MODEL: PTPH PTPH SPECIFICATIONS ES-1306 Rev.5 Page 1/3 http://www.m-system.co.jp/ Plug-in Signal Conditioners M-UNIT PT TRANSMITTER (true RMS sensing; high speed response; peak hold) Functions & Features

  • Converts an alternating voltage from a voltage transformer into a standard process signal
  • Dual output: The second output can be switched to ‘peak hold’ mode with the front DIP switch
  • Resetting the peak hold output with the front reset control button
  • True RMS sensing with fast 50-millisecond response time (0 – 90 %) is possible
  • Isolation up to 2000 V AC Typical Applications
  • Monitoring impulsive power line voltage change (1.97) 136 (5.35) (3.15) mm (inch) MODEL: PTPH–[1][2][3]-[4][5]

ORDERING INFORMATION

  • Code number: PTPH-[1][2][3]-[4][5] Specify a code from below for each [1] through [5]. (e.g. PTPH-5AA-M2/CE/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01) [1] INPUT Voltage 1: 0 – 110 V AC 2: 0 – 220 V AC 5: 0 – 150 V AC 6: 0 - 300 V AC 8: 0 – 259 V AC [2] OUTPUT 1 Current A: 4 – 20 mA DC (Load resistance 500 Ω max.) G: 0 – 1 mA DC (Load resistance 10 kΩ max.) Voltage 4: 0 – 10 V DC (Load resistance 10 kΩ min.) 5: 0 – 5 V DC (Load resistance 5000 Ω min.) 6: 1 – 5 V DC (Load resistance 5000 Ω min.) [3] OUTPUT 2 (momentary value or peak hold) Current A: 4 – 20 mA DC (Load resistance 350 Ω max.) G: 0 – 1 mA DC (Load resistance 7000 Ω max.) Voltage Same range availability as Output 1 [4] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) (CE not available) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.) (CE not available) [5] OPTIONS (multiple selections) Standards & Approvals blank: Without CE /CE: CE marking Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3.5 screw terminals Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output 1 to output 2 to contact input to power Input waveform: Up to 20 % of 3rd harmonic content Overrange output: 0 to 120 % at 1 – 5 V Zero adjustment: -5 to +5 % (front)

MODEL: PTPH PTPH SPECIFICATIONS ES-1306 Rev.5 Page 2/3 http://www.m-system.co.jp/ Span adjustment: 95 to 105 % (front) Adjustable individually for each output 1 and output 2. Indicator LED: Red light blinks in 800 millisecond intervals when the power is supplied; blinks in 200 millisecond intervals when the peak hold output is reset. Function setting: DIP switch

  • Output 2 Function (Momentary value output/Peak hold value output)
  • Line Frequency
  • Response Time Reset control: Used to reset the peak hold output. Momentary value is output immediately after the resetting. INPUT SPECIFICATIONS ■ VOLTAGE INPUT Frequency: 50 or 60 Hz Input burden: ≤ 0.5 VA Overload capacity: 200 % of rating for 1 minute, 120 % continuous Operational range: 0 – 120 % of rating ■ Contact Input: Used to reset the peak hold output. Momentary value is output immediately after the resetting. Detecting voltage/current: 15 V DC / approx. 2.5 mA Detection levels: ≤ 5 kΩ, ≤ 6 V for ON; ≥ 100 kΩ, ≥ 14 V for OFF INSTALLATION Power Consumption
  • AC: Approx. 5 VA at 100 V Approx. 6 VA at 200 V Approx. 7 VA at 240 V
  • DC: Approx. 3 W Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 210 g (0.46 lb) PERFORMANCE in percentage of span Accuracy: ±0.5 % Temp. coefficient: ±0.03 %/°C (±0.02 %/°F) Response time: ≤ 50/100/200/500 msec. (0 – 90 %) Peak hold reset time: 20 msec. Ripple: 0.5 %p-p max. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to output 1 or output 2 or contact input to power to ground)

500 V AC @ 1 minute (output 1 to output 2 to contact input)

Impulse withstand voltage: 1.2/50 μsec., ±5 kV (input to output 1 or output 2 or contact input or ground) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (input) Installation Category II (power) Pollution Degree 2 Contact input or output to power: Reinforced insulation (300 V) Input to output: Reinforced insulation (300 V) Input to contact input or power: Basic insulation (300 V) RoHS Directive EN 50581

MODEL: PTPH PTPH SPECIFICATIONS ES-1306 Rev.5 Page 3/3 http://www.m-system.co.jp/ EXTERNAL VIEW ON ON Span Adj. Zero Adj. Output 2 Span Adj. Zero Adj. Output 1 Reset Control Indicator LED Function Setting Line Freq Output 2 Response Time EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 5678 2111 10 80 (3.15) 80 (3.15) (.79) 40 (1 .57) 50 (1 .97) 7 .8 (.31) CLAMP (top & bottom) DIN RAIL 35mm wide2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 11 –M3.5 SCREW

  • When mounting, no extra space is needed between units. SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM V U v uFUSE VT LOAD SOURCE Base Socket Digital Computation INPUT TRANSFORMER U(+) V(–) POWER OUTPUT 1 SZ Output Driver SZ Output Driver OUTPUT 2 CONTACT INPUT Isolation Isolation DIP SW RESET LED Specifications are subject to change without notice.