© TT Electronics plc General Note All data sheets are subject to change without notice. TT Electronics | Power Partners, Inc 43 Broad Street Suite B206, Hudson, MA 01749, USA. t: +1 (978) 567-9600 ISS.1 22/07/2020 Page: 1 Description: The PM110 series of compact, open PCB constructed, AC-DC switching power supplies are specially designed for medical applications. They are capable of delivering 72-110 watts of continuous power at 25 CFM forced air cooling or 60-80 watts at convection cooling. They operate at 85-264VAC input voltage without the need of a selector strap. All models meet the safety requirements of UL, CSA and IEC for medical equipment. Features:
- Low safety ground leakage current
- Meet EN55011 and FCC Class B
- Small size, light weigh
- 100% burn-in
- Wide input range 85-264 VAC
- Input surge current protection
- Overvoltage protection
- Overcurrent protection
- Compliant with RoHS requirements Model1 Output #12 Output #2 Output #3 Output #4 Max. Output Power3 V1 Imin Imax Tol. V2 Imin Imax Tol. V3 Imin Imax Tol. V4 Imin Imax Tol. Ipeak4 PM110-10-1A 3.3V 0A 22A ±3% (N/A) 60/72W PM110-10A 5V 0A 22A ±3% (N/A) 80/110W PM110-12A 12V 0A 9A ±2% (N/A) 80/110W PM110-13A 15V 0A 7.5A ±2% (N/A) 80/110W PM110-14A 24V 0A 4.5A ±2% (N/A) 80/110W PM110-16A 30V 0A 3.6A ±3% (N/A) 80/110W PM110-23A 5.1V 0A 10A ±3% 12V 0A 5A ±3% (N/A) 80/110W 9A PM110-31A 5.1V 0A 10A ±3% 12V 0A 5A ±3% -12V 0A 1A ±4% (N/A) 80/110W 9A PM110-32A 5.1V 0A 10A ±3% 15V 0A 4A ±3% -15V 0A 1A ±4% 80/110W (N/A) 7.5A PM110-40A 5.1V 0A 10A ±3% 12V 0A 5A ±3% -12V 0A 1A ±4% -5V 0A 1A ±4% 80/110W 9A PM110-41A 5.1V 0A 10A ±3% 15V 0A 4A ±3% -15V 0A 1A ±4% 24V 0A 1A ±4% 80/110W 7.5A PM110-42A 5.1V 0A 10A ±3% 12V 0A 5A ±3% -12V 0A 1A ±4% 12V 0A 1A ±4% 80/110W 9A PM110-45A 5.1V 0A 10A ±3% 12V 0A 5A ±3% -12V 0A 1A ±4% 24V 0A 1A ±4% 80/110W 9A PM110-45-1A 5.1V 0A 10A ±3% 12V 0A 5A ±3% -12V 0A 1A ±4% 24V 1.5A 3A ±10% 80/110W 9A PM110-45-2A 5.1V 0A 10A ±3% 24V 0A 3A ±3% -12V 0A 1A ±4% 12V 0A 1A ±4% 80/110W 5A PM110-46A 5.1V 0A 10A ±3% 15V 0A 4A ±3% -15V 0A 1A ±4% -5V 0A 1A ±4% 80/110W 7.5A NOTES: 1. Safety agency approvals are for the above listed models in PCB format. To order a model with a metallic L-bracket or box, change suffix “A” to “B” for L-bracket format, to “C” for enclosed form with cover, e.g. PM110-14C. (mechanical details shown in Annex H) 2. The output #1 of model PM110-45-1A needs a minimum current of 2A to support the other outputs at their maximum rated load. 3. 110 watts maximum at 25 CFM forced air cooling or 80 watts maximum at convection cooling, except model PM110 -10-1A which is rated at 60 watts maximum at convection cooling or 72 watts maximum at 25 CFM forced air cooling. 4. Peak output current with 10% maximum duty cycle for less than 60 seconds. Total peak power must not exceed 130 watts. 5. All models may be operated at no-load. At no-load, output voltage tolerance increases to ±10%. 6. Ripple and noise is maximum peak to peak voltage value measured at output within 20 MHz bandwidth, at rated line voltage and output load ranges, and with a 10 μF tantalum capacitor in parallel with a 0.1 μF ceramic capacitor across the output.
© TT Electronics plc General Note All data sheets are subject to change without notice. TT Electronics | Power Partners, Inc 43 Broad Street Suite B206, Hudson, MA 01749, USA. t: +1 (978) 567-9600 ISS.1 22/07/2020 Page: 2 Specifications Safety Standards & EMC Specifications Safety Standard Approvals UL ES 60601-1, CSA C22.2 No. 60601-1 File No. E178020 TÜV EN 60601-1 EMI Standard EN55011/EN55022, FCC & VCCI Class B (radiated and conducted) EMC Performance EN61000-3-2: Harmonic distortion, Class A EN61000-3-3: Line flicker EN61000-4-2: ESD, ±15 KV air and ± 8KV contact EN61000-4-3: Radiated immunity, 10V/m EN61000-4-4: Fast transient/burst, ±2KV EN61000-4-5: Surge, ±1 KV diff., ±2 KV com. EN61000-4-6: Conducted immunity, 10Vrms EN61000-4-8: Magnetic field immunity, 30 A/m EN61000-4-11: Voltage dip immunity, 30% reduction for 500ms, and 100% reduction for 10ms *Consult with TT Electronics for information on additional country safety approvals Input Specifications Input Voltage Range 85 to 264VAC Input Frequency Range 47 to 63Hz Input Current 3.2A (rms) @115VAC, 60 Hz 1.8A (rms) @240VAC, 50 Hz Earth Leakage Current 220μA max. @ 264VAC, 63Hz Touch Current 100μA max. @ 264VAC, 63Hz Output Specifications Ripple & Noise 1% peak to peak maximum Overvoltage Protection Provided on output #1 only; set at 112-132% of its nominal output voltage Overcurrent Protection All outputs protected to short circuit conditions Temperature Coefficient All outputs ±0.04%/°C maximum Transient Response Maximum excursion of 4% or better on all models, recovering to 1% of final value within 500 µs after a 25% step load change Environmental Specifications Operating Temperature -10°C to +70°C Storage Temperature -40°C to +85°C Relative Humidity 5% to 95% non-condensing Temperature Derating De-rate from 100% at +50°C linearly to 50% at +70°C Cooling 72-110 watts continuous output power at 25 CFM forced air cooling or 60- 80 watts at convection cooling General Specifications Switching Frequency 20-250 KHz, varied with load and line Power Factor >0.9 Efficiency 70% minimum on single output model with Vo ≥12 V, 65% minimum on the others Hold-up Time 12ms minimum at 110 VAC Line Regulation ±0.5% maximum at full load Inrush Current 15A @ 115 Vac or 30A @ 230 Vac at 25°C cold start Withstand Voltage
5600 VDC from input to output (2 MOPP)
2100 VDC from input to ground (1 MOPP)
700 VDC from output to ground
(To verify AC strength, get correct test method to avoid power supply dam- age.) MTBF 400,000 hours at full load at 25°C ambient, calculated per MIL-HDBK-217F Interface Signals PFD: TTL logic high for normal operation and TTL logic low upon loss of input power. This signal appears at least 1 ms prior to V1 output dropping 5% below its nominal value. This signal also provides a minimum delay of 100 ms after V1 is within regulation