, or modify the Electronic Timer.
  • When disposing of the Electronic Timer, do so as industrial waste.

Switches & Pilot LightsSignaling LightsRelays & SocketsTimersContactorsTerminal BlocksCircuit Breakers 949 800-262-IDEC (4332) • USA & Canada RTE Timers 1705151136 Accessories DIN Rail Mounting Accessories DIN Rail/Surface Mount Sockets and Hold-Down Springs DIN Rail Mount Socket Applicable Hold-Down Springs Style Appearance Use with Timers Part Number Appearance Part Number 11-Pin Screw Terminal (dual tier) RTE-P2 SR3P-05 SFA-203 11-Pin FingerSafe Socket SR3P-05C 8-Pin Screw Terminal RTE-P1 SR2P-06 SFA-2028-Pin Fingersafe Socket SR2P-05C 11-Blade Screw Terminal RTE-B1 RTE-B2 SR3B-05 DIN Mounting Rail Length 1000mm — BNDN1000 Panel Mounting Accessories Flush Panel Mount Adapter and Sockets that use an Adapter Accessory Description Appearance Use with Part No. Panel Mount Adapter Adaptor for flush panel mounting RTE timers All RTE timers RTB-G01 Sockets for use with Panel Mount Adapter 8-pin screw terminal (Shown: SR6P-M08G Wiring Socket Adapter) RTE-P1 SR6P-M08G 11-pin screw terminal RTE-P2 SR6P-M11G 8-pin solder terminal RTE-P1 SR6P-S08 11-pin solder terminal RTE-P2 SR6P-S11

Switches & Pilot LightsSignaling LightsRelays & SocketsTimersContactorsTerminal BlocksCircuit Breakers RTE Timers 950 www.IDEC.com 1705151136 Dimensions 36.0 77.9 40.0 13.0 7.3 13.7 RTE-P1 (8 pin) Terminal Style RTE-P2 (11 pin)Terminal Style RTE-B1/RTE-B2 (11 blade) Terminal Style Panel Mount Adapter RTE Timer, 8-Pin and 11-Pin with SR6P-S08 or SR6P-S11 Back Wiring Socket 1.7 11 61.2 Panel Thickness 0.8 to 5mm 42.5 98 maximum RTE Timer, 8-Pin with SR6P-M08G ø3.6 min. 8-M3.5 Terminal Screw 2187 34 56 6.9 max. 30.4 44.6 Panel Thickness 0.8 to 5mm 80.5 9.8 x 3 44.6 3.5 max.5 .6 min. RTE Timer, 11-Pin with SR6P-M11G ø3.6 min. 11-M3.5 Teminal Screws 6.9 max. 4 389 10 2 11 17 6 3.5 max. 5.8 min. 30.5 7 8.5 x 4 16.7