Features

  • Configurable power supply
  • Low profile for 1U applications
  • Medical and ITE approvals
  • Power from 850W at low line to 1200W at high line
  • Output voltages from 3V3 to 60V
  • Module power up to 300W
  • Parallel options for increased versatility
  • PMBus digital interface
  • Graphical user interface (GUI)
  • Optional reverse air fans with no load derating
  • 3 year warranty Healthcare Semi-fab Industrial Electronics & Robotics Instrumentation Technology Max Power 90 to 180VAC Max Power 180 to 264VAC Standby Capacity Width Code 850W 1200W 5V/2A 4 slots 4.2” (106.7 mm) N12 Models & Ratings Notes: For mechanical details, refer to pages 10 & 11. Series

Voltage Range(1,2) Preset Voltage Maximum Current Maximum Power Slots Code 3.3-5.5V 3V3 40.0A 132W 1 A Blank plate B 3.3-5.5V 5V 40.0A 200W 1 C 5V2 38.5A 200W 1 D 5V5 36.4A 200W 1 E 8-15V 8V 20.8A 166W 1 F 10V 20.8A 208W 1 G 12V 20.8A 250W 1 H 14V 17 .9A 250W 1 I 15V 16.7A 250W 1 J 18-30V 18V 12.5A 225W 1 K 20V 12.5A 250W 1 L 24V 12.5A 300W 1 M 28V 10.7A 300W 1 N 30V 10.0A 300W 1 O 33-60V 33V 9.09A 300W 1 P 36V 8.33A 300W 1 Q 48V 6.25A 300W 1 R 54V 5.56A 300W 1 S 60V 5.0A 300W 1 T Modules Notes: For configurations, refer to page 4. 1. Module output voltage can be adjusted within given range using digital serial interface, external 0 to 5.0V signal or inbuilt potentiometer. 2. The table shows the standard preset voltages available. For factory setting of other voltages a model order code will be assigned at the time of order. Series Input Characteristic Minimum Typical Maximum Units Notes & Conditions Input Voltage - Operating 90 264 VAC Input Voltage - Fault Condition 300 VAC For 5s maximum, without derating or damage Input Frequency 47 63 Hz 400Hz operation okay but not covered by safety approval Power Factor 0.98 230VAC 100% load EN61000-3-2 class A Input Current - Full Load 9.0/6.3 A 115/230VAC Inrush Current 70 A 264VAC cold start 25°C No Load Power W 90VAC, 4 modules fitted

10 With global inhibit

Earth Leakage Current 270 μA 264VAC/60Hz Input Protection F12.5A/250 V internal fuse fitted in line and neutral

3V3 40.00A 132W 1 A Blank plate 1 B 5V 40.0A 200W 1 C 5V2 38.5A 200W 1 D 5V5 36.4A 200W 1 E 8V 20.8A 166W 1 F 10V 20.8A 208W 1 G 12V 20.8A 250W 1 H 14V 17 .9A 250W 1 I 15V 16.7A 250W 1 J 18V 12.5A 225W 1 K 20V 12.5A 250W 1 L 24V 12.5A 300W 1 M 28V 10.7A 300W 1 N 30V 10.0A 300W 1 O 33V 9.09A 300W 1 P 36V 8.33A 300W 1 Q 48V 6.25A 300W 1 R 54V 5.56A 300W 1 S 60V 5.0A 300W 1 T Parallel Option Codes Code Description -00 No parallel required -12 Parallel module 1 & 2 from right -13 Parallel modules 1 to 3 from right -14 Parallel modules 1 to 4 from right -22 Parallel module 1 & 2, 3 & 4 Option Codes Code Description A00 No options A01 Fan fail signal A02 Reverse air flow A03 Faston O/P connections A04 IEC inlet Combined Option Codes Code Description C01 A01-02 C02 A01 & 03 C03 A01 & 04 C04 A01-03 C05 A01-02 & 04 C06 A01-04 C07 A02-03 C08 A02 & 04 C09 A02-04 C10 A03-04 C11 A01 & 03 & 04 Code Slot 4 3 2 1 Modules are populated from the right, when unit is viewed from the DC module end. The modules are configured such that an output requiring the highest number of paralleled modules would go first, then the next highest and so on. Once this sequence is complete or if two outputs use paralleled modules then modules are configured lowest to highest voltage again from the right when the unit is viewed from the DC module end. AC-DC Power Supplies www.xppower.com 2 Configuration Examples Modules are populated from the right, when unit is viewed from the DC module end. The modules are configured such that an output requiring the highest number of paralleled modules would go first, then the next highest and so on. Once this sequence is complete or if two outputs use paralleled modules then modules are configured lowest to highest voltage again from the right when the unit is viewed from the DC module end. Examples 1. 5 V at 80 A, 12 V at 12 A with no options: N12-CCHB-12A00 Slot 4 3 2 1 Front End Designation Model 115 V 230 V Slots N12 850 W 1200 W 4 Module Designation Voltage VDC Current Power Slots Code 3V3 40.00 A 132 W 1 A Blank Plate 1 B 5V 40.00 A 200 W 1 C 5V2 38.50 A 200 W 1 D 5V5 36.40 A 200 W 1 E 8V 20.80 A 166 W 1 F 10V 20.80 A 208 W 1 G 12V 20.80 A 250 W 1 H 14V 17.90 A 250 W 1 I 15V 16.70 A 250 W 1 J 18V 12.50 A 225 W 1 K 20V 12.50 A 250 W 1 L 24V 12.50 A 300 W 1 M 28V 10.70 A 300 W 1 N 30V 10.00 A 300 W 1 O 33V 9.09 A 300 W 1 P 36V 8.33 A 300 W 1 Q 48V 6.25 A 300 W 1 R 54V 5.56 A 300 W 1 S 60V 5.00 A 300 W 1 T Parallel Option Codes Code Description

00 No parallel required

12 Parallel module 1 & 2 from right

13 Parallel modules 1 to 3 from right

14 Parallel modules 1 to 4 from right

22 Parallel module 1 & 2, 3 & 4

A02 Reverse air flow A03 Faston O/P connections A04 IEC inlet Combined Option Codes Code Description C01 A01-02 C02 A01 & 03 C03 A01 & 04 C04 A01-03 C05 A01-02 & 04 C06 A01-04 C07 A02-03 C08 A02 & 04 C09 A02-04 C10 A03-04 C11 A01 & A03 & A04 -N 1 2 - C C H B - 1 2N 1 2 - A 0 0 R R R M - 1 3N 1 2 - A 0 4 Code Slot 4 3 2 1 1 2 3 4 Slot DC Module End 2. 24 V at 10 A, 48 V at 18 A with optional IEC Inlet: N12-RRRM-13A04 Series DC Module End Series Examples: 1.5V at 80A, 12V at 12A with no options: N12-CCHB-12A00 Front End Designation Parallel Option Codes Options Module Designation Slot 1 2 3 4 N12- - N12- -C C H B 1 2 A 00 N12- -R R R M 1 3 A 40 24V at 10A, 48V at 18A with optional IEC Inlet: N12-RRRM-13A04

526 Jan 2022Specifications subject to change without notice. General Characteristic Minimum Typical Maximum Units Notes & Conditions Efficiency 90 % See fig. 3 & 4 Isolation: Input to Output Input to Ground Output to Ground

4000 VAC 2 x MOPP

1500 VAC 1 x MOPP

500 VDC

110 125 135 Main converter 230 250 DC output module Power Density 15 W/in3 At high line Mean Time Between Failure 690 khrs T elcordia SR-332, Issue 2, based on N12-CMHB-00-A00 configuration Weight 2.6 (1.25) lb (kg) For chassis 0.15 (0.07) Each module Series Efficiency Graphs Efficiency vs Load Figure 3 N12-HHHH-14A00 Figure 4 N12-MMMM-14A00 50% 60% 70% 80% 90% 100% 10 20 30 40 50 60 70 80 90 100 Efficiency 115VAC input 230VAC input 50% 60% 70% 80% 90% 100% 10 20 30 40 50 60 70 80 90 100 Efficiency Load (%) 115VAC input 230VAC input Load (%) 50% 60% 70% 80% 90% 100% 10 20 30 40 50 60 70 80 90 100 Efficiency 115VAC input 230VAC input 50% 60% 70% 80% 90% 100% 10 20 30 40 50 60 70 80 90 100 Efficiency Load (%) 115VAC input 230VAC input Load (%) 50% 60% 70% 80% 90% 100% 10 20 30 40 50 60 70 80 90 100 Efficiency 115VAC input 230VAC input 50% 60% 70% 80% 90% 100% 10 20 30 40 50 60 70 80 90 100 Efficiency Load (%) 115VAC input 230VAC input Load (%)

Characteristic Minimum Typical Maximum Units Notes & Conditions Operating Temperature -40 +70 °C With integral fan, derate from 100% load at 50°C to 50% load at 70°C, see derating curve Storage Temperature -40 +85 °C Humidity 95 %RH Non-condensing Operating Altitude 3048 m Acoustic Fan Noise 54 62 Lw db(A) 115VAC 850W/230VAC 1200W. Fan speed based on output load and ambient temperature Shock ±3 x 30g on each plane 30g = 11ms (±0.5ms) Half sine conforms to EN60068-2-27 and -2-47 Vibration Single axis 10 - 500 Hz at 2g sweep and endurance resonance in all 3 planes conforms to EN60068-2-6 Thermal Derating Curve Figure 5 1200 850 765 680 90 180 Input Voltage (VAC) Output Power (W) 264 100 -40- 20 50 Temperature (°C) Some specifica/g2462on parameters may not be met Load (%) 100ms 100ms 100ms3s 3s Series EMC: Emissions Phenomenon Standard T est Level Notes & Conditions Conducted EN55011/32 Class B Radiated EN55011/32 Class A Harmonic Current EN61000-3-2 Class A Harmonic Fluctuations EN61000-3-3 Class A

26 Jan 2022Specifications subject to change without notice. EMC: Immunity Phenomenon Standard T est Level Criteria Notes & Conditions Low Voltage PSU EMC EN61204-3 High severity level As below Medical Device EMC IEC60601-1-2 Ed 4.0:2014 As below ESD EN61000-4-2 4 A ±8kV contact, ±15kV Air Radiated EN61000-4-3 3 A EFT EN61000-4-4 3 A Surge EN61000-4-5 Installation class 3 A Conducted EN61000-4-6 3 A Magnetic Fields EN61000-4-8 4 A Dips and Interruptions EN55024 (100VAC) Int >95% (0VAC) 8.3ms A Dip 30% (70VAC) 416ms A Int >95% (0VAC) 4160ms B EN55024 (240VAC) Int >95% (0 VAC) 10ms A Dip 30% (168VAC) 500ms A Int >95% (0VAC) 5000ms B EN60601-1-2 (100VAC) Int 100% (0VAC) 10ms A Int 100% (0VAC) 20ms B Dip 60% (40VAC) 100ms A Dip 30% (70VAC) 500ms A Int 100% (0VAC) 5000ms B EN60601-1-2 (240VAC) Int 100% (0VAC) 10ms A Dip 60% (96VAC) 100ms A Int 100% (0VAC) 20 ms B Dip 30% (168VAC) 500 ms A Int 100% (0VAC) 5000ms B Safety Approvals Certification Standard Notes & Conditions CB IEC62368-1 Information T echnology IEC60601-1 Medical UL UL 62368-1 Information T echnology ANSI/AAMI ES60601-1 +CSA C22.2 No.60601-1:08 Medical TUV EN62368-1 Information T echnology EN60601-1 Medical CE Meets all applicable directives UKCA Meets all applicable legislation Equipment Protection Class Class I Means of Protection Category Primary to Secondary 2 x MOPP IEC60601-1 Ed 3.1 Primary to Earth 1 x MOPP Series

Application Notes: Modules Modules: A, C, D & E Output Module Signal Connector

10 Pos

2 P_Sync

3 I_Share

4 I_Share

5 V_Prog

7 DCOK_C

8 DCOK_E

9 INH

10 INH_RTN

0.26 (6.6) 0.35 (8.9) 0.31 (8.0) 0.76 (19.3) 0.68 (17.3) 0.64 (16.3) VOLTAGE SIGNAL CONNECTOR ADJUST M3X0.5 THD OUTPUT HARDWARE TORQUE 8-9 IN-LB (0.9-1.0 N-m) .31 (7.9) 0.31 (8.0) 0.76 (19.3) 0.68 (17.3) 0.64 (16.3) VOLTAGE ADJUST M3X0.5 THD OUTPUT HARDWARE TORQUE 8-9 IN-LB (0.9-1.0 N-m) 5V (C) MODULE 12V (H), 24V (M), 48V (R) MODULE 0.26 (6.6) 0.35 (8.9) 0.31 (8.0) 0.76 (19.3) 0.68 (17.3) 0.64 (16.3) VOLTAGE SIGNAL CONNECTOR ADJUST M3X0.5 THD OUTPUT HARDWARE TORQUE 8-9 IN-LB (0.9-1.0 N-m) .31 (7.9) 0.31 (8.0) 0.76 (19.3) 0.68 (17.3) 0.64 (16.3) VOLTAGE ADJUST M3X0.5 THD OUTPUT HARDWARE TORQUE 8-9 IN-LB (0.9-1.0 N-m) 5V (C) MODULE 12V (H), 24V (M), 48V (R) MODULE Series Output Module Signal Connector

Application Notes: Analogue Signals 926 Jan 2022Specifications subject to change without notice. Global AC OK/Power Fail Global AC OK is an isolated transistor of an optocoupler providing a minimum of 5ms warning of loss of output regulation. The signal is fully isolated and the collector and emitter must be connected externally. Maximum sink current 2mA, maximum voltage 60V. AC OK_C (C ollecto r) Pin 12 AC OK_E (E mi/g130e r) Pin 11 PO WER SUPPL Y Tr ansistor On (<0.8V): AC NO T OK Tr ansistor Off (>4.5V): AC OK Global Inhibit Pin 15 PO WER SUPPL Y 100R M odule 1 Pin 2 Pin 3 or 4 M odule 2 Pin 2 Pin 3 or 4 M odule 4 Pin 2 Pin 3 or 4 Chassis Lo gic Connecto r Chassis Lo gic Connecto r Global Inhibit Re turn Pin 13 3300R 5V St andb y Re turn Pin 17, 18 5V St andb y Re turn Pin 17, 18 5V St andb y Pin 19, 20 DC OK_C (C ollector ) Pin 16 DC OK_E (E mi/g130e r) Pin 14 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK Chassis Lo gic Connecto r 3300R 5V St andb y Pin 19, 20 5V St andb y Pin 19, 20 5V St andb y Re turn Pin 17, 18 St andar d Lo gic 0 0V or Floa/g2462ng: Po we r Suppl y On 2-5mA: Po we r Suppl y Off 800R 2-5m A M odule DC OK_C (C ollecto r) Pin 7 M odule DC OK _E (E mi/g130e r) Pin 8 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK M odule Lo gic Connecto r 3300R +5V M odule Inhibit Pin 9 PO WER SUPPL Y 1KΩ M odule Lo gic Connecto r M odule Inhibit Re turn Pin 10 0V or Floa/g2462ng: M odule On 2-5mA: M odule Off 2-5m A +5V Global DC OK Global DC OK is an isolated transistor of an optocoupler providing warning that the output voltage has fallen below 90% of nominal. The signal is fully isolated and the collector and emitter must be connected externally. Maximum sink current 2mA, maximum voltage 60V. On Dual output module, DC OK monitors V1 output only. AC OK_C (C ollecto r) Pin 12 AC OK_E (E mi/g130e r) Pin 11 PO WER SUPPL Y Tr ansistor On (<0.8V): AC NO T OK Tr ansistor Off (>4.5V): AC OK Global Inhibit Pin 15 PO WER SUPPL Y 100R M odule 1 Pin 2 Pin 3 or 4 M odule 2 Pin 2 Pin 3 or 4 M odule 4 Pin 2 Pin 3 or 4 Chassis Lo gic Connecto r Chassis Lo gic Connecto r Global Inhibit Re turn Pin 13 3300R 5V St andb y Re turn Pin 17, 18 5V St andb y Re turn Pin 17, 18 5V St andb y Pin 19, 20 DC OK_C (C ollector ) Pin 16 DC OK_E (E mi/g130e r) Pin 14 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK Chassis Lo gic Connecto r 3300R 5V St andb y Pin 19, 20 5V St andb y Pin 19, 20 5V St andb y Re turn Pin 17, 18 St andar d Lo gic 0 0V or Floa/g2462ng: Po we r Suppl y On 2-5mA: Po we r Suppl y Off 800R 2-5m A M odule DC OK_C (C ollecto r) Pin 7 M odule DC OK _E (E mi/g130e r) Pin 8 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK M odule Lo gic Connecto r 3300R +5V M odule Inhibit Pin 9 PO WER SUPPL Y 1KΩ M odule Lo gic Connecto r M odule Inhibit Re turn Pin 10 0V or Floa/g2462ng: M odule On 2-5mA: M odule Off 2-5m A +5V Global Inhibit Global Inhibit is an isolated control signal input which turns the power supply off by supplying 2 to 5mA into the pin. AC OK_C (C ollecto r) Pin 12 AC OK_E (E mi/g130e r) Pin 11 PO WER SUPPL Y Tr ansistor On (<0.8V): AC NO T OK Tr ansistor Off (>4.5V): AC OK Global Inhibit Pin 15 PO WER SUPPL Y 100R M odule 1 Pin 2 Pin 3 or 4 M odule 2 Pin 2 Pin 3 or 4 M odule 4 Pin 2 Pin 3 or 4 Chassis Lo gic Connecto r Chassis Lo gic Connecto r Global Inhibit Re turn Pin 13 3300R 5V St andb y Re turn Pin 17, 18 5V St andb y Re turn Pin 17, 18 5V St andb y Pin 19, 20 DC OK_C (C ollector ) Pin 16 DC OK_E (E mi/g130e r) Pin 14 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK Chassis Lo gic Connecto r 3300R 5V St andb y Pin 19, 20 5V St andb y Pin 19, 20 5V St andb y Re turn Pin 17, 18 St andar d Lo gic 0 0V or Floa/g2462ng: Po we r Suppl y On 2-5mA: Po we r Suppl y Off 800R 2-5m A M odule DC OK_C (C ollecto r) Pin 7 M odule DC OK _E (E mi/g130e r) Pin 8 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK M odule Lo gic Connecto r 3300R +5V M odule Inhibit Pin 9 PO WER SUPPL Y 1KΩ M odule Lo gic Connecto r M odule Inhibit Re turn Pin 10 0V or Floa/g2462ng: M odule On 2-5mA: M odule Off 2-5m A +5V Module Inhibit Module Inhibit signal is an isolated control signal which turns the module off by supplying 2 to 5mA into the pin. AC OK_C (C ollecto r) Pin 12 AC OK_E (E mi/g130e r) Pin 11 PO WER SUPPL Y Tr ansistor On (<0.8V): AC NO T OK Tr ansistor Off (>4.5V): AC OK Global Inhibit Pin 15 PO WER SUPPL Y 100R M odule 1 Pin 2 Pin 3 or 4 M odule 2 Pin 2 Pin 3 or 4 M odule 4 Pin 2 Pin 3 or 4 Chassis Lo gic Connecto r Chassis Lo gic Connecto r Global Inhibit Re turn Pin 13 3300R 5V St andb y Re turn Pin 17, 18 5V St andb y Re turn Pin 17, 18 5V St andb y Pin 19, 20 DC OK_C (C ollector ) Pin 16 DC OK_E (E mi/g130e r) Pin 14 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK Chassis Lo gic Connecto r 3300R 5V St andb y Pin 19, 20 5V St andb y Pin 19, 20 5V St andb y Re turn Pin 17, 18 St andar d Lo gic 0 0V or Floa/g2462ng: Po we r Suppl y On 2-5mA: Po we r Suppl y Off 800R 2-5m A M odule DC OK_C (C ollecto r) Pin 7 M odule DC OK _E (E mi/g130e r) Pin 8 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK M odule Lo gic Connecto r 3300R +5V M odule Inhibit Pin 9 PO WER SUPPL Y 1KΩ M odule Lo gic Connecto r M odule Inhibit Re turn Pin 10 0V or Floa/g2462ng: M odule On 2-5mA: M odule Off 2-5m A +5V Module DC OK Module DC OK is a nominal “ON” isolated transistor of an optocoupler which provides a warning of the loss of output regulation on the main output of the module. Maximum sink current 2mA, maximum voltage 60V. AC OK_C (C ollecto r) Pin 12 AC OK_E (E mi/g130e r) Pin 11 PO WER SUPPL Y Tr ansistor On (<0.8V): AC NO T OK Tr ansistor Off (>4.5V): AC OK Global Inhibit Pin 15 PO WER SUPPL Y 100R M odule 1 Pin 2 Pin 3 or 4 M odule 2 Pin 2 Pin 3 or 4 M odule 4 Pin 2 Pin 3 or 4 Chassis Lo gic Connecto r Chassis Lo gic Connecto r Global Inhibit Re turn Pin 13 3300R 5V St andb y Re turn Pin 17, 18 5V St andb y Re turn Pin 17, 18 5V St andb y Pin 19, 20 DC OK_C (C ollector ) Pin 16 DC OK_E (E mi/g130e r) Pin 14 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK Chassis Lo gic Connecto r 3300R 5V St andb y Pin 19, 20 5V St andb y Pin 19, 20 5V St andb y Re turn Pin 17, 18 St andar d Lo gic 0 0V or Floa/g2462ng: Po we r Suppl y On 2-5mA: Po we r Suppl y Off 800R 2-5m A M odule DC OK_C (C ollecto r) Pin 7 M odule DC OK _E (E mi/g130e r) Pin 8 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK M odule Lo gic Connecto r 3300R +5V M odule Inhibit Pin 9 PO WER SUPPL Y 1KΩ M odule Lo gic Connecto r M odule Inhibit Re turn Pin 10 0V or Floa/g2462ng: M odule On 2-5mA: M odule Off 2-5m A +5V Current Share Connecting pins 3 and 4 of like voltage modules (4 maximum) within the same chassis will force the current to share between the outputs. For paralleling modules in separate chassis, connect pin 2 to pin 2 and pin 8 to pin 8 of the chassis logic signal connector, J2. AC OK_C (C ollecto r) Pin 12 AC OK_E (E mi/g130e r) Pin 11 PO WER SUPPL Y Tr ansistor On (<0.8V): AC NO T OK Tr ansistor Off (>4.5V): AC OK Global Inhibit Pin 15 PO WER SUPPL Y 100R M odule 1 Pin 2 Pin 3 or 4 M odule 2 Pin 2 Pin 3 or 4 M odule 4 Pin 2 Pin 3 or 4 Chassis Lo gic Connecto r Chassis Lo gic Connecto r Global Inhibit Re turn Pin 13 3300R 5V St andb y Re turn Pin 17, 18 5V St andb y Re turn Pin 17, 18 5V St andb y Pin 19, 20 DC OK_C (C ollector ) Pin 16 DC OK_E (E mi/g130e r) Pin 14 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK Chassis Lo gic Connecto r 3300R 5V St andb y Pin 19, 20 5V St andb y Pin 19, 20 5V St andb y Re turn Pin 17, 18 St andar d Lo gic 0 0V or Floa/g2462ng: Po we r Suppl y On 2-5mA: Po we r Suppl y Off 800R 2-5m A M odule DC OK_C (C ollecto r) Pin 7 M odule DC OK _E (E mi/g130e r) Pin 8 PO WER SUPPL Y Tr ansistor On (<0.8V): DC OK Tr ansistor Off (>4.5V): DC NO T OK M odule Lo gic Connecto r 3300R +5V M odule Inhibit Pin 9 PO WER SUPPL Y 1KΩ M odule Lo gic Connecto r M odule Inhibit Re turn Pin 10 0V or Floa/g2462ng: M odule On 2-5mA: M odule Off 2-5m A +5V Series

  1. All dimensions in inches (mm). 3. Weight: With 1 module: 2.75lbs (1.25kg) With 2 modules: 2.90lbs (1.32kg) With 3 modules: 3.05lbs (1.38kg) With 4 modules: 3.20lbs (1.45kg) Notes:

16 Mar 2022

N12 with Standard Barrier Input T erminal AIRF LOW L G N 0.18 (4.4) 0.52 (13.3) AC Input terminal block M3 hardware, 0.300 centres 0.37 (9.5) 11.00 (279.4) 11.35 (288.3) 1.67 (42.2) 1.25 (31.7) 1.00 (25.4) 4.20 (106.7) 0.25 (6.4) 3.70 (94.0) 0.18 (4.4) 0.23 (5.8) 11.0 (279.4) 11.5 (292.0) 10.0 (254.0) Configura/g2462on label 2 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on 4 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on Max. torque 10 lb-in 2X M3 PEM NUT 0.16(4.0) max. Screw Penetra/g2462on Signal connector (modules) P/N: JST P/N S10B-PHDSS Ma/g2462ng part: JST PHDR-10VS Contact: SPHD-002T-P0.5 Logic Connector P/N: JST P/N S20B-PHDSS Ma/g2462ng Part: JST PHDR-20VS Contact: SPHD-002T-P0.5

5 V Module shown

M3 x 0.5 screw Max torque 7lb-in Voltage Adjust. typ. Pin 1 Pin 1 Blank Panel shown 0.65 (16.5) 0.25 (6.3) 0.250X 0.82 Faston tab op/g2462on N12 with Optional Faston Output (A03) AIRF LOW L G N 0.18 (4.4) 0.52 (13.3) AC Input terminal block M3 hardware, 0.300 centres 0.37 (9.5) 11.00 (279.4) 11.35 (288.3) 1.67 (42.2) 1.25 (31.7) 1.00 (25.4) 4.20 (106.7) 0.25 (6.4) 3.70 (94.0) 0.18 (4.4) 0.23 (5.8) 11.0 (279.4) 11.5 (292.0) 10.0 (254.0) Configura/g2462on label 2 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on 4 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on Max. torque 10 lb-in 2X M3 PEM NUT 0.16(4.0) max. Screw Penetra/g2462on Signal connector (modules) P/N: JST P/N S10B-PHDSS Ma/g2462ng part: JST PHDR-10VS Contact: SPHD-002T-P0.5 Logic Connector P/N: JST P/N S20B-PHDSS Ma/g2462ng Part: JST PHDR-20VS Contact: SPHD-002T-P0.5 M3 x 0.5 screw Max torque 7lb-in Voltage Adjust. typ. Pin 1 Pin 1 Blank Panel shown 0.65 (16.5) 0.25 (6.3) 0.250X 0.82 Faston tab op/g2462on Chassis Logic Signal Connector J2 Logic BD Connector Pin Function Pin Function

1 SCL_USER 11 GL_ACOK_E

2 GINH_SHARE 12 GL_ACOK_C

3 SDA_USER 13 GL_INH_RTN

4 I2C_A2 14 GL_DCOK_E

5 I2C_A0 15 GL_INH

6 NC 16 GL_DCOK_C

7 I2C_A1 17 5V_SB_RTN

8 GND 18 5V_SB_RTN

9 NC 19 5V_SB

10 NC 20 5V_SB

  1. All dimensions in inches (mm). 3. Weight: With 1 module: 2.75lbs (1.25kg) With 2 modules: 2.90lbs (1.32kg) With 3 modules: 3.05lbs (1.38kg) With 4 modules: 3.20lbs (1.45kg) Notes: N12 with Optional IEC320 Input T erminal (A04) AIRF LOW 11.0 (279.4) 11.64 (295.7) 1.0 (25.4) 4.2 (106.7) 1.00 (25.4) Configura/g2462on Label 0.18 (4.4) 2 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on 4 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on Max. torque 10lb-in Signal connector (modules) P/N: JST P/N S10B-PHDSS Ma/g2462ng part: JST PHDR-10VS Contact: SPHD-002T-P0.5 Logic Connector P/N: JST P/N S20B-PHDSS Ma/g2462ng Part: JST PHDR-20VS Contact: SPHD-002T-P0.5 5V Module shown M3 x 0.5 screw Max. torque 7lb-in Voltage Adjust. typ. Blank Panel shown AC Input IEC Inlet C14 with retainer clip 1.25 (31.8) 0.18 (4.4) 0.25 (6.4) 0.23 (5.8) 3.7 (94.0) 11.0 (279.4) 11.5 (292.0) 10.0 (254.0) Retainer clip 0.65 (16.5) 0.25 (6.3) 4.2 (106.7) Pin 1 Pin 1 2X M3 PEM NUT 0.16(4.0) max. Screw Penetra/g2462on N12 with Combined Optional IEC Inlet and Faston Output (C10) AIRF LOW L G N 0.18 (4.4) 0.52 (13.3) AC Input terminal block M3 hardware, 0.300 centres 0.37 (9.5) 11.00 (279.4) 11.35 (288.3) 1.67 (42.2) 1.25 (31.7) 1.00 (25.4) 4.20 (106.7) 0.25 (6.4) 3.70 (94.0) 0.18 (4.4) 0.23 (5.8) 11.0 (279.4) 11.5 (292.0) 10.0 (254.0) Configura/g2462on label 2 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on 4 x M3 PEM NUT 0.16 (4.0) max. screw penetra/g2462on Max. torque 10 lb-in 2X M3 PEM NUT 0.16(4.0) max. Screw Penetra/g2462on Signal connector (modules) P/N: JST P/N S10B-PHDSS Ma/g2462ng part: JST PHDR-10VS Contact: SPHD-002T-P0.5 Logic Connector P/N: JST P/N S20B-PHDSS Ma/g2462ng Part: JST PHDR-20VS Contact: SPHD-002T-P0.5

M3 x 0.5 screw Max torque 7lb-in Voltage Adjust. typ. Pin 1 Pin 1 Blank Panel shown 0.65 (16.5) 0.25 (6.3) 0.250X 0.82 Faston tab op/g2462on Chassis Logic Signal Connector PCB PCB PIN 1 PIN 10 PIN 1 PIN 20 1126 Jan 2022Specifications subject to change without notice. Series J2 Logic BD Connector Pin Function Pin Function

Signals & Controls

16 Jun 2023

Name Global, On Chassis Local On Module Description AC OK • • Global AC OK is an isolated transistor of an optocoupler providing a minimum of 5ms warning of loss of output regulation. The signal is fully isolated and the collector and emitter must be connected externally. Maximum sink current 2mA. Maximum voltage 60V . DC OK • • Global DC OK is an isolated transistor of an optocoupler providing warning that the output voltage has fallen below 90% of nominal. The signal is fully isolated and the collector and emitter must be connected externally. Maximum sink current 2mA. Maximum voltage 60 V.

  • • Module DC OK is a nominal ‘ON’ isolated transistor of an optocoupler which provides a warning of loss of output regulation on the main output module. Maximum sink current 2mA. Maximum voltage 60V. Inhibit • • Global inhibit is an isolated control signal input which turns the power supply off by supplying 2 to 5mA into the pin.
  • • Module inhibit signal is an isolated control signal which turns the module off by supplying 2 to 5mA into the pin. Voltage Program • • Non-isolated analogue input, referenced to the module -Sense, pin 1. 0VDC - 5VDC input will program the module over the range shown in the module table. Current Share • • Connecting pins 3 and 4 of like voltage modules (4 maximum) will force the current to share between the outputs. Name Description Select Module (PAGE) Each module can be addressed individually via this PMBus commands. On/Off (OPERATION) The command will turn off or turn on the selected module. Voltage Program (VOUT_COMMAND) The command will set the output voltage of the selected module. If multiple modules are connected in parallel, this command will be applied to all paralleled modules. Maximum Voltage Level (VOUT_MAX) This command will set an upper limit of the selected output module voltage. If a voltage is programmed via Voltage Program (VOUT_COMMAND) above to be higher than VOUT max. This maximum voltage level will take priority and limit the voltage to this set level. If multiple modules are connected in parallel, this command will be applied to all paralleled modules. Overvoltage Alarm Set Point (VOUT_OV_FAULT_LIMIT) The command will set the selected module’s voltage threshold value such that any measured output voltage above this threshold will signal a fault. If multiple modules are connected in parallel, this command will be applied to all paralleled modules. OCP Set Point (IOUT_OC_FAULT_LIMIT) The command will set the selected module’s current threshold value such that any measured output current above this threshold will signal a fault. If multiple modules are connected in parallel, this command will be applied to all paralleled modules. Output Voltage Readback (READ_VOUT) This command will return the actual measured output voltage value of the selected module. Output Current Readback (READ_IOUT) This command will return the actual measured current voltage value of the selected module. Unit Temp Readback (READ_TEMPERATURE1) This command will return the actual measured highest temperature value from the various monitored points. XP Power Readback (MFR_ID) This command will return the XP Power name as the manufacturer. Stock Key Readback (MFR_MODEL) This command will return the STOCK KEY of the product and not the model number. This assumes the product has been configured by XP Power and not via distribution. Combined Fault Alarm (STATUS_MFR_SPECIFIC) OCP , SCP , OTP , UVP , OVP Output Overvoltage Warning (STATUS_VOUT) This command will signal 3 different output voltage faults. Vout >10% warning of Vprogram, Vout >15% fault of Vprogram & when a voltage is programmed greater than the overvoltage set point. Output Over Current Warning (STATUS_IOUT) OC Fault & Warning Over Temp Warning (STATUS_TEMPERATURE) OT Fault & Warning as set by OT_Fault and OT_Warn. Fan Fail (Optional) (STATUS_FAN_1_2) This command will signal 2 different fan fail conditions when the 3 wire fan option has been selected. Fan speed below 3000RPM fault expected speed and below 5000RPM warning expected speed. Series