MSR10D ALLEN-BRADLEY | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
Features
- Category 3 per EN 954-1
- Stop category 0 and 1
- 2 N.C. dual channel input
- 8 N.O. instantaneous safety outputs
- 1 N.C. instantaneous auxiliary output
- 1 N.O. delayed safety output
- 1 N.C. delayed auxiliary output
- Automatic/manual or monitored manual reset
- 152mm wide housing Specifications ➊ See Output Ratings on page 1-29 for details. Consult factory for ratings not shown. Standards EN 954-1, ISO 13849-1, IEC/EN 60204-1, IEC 60947-4-1, IEC 60947-5-1, ANSI B11.19, AS4024.1 Category Cat. 3 per EN 954-1 (ISO 13849-1) Approvals C-Tick, CE marked for all applicable directives and cULus Power Supply 24V AC/DC and 110/230V AC Power Consumption <4VA Safety Inputs 2 N.C. Input Simultaneity 0.5s Maximum Input Resistance 500 Ω Reset Monitored Manual or Auto./Manual Outputs 8 N.O. Safety Instantaneous 1 N.O. Safety delayed 0.1 to 10s 1 N.C. Auxiliary Instantaneous 1 N.C. Auxiliary delayed 0.1 to 10s ➊ Output Utilization per IEC 60947-5-1 (Inductive) B300, AC-15 4A/250V AC, 4A/125V AC P300, DC-13 3A/24V DC Thermal Current (non switching) 4A Fuses Input (internal, replace.) Output (external) 500mA time lag 5A quick acting Min. Switched Current/Voltage 10mA/10V Maximum Dropout Time 50ms instantaneous Indication LEDs Red = Power On Green = K1 Closed Green = K2 Closed Green = Off Delay Closed Impulse Withstand Voltage 2500V Installation Group C in accordance with VDE 0110 Pollution Degree 3 Operating T emperature -10°C to +55°C (+14°F to +131°F) Humidity 90% RH Enclosure Protection IP40, (NEMA 1), DIN 0470 T erminal Protection IP20, DIN 0470 Conductor Size 1 x 2.5mm 2 (14AWG) stranded, 1 x 4mm2 (12AWG) solid T orque Settings—term. screws 1N⋅m (8.85lb⋅in) Case Material Red Polycarbonate Mounting 35mm DIN rail Weight 1054g (2.32lbs) Electrical Life 220V AC/4A/880VA cosϕ=0.35 220V AC/1.7A/375VA cosϕ=0.6 30V DC/2A/60W 10V DC/0.01A/0.1W 100,000 operations 500,000 operations 1,000,000 operations 2,000,000 operations Mechanical Life 2,000,000 operations Vibration 0.75mm (0.30in) peak, 10-55Hz Shock 30g, 11ms half sine
Monitoring Safety Relays with Delayed Outputs Minotaur MSR10D Product Selection Accessories Dimensions—mm (inches) Block Diagram Typical Wiring Diagrams Application Details Inputs Safety Outputs Auxiliary Outputs Reset Delayed Timing Catalogue Number 2 N.C. 8 N.O. Instantaneous 1 N.O. Delayed 1 N.C. Instantaneous 1 N.C. Delayed Monitored Manual 0.1 to 10s 440R-G23029 Automatic/Manual 1 second fixed delay 440R-G23067 0.5 second fixed delay 440R-G23068 Description Page Number Catalogue Number 500mA Fuse 14-6 440R-A31562 A2 X2 S13 S14A1 34 44 33 43 D21 D2214 24 13 23 74 84 73 83 D14 D13 54 64 53 63 91 K3 K3 K5 K8K6K6 S24 F1 24V DC S23 K10 VR1 K10 K3 K4 K5 K6 K7 K8 K3K2 K6K2 K4 K4 K9 K7 K7 K10 110/ 230 118.2 (4.65) 35mm DIN Rail Mounting 152 (5.98) 73 (2.87) Timer A2 X2 S13 S14 A1 34 44 33 43 D21 D2214 24 13 23 74 84 73 83 D14 D13 54 64 53 63 91 S24S23 M L N 12 22 34 11 21 33 54A1 Guard Closed & Unlocked TLS2-GD2 Stop MSR10RD Aux Aux Reset Dual Channel Guardlocking Safety Gate, Delayed Gate Release, Manual Reset, Dual Channel Output, Monitored Output Replaceable Fuse 230V AC 110V ACVoltage Selector Switch Timing Potentiometer Fully CCW Maximum 10s Fully CW Minimum 0s