PP10-IEC NOVARIS | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 1
Technical content
POWER PROTECTION - Surge Filters Plug-in Surge Filters Electrical Specifications Connection type Series Modes of protection All mode (L-N, L-PE, N-PE) Nominal voltage U 0 230V / 50Hz Maximum continuous voltage U c 275V / 50Hz Maximum discharge current (8/20µs) I max 50kA Nominal discharge current (15 x 8/20μs) I n 20kA Maximum load current I L 10A Protection stages Metal oxide varistor / LC filter / Metal oxide varistor Voltage protection level @3kA (8/20µs) U P <600V Response time t A Instantaneous Power Consumption (@230V 50Hz) <1W Attenuation -3dB at 900Hz, -60dB at 100kHz Earth leakage current <500µA Maximum voltage drop (% of U0) ΔU <1% Display LED power and status Mechanical Specifications Dimensions Standards Compliance IEC 61643-11 class II, III AS/NZS 1768 categories A, B IEEE C62.41 categories A, B IEC 1000-4-5 Country Option Australian - AS-3112 A European - CEE7/4 E British - BS-1363 B Novaris plug-in surge filters plug into a standard mains outlet socket to provide premium protection for sensetive or critical electronic equipment PP10-IEC PP10-IEC Operating temperature / humidity -40 to +70ºC / 0 to 90% non-condensing Connection type - line side cord IEC C14 Inlet Connection type - load side outlet IEC C14 Socket Number of outlets 1 Environmental IP 20 Mounting Free standing, (optional wall mount -M) Weight 1.2kG Width 100 mm Height 140mm Depth 60mm