PMP105 TTELEC | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 3

Technical content

© TT Electronics plc General Note All data sheets are subject to change without notice. ISS.2 14/07/2020 Page: 1 TT Electronics | Power Partners, Inc 43 Broad Street Suite B206, Hudson, MA 01749, USA. t: +1 (978) 567-9600 Description: The PMP105 series of AC/DC switching power supplies are for 90-105 watts of continuous output power. They are enclosed in a 94V-0 rated polyphenylene-oxide case with an IEC320/C14, C6, C18 or C8 inlet to mate with interchangeable cord for world-wide use. All models meet EN55011 and FCC class B emission limits, and are designed for medical applications. Features:

  • Low safety ground leakage current
  • Wide input range 90 to 264 VAC
  • Optional output connectors
  • 100% burn-in at full load
  • Overvoltage protection
  • Over-temperature protection
  • Overcurrent protection
  • Compliant with CEC and Energy Star Efficiency Level V requirements * No load power consumption less than 0.5W * Average active efficiency greater than 87%
  • Compliant with RoHs requirements
  • IEC 60601-2-4th Edition EMC Compliant Model (1) Output Average Active Efficiency (typical) @115/230 Vac Class I (1) Class II (2) V1 Imin. Tol Ripple & Noise4 Max Power Peak Current3 Imax. PMP105-12 PMP105SF-12 12V 0A ±5% 120mV 90W 87/87% 15A 7.5A PMP105-12-1 PMP105SF-12-1 13V 0A ±5% 130mV 90W 87/87% 13.8A 6.93A PMP105-13 PMP105SF-13 14-16V 0A ±5% 150mV 95W 87/88% 13.58A 6.79A PMP105-13-1 PMP105SF-13-1 18-19V 0A ±5% 180mV 105W 88/89% 11.6A 5.84A PMP105-13-3 PMP105SF-13-3 20-21V 0A ±5% 200mV 105W 88/89% 10.5A 5.25A PMP105-14 PMP105SF-14 24-25V 0A ±5% 240mV 105W 88/89% 8.7A 4.38A PMP105-15 PMP105SF-15 28-29V 0A ±5% 280mV 105W 88/89% 4.5A 3.75A PMP105-16 PMP105SF-16 30-32V 0A ±5% 300mV 105W 88/89% 4.2A 3.50A PMP105-17 PMP105SF-17 36-38V 0A ±5% 360mV 105W 89/90% 3.5A 2.92A PMP105-18 PMP105SF-18 46-50V 0A ±5% 480mV 105W 90/91% 2.7A 2.29A NOTES: 1. Class I models are equipped with IEC320/C14 inlet. To order a model with C6 inlet, add “S” to the prefix, PMP105, of model number, e.g. PMP105S-12. 2. Class II models are equipped with IEC320/C8 inlet. To order a model with C18 inlet, change “SF” in the prefix of model number to “F”, e.g. PMP105F-12. 3. For 10 seconds maximum, average power not to exceed maximum power rating. 4. Ripple and noise is maximum peak to peak voltage value measured at output within 20 MHz bandwidth, at rated line voltage and output load ranges, and with a 10 μF tantalum capacitor in parallel with a 0.1 μF ceramic capacitor across the output.

© TT Electronics plc General Note All data sheets are subject to change without notice. ISS.2 14/07/2020 Page: 2 TT Electronics | Power Partners, Inc 43 Broad Street Suite B206, Hudson, MA 01749, USA. t: +1 (978) 567-9600 Specifications Safety Standards & EMC Specifications Safety Standard Approvals UL ES 60601-1, CSA C22.2 No. 60601-1 File No. E178020 TÜV EN 60601-1 EMI Standard EN55011, FCC & VCCI Class B conducted and radiated EMC Performance EN61000-3-2: Harmonic distortion, class A and D EN61000-3-3: Line flicker EN61000-4-2: ESD, ±15 KV air and ±8 KV contact EN61000-4-3: Radiated immunity, 10 V/m EN61000-4-4: Fast transient/burst, ±2 KV EN61000-4-5: Surge, ±1 KV diff., ±2 KV com EN61000-4-6: Conducted immunity, 10 Vrms EN61000-4-8: Magnetic field immunity, 30 A/m EN61000-4-11: Voltage dip immunity, 30% reduction for 500 ms, 100% reduction for 10 ms *Consult with TT Electronics for information on additional country safety approvals Input Specifications Input Voltage Range 90-264 VAC Input Frequency Range 47 to 63Hz Input Current 1.4 A (rms) for 115 VAC, 0.7 A (rms) for 230 VAC Earth Leakage Current 200 μA max. @ 264 VAC, 63Hz Touch Current 100 μA max. @ 264 VAC, 63Hz Power Factor >0.9 Output Specifications Ripple and Noise 1% peak to peak maximum at the full load Overvoltage Protection Provided and set at 115-140% of its nominal output voltage Overcurrent Protection Protected to short circuit conditions Temperature Coefficient ±0.04% /°C maximum Transient Response Maximum excursion of 4% or better on all models, recovering to 1% of final value within 500 us after a 25% step load change Environmental Specifications Operating Temperature 0°C to +60°C (See Derating) Storage Temperature -40°C to +85°C Relative Humidity 5% to 95% non-condensing Temperature derating Derate from 100% at +40°C linearly to 50% at +60°C General Specifications Switching Frequency 70-140KHz Power Factor 0.98 Typical at 115 VAC Efficiency 87% min. at full load Hold-up Time 10ms minimum at 110 VAC Line Regulation ±0.5% maximum at full load Inrush Current 80 A @ 115 VAC or 120 A @ 230 VAC, at 25℃ cold start Withstand Voltage

5600 VDC from input to output (2 MOPP)

2100 VDC from input to ground (1 MOPP)

700 VDC from output to ground

(To verify AC strength, get correct test method to avoid power sup- ply damage.) For Class II models, 4000 VAC from input to output MTBF 150,000 hours at full load at 25℃ ambient, calculated per MIL-HDBK -217F