G-8 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC GTimers General Specifications Operation System Solid state CMOS Circuit Operation Type Multi-Mode Time Range 0.1sec to 600 hours Pollution Degree 2 (IE60664-1) Over voltage category III (IE60664-1) Rated Operational Voltage AF20 100-240V AC(50/60Hz) AD24 24V AC(50/60Hz)/24V DC D12 12V DC Voltage Tolerance AF20 85-264V AC(50/60Hz) AD24 20.4-26.4V AC(50/60Hz)/21.6-26.4V DC D12 10.8-13.2V DC Input off Voltage Rated Voltage x10% minimum Ambient Operating Temperature -20 to +65ºC (without freezing) Ambient Storage and Transport Temperature -30 to +75ºC (without freezing) Relative Humidity 35 to 85%RH (without condensation) Atmospheric Pressure 80kPa to 110kPa (Operating), 70kPa to 110kPa (Transport) Reset Time 100msec maximum Repeat Error ±0.2%, ±20msec* Voltage Error ±0.2%, ±20msec* Temperature Error ±0.5%, ±20msec* Setting Error ±10% maximum Insulation Resistance 100M Ω minimum (500V DC) Dielectric Strength Between power and output terminals: 2000V AC, 1 minute Between contacts of different poles: 2000V AC, 1 minute Between contacts of the same pole:1000V AC, 1 minute Vibration Resistance 10 to 55Hz amplitude 0.5mm2 hours in each of 3 axes Shock Resistance Operating extremes: 98m/sec2 (10G) Damage limits: 490m/sec2 (50G) 3 times in each of 3 axes Degree of Protection IP40 (enclosure) (IEC60529) Power Consumption (Approx.) TYPE RTE-P1, -B1 RTE-P2, -B2 AF20 120V AC/60Hz 6.5VA 6.6VA 240V AC/60Hz 11.6VA 11.6VA 24V AC 60Hz/DC 3.4VA/1.7W 3.5VA/1.7W D12 1.6W 1.6W Mounting Position Free Dimensions RTE-P1, P2 40Hx 36W x 77.9D mm RTE-B1, B2 40Hx 36W x 74.9D mm Weight (Approx.) RTE-P1 RTE-P2 RTE-B1, -B2 87g 89g 85g R TE Series — Analog Timers UL Listed File No. E66043 Cert. No. E9950913332316 (EMC, RTE) cert. No. BL960813332355 (LVD, RTE) Contact Ratings Contact Configuration 2 Form C, DPDT (Delay output) Allowable Voltage / Allowable Current 240V AC, 30V DC / 10A Maximum Permissible Operating Frequency 1800 cycles per hour Rated Load Resistive 10A 240V AC, 30V DC Inductive 7A 240V AC, 30V DC Horse Power Rat- ing 1/6 HP 120V AC, 1/3 HP 240V AC Life Electrical 500,000 op. minimum (Resistive) Mechanical 50,000,000 op. minimum RTE Table of Contents Specifications —G-8 Part Number Guide — G-9 Part Number List — G-9 RTE Timing Diagrams — G-10 RTE Accessories — G-12 Instructions: Setting Timer — G-11 RTE Dimensions — G-13 General Timing Diagrams — G-4 *For the value of the error against a preset time, whichever the largest. Key features of the RTE series include:

  • 20 time ranges and 10 timing functions
  • T ime delays up to 600 hours
  • Space-saving package
  • High repeat accuracy of ± 0.2%
  • ON and timing OUT LED indicators
  • Standard 8- or 11-pin and 11-blade termination
  • 2 form C delayed output contacts
  • 10A Contact Rating

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-9 GTimers RTE series part numbers are composed of 4 part number codes. When ordering a RTE series part, select one code from each category. Example: RTE-P1AF20 Part Numbers: RTE Series Part Numbers Time Range Determined by Time Range Selector & Dial Selector Description Part Number Code Remarks ➀ Series RTE series RTE For internal circuits, see next page. ➁ Terminal Style Pin P Select one only. Blade B ➂ Function Group ON-delay, interval, cycle OFF, cycle ON 1 Each function group has different timing functions. See page G-4.ON-delay, cycle OFF, cycle ON, signal ON/OFF delay, OFF-delay, one-shot 2 ➃ Input Voltage 100 to 240V AC(50/60Hz) AF20 24V AC(50/60Hz)/24V DC AD24 12V DC D12 Power Triggered Start Input Triggered Voltage 8-Pin Blade 11-Pin Blade 12V DC RTE-P1D12 RTE-B1D12 RTE-P2D12 RTE-B2D12 24V AC/DC RTE-P1AD24 RTE-B1AD24 RTE-P2AD24 RTE-B2AD24 100-240V AC RTE-P1AF20 RTE-B1AF20 RTE-P2AF20 RTE-B2AF20 Dial 0 - 1 0 - 3 0 - 10 0 - 30 0 - 60 Range Minute 1.2 sec - 1 min 3.6 sec - 3 min 12 sec - 10 min 36 sec - 30 min 1.2 min - 60 min Hour 1.2 min - 1 hr 3.6 min - 3 hr 12 min - 10 hr 36 min - 30 hr 1.2 hr - 60 hr

10 Hours 12 min - 10 hr 36 min - 30 hr 2 hr - 100 hr 6 hr - 300 hr 12 hr - 600 hr

➀ Series ➁ Terminal AF201RTE P ➂ Function Group ➃ Input Voltage Style Part Number List Time Range Table

G-10 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC GTimers Timing Diagrams RTE-P2 4 8 (~/-)(~/+) start RTE-B2 2 3 A B (~/-)(~/+) 4 5 6 7 8 2 3 A B (~/-)(~/+) 5 6 7 8 RTE-B1 4 5 (~/-)(~/+) RTE-P1 start ext ern al co ntr ol ext ern al co ntr ol E: Signal OFF-Delay C: Cycle 1 (power start, OFF first) A: ON-Delay 1 (power start) Set timer for desired delay, apply power to coil. First transfer of contacts occurs after preset delay has elapsed, after the next elapse of preset delay contacts return to original position. The timer now cycles between on and off as long as power is applied (duty ratio 1:1). Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (1)1-4,5-8 (2)1-7,3-9 (NC) (1)1-3,6-8 (2)4-7,6-9 (NO) (1)2-7 (2)A-B Operation TT When a preset time has elapsed after the start input turned on while power is on, the NO output contact goes on. RTE-P1, -B1 Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (A)1-4,8-11 (B)1-7,3-9 (NC) (A)1-3,9-11 (B)4-7,6-9 (NO) (A)2-10 (B)A-B Operation Start (A)5-6 (B)2-5 T When the start input turns on while power is on, the NO contact goes on. The output oscillates at a preset cycle (duty ratio 1:1). Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (A)1-4,8-11 (B)1-7,3-9 (NC) (A)1-3,9-11 (B)4-7,6-9 (NO) (A)2-10 (B)A-B Operation Start (A)5-6 (B)2-5 TT a TT T TTTT When power is turned on while the start input is on, the NO output contact goes on. When a preset time has elapsed after the start input turned off, the NO output contact goes off. Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (A)1-4,8-11 (B)1-7,3-9 (NC) (A)1-3,9-11 (B)4-7,6-9 (NO) (A)2-10 (B)A-B Operation Start (A)5-6 (B)2-5 TT a Ta T When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed, the NO output contact goes off. Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (A)1-4,8-11 (B)1-7,3-9 (NC) (A)1-3,9-11 (B)4-7,6-9 (NO) (A)2-10 (B)A-B Operation Start (A)5-6 (B)2-5 TT a Set timer for desired delay, apply power to coil. Contacts transfer after preset time has elapsed, and remain in transferred position until timer is reset. Reset occurs with removal of power. Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (1)1-4,5-8 (2)1-7,3-9 (NC) (1)1-3,6-8 (2)4-7,6-9 (NO) (1)2-7 (2)A-B Operation T Set timer for desired delay, apply power to coil. Contacts transfer immediately, and return to original position after preset time has elapsed. Reset occurs with removal of power. Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (1)1-4,5-8 (2)1-7,3-9 (NC) (1)1-3,6-8 (2)4-7,6-9 (NO) (1)2-7 (2)A-B Operation T Note : T=Set Time, Ta=Shorter than set time, (1): RTE-P1, (2): RTE-B1, (A): RTE-P2, (B): RTE-B2 Functions in same manner as Mode C, with the exception that first transfer of contacts occurs as soon as power is applied. The ratio is 1:1. Time On = Time Off Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (1)1-4,5-8 (2)1-7,3-9 (NC) (1)1-3,6-8 (2)4-7,6-9 (NO) (1)2-7 (2)A-B Operation TT RTE-P2, -B2 When the start input turns on while power is on, the output oscillates at a preset cycle (duty ratio 1:1), starting while the NO contact off. Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (A)1-4,8-11 (B)1-7,3-9 (NC) (A)1-3,9-11 (B)4-7,6-9 (NO) (A)2-10 (B)A-B Operation Start (A)5-6 (B)2-5 TT a TT T TTTT T When the start input turns on while power is on, the NO output contact goes on. When a preset time has elapsed while the start input remains on, the output contact goes off. When the start input turns off, the NO contact goes on again. When a preset time has elapsed after the start input turned off, the NO contact goes off. D: Signal ON/OFF-Delay Item Terminal No. Power Delayed Contact Indicator Set Time PWR OUT (A)1-4,8-11 (B)1-7,3-9 (NC) (A)1-3,9-11 (B)4-7,6-9 (NO) (A)2-10 (B)A-B Operation Start (A)5-6 (B)2-5 TT a TT a T T A: ON-Delay 2 (signal start) C: Cycle 4 (signal start, ON first) F: One-Shot (signal start) B: Cycle 2 (signal start, OFF first) B: Interval (power start) D: Cycle 3 (power start, ON first) 1. RTE-P2: Do not apply voltage to terminals #5, #6 & #7. 2. RTE-B1, -B2: Do not apply voltage to terminals #2, #5 & #8. 3. IDEC sockets are as follows: RTE-P1: SR2P-06* pin type socket, RTE-P2: SR3P-05* pin type socket, RTE-B1, -B2: SR3B-05* blade type socket, (*-may be followed by suffix letter A,B,C or U).

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-11 GTimers Types Switch Settings Installation of Hold-Down Springs Temperature Derating Curves Mounting BMounting A 10A Ambient Temperature Allowable CurrentMounting A Derating Curve Ambient Temperature Allowable Current Mounting B Derating Curve 50ºC 65ºC 50ºC 65ºC Instructions RTE-P1AF20 Connection type P: Pin B: Blade Operation Mode Power Voltage AF20: 100 to 240V AC(50/60Hz) AD24: 24V AC(50/60Hz)/24V DC D12: 12V DC 2: Control Signal A: ON-Delay 2 B: Cycle 2 C: Cycle 4 Signal ON/OFF-Delay E: Signal OFF-Delay F: One-Shot 1: No Control Signal A: ON-Delay 1 B: Interval C: Cycle 1 D: Cycle 3 Time Range Selector Scale Selector Operation Mode Selector 1. Turn the selectors securely using a flat screwdriver 4mm wide (maximum). Note that incorrect setting may cause malfunction. Do not turn the selectors beyond their limits. 2. Since changing the setting during timer operation may cause malfunction, turn power off before changing. D IN Rail Mount Socket Socket SR2P-06 Hold-down Spring (sold separately) SFA-202 (use two springs) Insert the springs into the outer slots with the projections facing inside. Socket SR3P-05 Insert the springs into the slots. Hold-down Spring (sold separately) SFA-203 (use two springs)Safety Precautions Special expertise is required to use Electronic Timers.

  • All Electronic Timers are manufactured under IDEC's rigorous qual- ity control system, but users must add a backup or fail safe provision to the control system when using the Electronic Timer in applica- tions where heavy damage or personal injury may occur should the Electronic Timer fail.
  • Install the Electronic Timer according to instructions described in this catalog.
  • Make sure that the operating conditions are as described in the spec- ifications. If you are uncertain about the specifications, contact IDEC in advance.
  • In these directions, safety precautions are categorized in order of importance under Warning and Caution. Warnings W arning notices are used to emphasize that improper operation may cause severe personal injury or death.
  • Turn power off to the Electronic timer before starting installation, removal, wiring, maintenance, and inspection on the Electronic Timer.
  • Failure to turn power off may cause electrical shocks or fire hazard.
  • Do not use the Electronic Timer for an emergency stop circuit or interlocking circuit. If the Electronic Timer should fail, a machine malfunction, breakdown, or accident may occur. Caution Caution notices are used where inattention might cause personal injury or damage to equipment.
  • The Electronic Timer is designed for installation in equipment. Do not install the Electronic Timer outside equipment.
  • Install the Electronic Timer in environments described in the specifi- cations. If the Electronic Timer is used in places where it will be subjected to high-temperature, high-humidity, condensation, corro- sive gases, excessive vibrations, or excessive shocks, then electrical shocks, fire hazard, or malfunction could result.
  • Use an IEC60127-approved fuse and circuit breaker on the power and output line outside the Electronic Timer.
  • Do not disassemble, repair, or modify the Electronic Timer.
  • When disposing of the Electronic Timer, do so as industrial waste.

G-12 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC GTimers Part Numbers: DIN Rail/Surface Mount Sockets and Hold-Down Springs Part Numbers: Flush Panel Mount Adapter and Sockets that use an Adapter DIN Rail Mount Socket Applicable Hold-Down Springs Style Appearance Use with Timers Part No. Appearance Part No. 11-Pin Screw Terminal (dual tier) RTE-P2 SR3P-05 SFA-203 11-Pin FingerSafe Socket RTE-P2 SR3P-05C 8-Pin Screw Terminal RTE-P1 SR2P-06 SFA-202 11-Blade Screw Terminal RTE-B1 RTE-B2 SR3B-05 DIN Mounting Rail Length 1000mm — BNDN1000 Accessory Description Appearance Use with Part No. Panel Mount Adapter Adaptor for flush panel mounting RTE timers All RTE timers RTB-G01 Sockets for use with Panel Mount Adapter 8-pin screw terminal RTE-P1 SR6P-M08G 11-pin screw terminal RTE-P2 SR6P-M11G 8-pin solder terminal RTE-P1 SR6P-S08 11-pin solder terminal RTE-P2 SR6P-S11 DIN Rail Mounting Accessories Panel Mounting Accessories (Shown: SR6P-M08G Wiring Socket Adapter) No hold down clips are available for flush panel mounting applications.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-13 GTimers Dimensions 36.0 77.9 40.0 13.0 7.3 13.7 RTE-P1 (8 pin) Terminal Style RTE-P2 (11 pin)Terminal Style RTE-B1/RTE-B2 (11 blade) Terminal Style Panel Mount Adapter R TE Timer, 8-Pin and 11-Pin with SR6P-S08 or SR6P-S11 Back Wiring Socket 1.7 11 61.2 Panel Thickness 0.8 to 5mm 42.5 98 maximum R TE Timer, 8-Pin with SR6P-M08G R TE Timer, 11-Pin with SR6P-M11G ø3.6 min. 8-M3.5 Terminal Screw 2187 3456 6.9 max. 30.4 44.6 Panel Thickness 0.8 to 5mm 80.5 9.8 × 3 44.6 3.5 max. 5.6 min. ø3.6 min. 11-M3.5 Teminal Screws 6.9 max. 4389 10 2 11 17 6 3.5 max. 5.8 min. 30.5 7 8.5 × 4 16.7

General Instructions Timers G-68 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC GTimers Timing accuracies are calculated from the following formulas: Repeat Error Voltage Error Tv: Average of measured values at voltage V Tr: Average of measured values at the rated voltage Temperature Error Tt: Average of measured values at °C T20: Average of measured values at 20°C Setting Error General Instructions for All Timer Series Load Current With inductive, capacitive, and incandescent lamp loads, inrush current more than 10 times the rated current may cause welded contacts and other undes- ired effects. The inrush current and steady-state current must be taken into consideration when specifying a timer. Contact Protection Switching an inductive load generates a counter-electromotive force (back EMF) in the coil. The back EMF will cause arcing, which may shorten the con- tact life and cause imperfect contact. Application of a protection circuit is recommended to safeguard the contacts. Temperature and Humidity Use the timer within the operating temperature and operating humidity ranges and prevent freezing or condensation. After the timer has been stored below its operating temperature, leave the timer at room temperature for a sufficient period of time to allow it to return to operating temperatures before use. Environment Avoid contact between the timer and sulfurous or ammonia gases, organic solvents (alcohol, benzine, thinner, etc.), strong alkaline substances, or strong acids. Do not use the timer in an environment where such substances are prevalent. Do not allow water to run or splash on the timer. Vibration and Shock Excessive vibration or shocks can cause the output contacts to bounce, the timer should be used only within the operating extremes for vibration and shock resis- tance. In applications with significant vibration or shock, use of hold down springs or clips is recommended to secure a timer to its socket. Time Setting The time range is calibrated at its maximum time scale; so it is desirable to use the timer at a setting as close to its maximum time scale as possible. For a more accurate time delay, adjust the control knob by measuring the operat- ing time with a watch before application. Input Contacts Use mechanical contact switch or relay to supply power to the timer. When driving the timer with a solid-state output device (such as a two-wire proxim- ity switch, photoelectric switch, or solid-state relay), malfunction may be caused by leakage current from the solid-state device. Since AC types com- prise a capacitive load, the SSR dielectric strength should be two or more times the power voltage when switching the timer power using an SSR. Generally, it is desirable to use mechanical contacts whenever possible to apply power to a timer or its signal inputs. When using solid state devices, be cautious of inrushes and back-EMF that may exceed the ratings on such devices. Some timers are specially designed so that signal inputs switch at a lower voltage than is used to power the timer (models designated as “B" type). T iming Accuracy Formulas = ± 1 x Maximum Measured Value – Minimum Measured Value x 100% Maximum Scale Value2 = ± Tv - Tr x 100% Tr = ± Tt - T20 x 100% T20 = ± Average of Measured Values - Set Value x 100% Maximum Scale Value