Applicable Standards Mark File No. or Organization UL508 UL13101 ANSI/ISA 12.12.01 CSA C22.2 No.107.1 CSA C22.2 No.213 CSA C22.2 No.223 UL/c-UL Listed File No. E467154, E177168 EN60950-1 EN50178 EN61204-3 EN50581 TÜV SÜD 2 EU Low Voltage Directive EMC Directive RoHS Directive SEMI F47 — EPRI Note 1: PS5R-VB/VC/VD/VE only Note 2: EN60950-1, EN50178 only POWER SUPPLY PART NUMBERS Output Capacity Part Number Input Voltage Output Voltage Output Current 10W PS5R-VB05 100 to 240V AC (Voltage range: 85 to 264V AC / 100 to 370V DC) 5V 2.0A 15W PS5R-VB12 12V 1.3A PS5R-VB24 24V 0.65A 30W PS5R-VC12 12V 2.5A PS5R-VC24 24V 1.3A 60W PS5R-VD24 24V 2.5A 90W PS5R-VE24 24V 3.75A 120W PS5R-VF24 24V 5.0A 240W PS5R-VG24 24V 10.0A Note 3: PS5R-VB only Note 4: PS5R-VB/VC only Use only for interpreting part numbers. Do not use for developing part numbers. Part Number Structure PS5R - V Output Voltage 05: 5V 3 12: 12V 4 24: 24V Output Capacity B: 10W/15W C: 30W D: 60W E: 90W F: 120W G: 240W PRODUCT DESCRIPTION DIN-rail mount switching power supplies with global approvals for both industrial and hazardous locations KEY FEATURES
- Compact size preserves panel space
- Slim size (width): 22.5mm (10W/15W/30W) 36mm (60W/90W) 46mm (120W) 60mm (240W)
- Universal Voltage Input: 85-264V AC/100-370V DC
- Wide operating temperature range
- Spring-up terminals accept ring & fork terminals
- Approved for use in Class I Division 2 hazardous locations
- Can be installed in 6 directions
- 10W ~ 90W meet NEC Class 2 output ratings
- Overcurrent protection with auto-reset
- Meets SEMI F47 Sag Immunity (208V AC input)
- RoHS compliant
- Five-year factory warranty
5V DC output PS5R-VB05 - - - 12V DC output PS5R-VB12 PS5R-VC12 - - 24V DC output PS5R-VB24 PS5R-VC24 PS5R-VD24 PS5R-VE24 PS5R-VF24 PS5R-VG24 Output Capacity 15W (5V Model is 10W) 30W 60W 90W 120W 240W Input Rated Input Voltage (Single-phase two-wire) 1 100 to 240V AC (Voltage range: 85 to 264V AC/100 to 370V DC) (Load ≤ 80% at 100-105V DC) Frequency 50/60 Hz Input Current (Typ.) 100V AC 5V: 0.25A 230V AC 5V: 0.14A Inrush Current (Typ.) (Ta=25°C, cold start) 100V AC 18A 14A 230V AC 45A 41A 30A Leakage Current 120V AC 0.5mA max. 230V AC 1.0mA max. Efficiency (Typ.) (at rated output) 2 100V AC 5V: 77%, 12V: 82%, 24V: 84% 12V: 83%, 24V: 85% 86% 88% 89% 89% 230V AC 5V: 73%, 12V: 80%, 24V: 81% 12V: 85%, 24V: 87% 86% 90% Power Factor (Typ.) 100V AC — — — 0.99 230V AC — — — 0.86 0.92 0.96 Output Adjustable Voltage Range ±10% ±5% ±10% Output Holding Time (Typ.) (at rated output) 100V AC 5V: 53ms, 12V: 34ms, 24V: 36ms 12V: 13ms, 24V: 15ms 13ms 20ms 30ms 230V AC 5V: 330ms 12V: 215ms 24V: 230ms 12V: 110ms 24V: 110ms 105ms 30ms 33ms 40ms Rise Time (at rated input and output) 5V, 12V: 200ms max. 24V: 250ms max. 200ms max. Regulation Input Fluctuation 0.4% max. Load Fluctuation 5V: 2.5% max. 12V, 24V: 1.0% max. 1.0% max. Temperature Change 0.05%/oC max. (-10 to +65°C ) 12V: 0.05%/°C max. (-10 to +50°C) 0.05%/°C max. (-10 to +55°C ) 0.05%/°C max. (-10 to +50°C ) 0.05%/°C max. (-25 to +55°C ) 0.05%/°C max. (-25 to +50°C) Ripple (including noise) 5V: 8% p-p max. (-25 to -10°C) 12V: 6% p-p max. (-25 to -10°C) 24V: 4% p-p max. (-25 to -10°C) 12V: 6% p-p max. (-25 to -10°C) 24V: 4% p-p max. (-25 to -10°C) 4% p-p max. (-25 to -10°C) 5V: 5% p-p max. (-10 to +0°C) 12V: 2.5% p-p max. (-10 to +0°C) 24V: 1.5% p-p max. (-10 to +0°C) 12V: 2.5% p-p max. (-10 to +0°C) 24V: 1.5% p-p max. (-10 to +0°C) 1.5% p-p max. (-10 to +0°C) 5V: 2.5% p-p max. (0 to +65°C) 12V: 1.5% p-p max. (0 to +65°C) 24V: 1% p-p max. (0 to +65°C) 12V: 1.5% p-p max. (0 to +50°C) 24V: 1% p-p max. (0 to +55°C) 1% p-p max. (0 to +55°C) 1% p-p max. (0 to +50°C) 1% p-p max. (0 to +55°C) 1% p-p max. (0 to +50°C) Overcurrent Protection 105% min. (auto reset) 101% min. (auto reset) 105% min. (auto reset) Operation Indicator LED (green) Dielectric Strength Between input and output terminals 3,000V AC, 1 minute Between input and ground terminals 2,000V AC, 1 minute Between output and ground terminals 500V AC, 1 minute Insulation Resistance Between input and output terminals: 100MΩ min. (500V DC megger) Between input and ground terminals: 100MΩ min. (500V DC megger) Operating Temperature 4 (No freezing) -25 to +75°C -25 to +70°C -25 to +65°C Operating Humidity 20 to 90% RH (no condensation) Storage Temperature (No freezing) -25 to +75°C Storage Humidity 20 to 90% RH (no condensation) Vibration Resistance 10 to 55Hz, amplitude 0.375mm, 2 hours each in 3 axes (when used with BNL6 end clips) 10 to 55Hz, amplitude 0.33mm, 2 hours each in 3 axes (when used with BNL6 end clips) 10 to 55Hz, amplitude 0.375mm, 2 hours each in 3 axes (when used with BNL8 end clips) 10 to 55Hz, amplitude 0.21mm, 2 hours each in 3 axes (when used with BNL6 end clips) 10 to 55Hz, amplitude 0.375mm, 2 hours each in 3 axes (when used with BNL8 end clips) 10 to 55 Hz, amplitude 0.375mm, 2 hours each in 3 axes (when used with part no. BNL6 mounting clips) Shock Resistance 300 m/s 2 (30G), 3 times each in 6 directions Expected Life 5 8 years minimum (at the rated input, 50% load, operating temperature +40°C, standard mounting direction) EMC EMI EN61204-3 (Class B) EMS EN61204-3 (industrial) Safety Standards UL508 (Listing), UL1310 Class 2 , ANSI/ISA-12.12.01 CSA C22.2 No. 107.1, 213, 223 EN60950-1, EN50178 UL508 (Listing) ANSI/ISA-12.12.01 CSA C22.2 No. 107.1, 213 EN60950-1, EN50178 Other Standard SEMI F47 (at 208V AC input only) Degree of Protection IP20 (EN60529) Dimensions (mm) 90H × 22.5W × 95D 95H × 36W × 108D 115H × 46W × 121D 125H × 60W × 125D Weight (approx.) 140g 150g 260g 310g 470g 960g Terminal Screw M3.5 At normal temperature and humidity unless otherwise specified. Note 1: DC input voltage is not subject to safety standards. When using on DC input, connect a fuse to the input terminal for DC input protection. Note 2: Under stable state. Note 4: See the output derating curves on page 3. Note 5: Calculation of the expected life is based on the actual life of the aluminum electrolytic capacitor. The expected life depends on operating conditions.
Operating Temperature vs. Output Current (Derating Curves) Conditions: Natural air cooling (Operating temperature is the temperature around the switching power supply.) PS5R-VB05, -VB12, -VB24 PS5R-VC12 PS5R-VC24 Mounting A Mounting B, C, D, E, F -30 -20 -10 0 10 20 30 40 50 60 70 80 100 Input Voltage: 85-100V AC Output Current (%) Operating Temperature (˚C) -30 -20 -10 0 10 20 30 40 50 60 70 80 100 Mounting A Mounting B, C, D, E, F Input Voltage: 85-100V AC Operating Temperature (˚C) Output Current (%) Mounting A, B Mounting C Mounting D, E, F Input Voltage: 85-100V AC -30 -20 -10 0 10 20 30 40 50 60 70 80 100 Operating Temperature (˚C) Output Current (%) PS5R-VD24 PS5R-VE24 PS5R-VF24 Mounting E Input Voltage: 85-100V AC Mounting F -30 -20 -10 0 10 20 30 40 50 60 70 80 100 Mounting B, C, D Mounting A Operating Temperature (˚C) Output Current (%) Mounting E Mounting B, C, D, F Mounting A Operating Temperature (˚C) Output Current (%) -30 -20 -10 10 20 30 40 50 60 70 80 100 Mounting F Mounting C, E -30 -20 -10 0 10 20 30 40 50 60 70 80 100 Mounting B, D Mounting A Operating Temperature (˚C) Output Current (%) PS5R-VG24 Mounting E Mounting B Mounting C, D, F Mounting A Operating Temperature (˚C) Output Current (%) -30 -20 -10 0 10 20 30 40 50 60 70 80 100 Input Voltage vs. Output Current (Derating Curves) PS5R-VB05, -VB12, VB24, -VC12, -VC24, -VD24, -VE24, -VF24 PS5R-VG24 85 100 264 100 (ACV) (DCV) 140 370 100 Input Voltage (V) Output Current (%) Output Current (%) Input voltage (V) 85 264 100 DC AC (ACV) 100 (DCV) 105100 370 Overcurrent Protection Characteristics PS5R-VB/VC/VD/VF PS5R-VE24 PS5R-VG24 -30 0 100 105 and over 100 Output Current (%) Output Voltage (%) Intermittent Operation 1 0 0 9 5 100 101 and over Output Current (%) Output Voltage (%)Intermittent Operation 1 0 0 9 5 100 105 and overOutput Current (%) Output Voltage (%)Intermittent Operation (Ta=25ºC)
Operating Temperature Approved by Safety Standards Part Number Mounting A Mounting B Mounting C Mounting D Mounting E Mounting F PS5R-VB05, -VB12, -VB24 65 60 60 60 60 60 PS5R-VC12 50 45 45 45 45 45 PS5R-VC24 55 55 50 45 45 45 PS5R-VD24 55 40 40 40 45 35 PS5R-VE24 50 40 40 40 45 40 PS5R-VF24 55 40 45 40 45 35 PS5R-VG24 50 35 30 30 45 30 MOUNTING STYLE Mounting A (Vertical, standard) Mounting B (Upright) Mounting C (Right side up) Mounting D (Left side up) Mounting E (Upside down) Mounting F (Downward) Up FRONT PANEL PS5R-VB/VC PS5R-VD/VE/VF PS5R-VG Marking Name Description L, N AC Input Terminal Voltage range: 85 to 264V AC/100 to 370V DC Ground Terminal Be sure to connect this terminal to a proper ground. +V, -V DC Output Terminals +V: Positive output terminal -V: Negative output terminal VR.ADJ Output Voltage Adjustment Allows adjustment within ±10%. (VE = ±5%) Turning clockwise increases the output voltage. Turning counterclockwise decreases the output voltage. DC ON Operation Indicator (green) Illuminates when the output voltage is on. 100 -240 VAC INP UT VR. ADJ ON O UTP UT L INPUT 50/60Hz VR. ADJ DC ON N OUTPUT ACCESSORIES Panel Mounting Bracket2 Applicable Switching Power Supply Part Number Remarks PS5R-VB PS5R-VC PS9Z-5R1B — PS9Z-5R2B For side mounting PS5R-VD PS5R-VE PS9Z-5R1C — PS5R-VF PS9Z-5R1E — PS5R-VG PS9Z-6R1F — PS9Z-6R2F For side mounting Note 2: Used when installing on a panel directly. DIN Rail (35mm-wide) Length Part Number Material 1000mm BNDN1000 Aluminum End Clip Part Number BNL6 BNL8
DIMENSIONS ( mm) Tolerance: ±1mm PS5R-VB/VC PS5R-VD/VE 3.8 4.4 35.3 27.3 61.6 12.2 8.2 9.5 22.5 Screw Terminal 5-M3.5 79 8 10 10 108 3.8 4.5 24.935.3 5-M3.5 Screw Terminal PS5R-VF PS5R-VG 115 98 8.5 11.5 11.5 4.5 44.935.3 3.8 121 5-M3.5 Screw Terminal 35 .3 44 .9 10 6 .5 6 0 9.5 9.5 9.5 9.5 9.5 9.5 9 .3 5.5 12 54 .5 1 25 3 .8 8-M3.5 Screw Terminal Panel Mounting Bracket When installed on switching power supply Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout for side mounting Side View Side View Front View Front View Front View Side View Front View Side View Front View Side View Side View Back View Mounting Screws (4 -M3×6 countersunk screws) 13.616.4 96.7 5.528.8 10.010.0 112102 105 10.29.9 109.8 24.7 112 120 102.0 110 62.9 105 115 125 135 125 10.29.9 122.8 135 145 135 10.5 10.5 145 130.6 138.6 148.6 138.6 62.3 29.5 11.8 11.8 PS9Z-5R1B PS9Z-5R1C PS9Z-5R1E PS9Z-6R1F PS9Z-6R2F Side-mount PS9Z-5R2B Side-mount 2-M4 or 2- ø 4.5 holes 2-M4 or 2- ø 4.5 holes 2-M4 or 2- ø 4.5 holes 2-M4 or 2- ø 4.5 holes 4-M4 or 4- ø 4.5 holes 4-M4 or 4- ø 4.5 holes
Panel Mounting Bracket When installed on switching power supply Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout when installing on a panel directly Mounting hole layout for side mounting Side View Side View Front View Front View Front View Side View Front View Side View Front View Side View Side View Back View Mounting Screws (4 -M3×6 countersunk screws) 13.616.4 96.7 5.528.8 10.010.0 112102 105 10.29.9 109.8 24.7 112 120 102.0 110 62.9 105 115 125 135 125 10.29.9 122.8 135 145 135 10.5 10.5 145 130.6 138.6 148.6 138.6 62.3 29.5 11.8 11.8 PS9Z-5R1B PS9Z-5R1C PS9Z-5R1E PS9Z-6R1F PS9Z-6R2F Side-mount PS9Z-5R2B Side-mount 2-M4 or 2- ø 4.5 holes 2-M4 or 2- ø 4.5 holes 2-M4 or 2- ø 4.5 holes 2-M4 or 2- ø 4.5 holes 4-M4 or 4- ø 4.5 holes 4-M4 or 4- ø 4.5 holes MTBF* PS5R-VB: 900,000H minimum MIL-HDBK-217FN2 (GB, 30°C) PS5R-VC: 650,000H minimum PS5R-VD: 450,000H minimum PS5R-VE: 380,000H minimum PS5R-VF: 350,000H minimum PS5R-VG: 290,000H minimum *MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of the unit to fail and does not necessarily represent the expected life of a product.
The PS5R-V should be placed in a proper enclosure. It is designed to be used with general electrical equipment and industrial electric devices
- Do not use switching power supplies with electric equipment whose malfunction or inadvertent operation may damage the human body or life directly.
- Make sure that the input voltage and output current do not exceed the ratings. If the input voltage and output current exceed the ratings, electric shock, fire, or malfunction may occur.
- Do not touch the terminals of the switching power supply while input voltage is applied, otherwise electric shock may occur.
- Provide the final product with protection against malfunction or damage that may be caused by malfunction of the switching power supply.
- Operating temperatures should not exceed the ratings. Be sure to note the derating characteristics. If the operating temperature exceeds the ratings, electric shock, fire, or malfunction may occur.
- Blown fuses indicate that the internal circuits are damaged. Contact IDEC for repair. Do not just replace the fuse and reoperate, otherwise electric shock, fire, or malfunction may occur.
- Do not use the switching power supplies to charge rechargeable batteries.
- Do not overload or short-circuit the switching power supply for a long period of time, otherwise the internal elements may be damaged.
- Do not disassemble, repair, or modify the power supplies, otherwise the high voltage internal part may cause electric shock, fire, or malfunction.
- The fuse inside the PS5R-V switching power supply is for AC input. Use an external fuse for DC input. OPERATING INSTRUCTIONS Notes for installation
- Do not close the top or bottom openings of the PS5R-V to allow for heat radiation by convection.
- When mounting multiple PS5R-V switching power supplies side by side, maintain a minimum of 10 mm clearance. Observe the derating curves in consideration of the ambient temperature. 10mm minimum
- When the derating voltage may exceed the recommended value, provide forced air- cooling.
- Make sure to wire the ground terminal correctly.
- For wiring, use wires of heat resistance of 60oC or higher (PS5R-VB: 80oC or higher). Use copper wire of the following sizes, according to the rated current. Terminal Wire Size (allowable current) Wire Type Input AWG 18 to 14 Copper Solid/StrandedOutput AWG18 to 14 (AWG18: 7A, AWG16: 10A, AWG14: 15A) Cross-Sectional are AWG18: 0.82mm2, AWG16: 1.31mm2, AWG14: 2.0mm2 Applicable crimp terminal (reference) 7.0 max. ø3.6min.
- Recommended tightening torque of the input and output terminals is 1.0 to 1.3N·m (0.8N·m for UL). Mounting on DIN Rails 1. Use a 35mm-wide DIN rail. 2.Place the PS5R-V on the DIN rail as shown with input terminal side up (), and press the PS5R-V towards the DIN rail (). Make sure that the PS5R-V is installed firmly. 3. Use BNL6 end clips to ensure power supplies do not slide off the end of the DIN rail. Use of BNL8 end clips is recommended when excessive vibration or shock is anticipated. Removal
- Insert a flat screwdriver into the slot in the clamp, and pull out until it clicks (). The lock mechanism is released and the PS5R-V can be removed (). When mounting the PS5R-V again, push in the latch first. Mounting Removal Clamp Installing a Panel Mounting Bracket Latch Latch LOCK LOCK Panel Mounting Bracket (PS9Z-5R1, PS9Z-6R1F) Panel Mounting Bracket (PS9Z-5R2B) Power Supply Power Supply Tab Tab Slot LOCK UNLOCK LOCK UNLOCK Push in the latch to LOCK position. Install the tab on the panel mounting bracket into the slot on the power supply. Install the brackets as shown on the left. Ensure that the panel mounting bracket is locked by the latch. Pull out the latch to UNLOCK position. Insert the tab on the panel mounting bracket into the slot on the power supply. Push in the latch to LOCK position. Ensure that the panel mounting bracket is locked by the latch. Latch Latch LOCK LOCK Panel Mounting Bracket (PS9Z-5R1, PS9Z-6R1F) Panel Mounting Bracket (PS9Z-5R2B) Power Supply Power Supply Tab Tab Slot LOCK UNLOCK LOCK UNLOCK Push in the latch to LOCK position. Install the tab on the panel mounting bracket into the slot on the power supply. Install the brackets as shown on the left. Ensure that the panel mounting bracket is locked by the latch. Pull out the latch to UNLOCK position. Insert the tab on the panel mounting bracket into the slot on the power supply. Push in the latch to LOCK position. Ensure that the panel mounting bracket is locked by the latch.
IDEC Corporation • 1175 Elko Drive • Sunnyvale, CA 94089 • 800-262-IDEC (4332) • Fax: 408-745-5258 • www.IDEC.com/usa ©2016 IDEC Corporation. All Rights Reserved. PS9Y-DS500-1a PDF Only 160328157 Installing PS9Z-6R2F Side-mount Panel Mounting Bracket Install the bracket on the switching power supply using four M3 × 6 countersunk screws supplied with the bracket. Recommended tightening torque is 0.5 to 0.6N.m (should be in the center positions) Adjustment of Output Voltage The output voltage can be adjusted within ±10% (VE: ±5%) of the rated output voltage by using the VR.ADJ control on the front. Turning the VR.ADJ clockwise increases the output voltage. Turning the VR.ADJ counterclockwise decreases the output voltage. Overcurrent Protection The output voltage drops automatically when an overcurrent flows due to an overload or short circuit. Normal voltage is auto matically restored when the load returns to normal conditions. Insulation/Dielectric Test When performing an insulation/dielectric test, short-circuit the input (between L and N) and out- put (between +V and -V). Do not apply or interrupt the voltage quickly, otherwise surge voltages may be generated and the PS5R-V may be damaged. Notes for Operation
- Output interruption may indicate blown fuses. Contact IDEC.
- The PS5R-V switching power supply contains an internal fuse for AC input. When using DC input, install an exter nal fuse. To avoid blown fuses, select a fuse in consideration of the rated current of the internal fuse. Rated Current of Internal Fuses Part Number Internal Fuse Rated Current PS5R-VB/VC 2A PS5R-VD/VE/VF 4A PS5R-VG 6.3A
- Avoid overload and short-circuit for a long period of time, oth erwise the internal elements may be damaged.
- DC input operation is not subject to safety standards. Rust and Scratches on Metal parts Bonded metal parts are used for the PS5R-V. Rust on the edge and scratches on the surfaces may be developed depending on the storage condition, but the performance of the PS5R-V is not affected. Noise Small acoustic noise inside the PS5R-V may be heard depending on the input voltage and load, but the performance of the PS5R-V is not affected. Series Operation Series operation is allowed. Connect Schottky barrier diodes D as shown below. Select a Schottky diode in consideration of the rated current. The diode’s reverse voltage must be higher than the PS5R-V's output voltage. L D D N L N L N Load (a) L N L N L N Load Load (b) Parallel Operation Parallel operation is not possible to increase the output capacity, because the internal elements and load may be damaged. Backup Operation Backup operation is a connection method of two switching power supplies in parallel for emergency. Normally one switching power supply has a sufficient output. If one switching power supply fails, another one operates to continue the output. Make sure that the sum of power con- sumption by load and diode is not greater than the rated wattage (rated voltage × rated current) of one switching power supply. INAC OUT IN OUT Load D D Select a diode in consideration of: Diode's current must be more than double the PS5R-V's output current. Take heat dissipation into consideration. WARRANTY IDEC warranties the PS5R-V switching power supply for a period of five years from the date of shipment. Scope IDEC agrees to repair or replace the PS5R-V switching power supply if the product has been oper- ated under the following conditions. The maximum value of output capacity is within the range shown in “Operating Temperature vs. Output Current on page 3. 1. Average operating temperature (ambient temperature of switching power supply) is 40°C maximum. 2. The load is 80% maximum. 3. Input voltage is the rated input voltage. 4. Standard mounting style IDEC shall not be liable for other damages including consequential, contingent or incidental dam- ages. Warranty does not apply if the PS5R-V switching power supply was subject to: 1. Inappropriate handling, or operation beyond specifications. 2. Modification or repair by other than IDEC. 3. Failure caused by other than the PS5R-V switching power supply. 4. Failure caused by natural disasters.