Datasheet search site | www.alldatasheet.com

Document overview

  • Manufacturer or author: Rockwell Automation
  • PDF pages: 114

Technical content

IEC Contactor Specifications Bulletin Numbers 100/104-K, 100/104-C, 100/104S-C, 100/104-E, 100S-E, 100Q-C Topic Page Summary of Changes 2 Product Line Overview 3 IEC Contactors 3 Safety Contactors 4 100-K/104-K Miniature Contactors 5 Product Selection 5 Accessories 8 Specifications 11 Life-Load Curves 15 Approximate Dimensions 16 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors 17 Product Selection—100-C/104-C Contactors 17 Product Selection—100S-C/104S-C Safety Contactors 22 Product Selection—100Q-C Capacitor-switching Contactors 30 Accessories 31 Renewal Parts 36 Specifications 38 Life-Load Curves 49 Approximate Dimensions 56 100-E/104-E, 100S-E/104S-E Contactors 59 Product Selection—100-E/104-E Contactors 59 Product Selection—100S-E Safety Contactors 62 Accessories 66 Renewal Parts 73 Specifications 75 Life-Load Curves 96 Approximate Dimensions 101 Additional Resources 113

2 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes. Topic Page Corrected pkg. qty. for mechanical interlocks 68 Corrected Cat. Nos. for mechanical latches 69

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 3 Product Line Overview IEC Contactors Bulletin No. 100-K/104-K 100-C/104-C 100-E/104-E Screw Terminals   (9…96 A), Thru-hole (116…2650 A) Spring Terminals (5…9 A)  (9…16 A) — Max.Current Ie 12 A 97 A 2650 A Current Rating 5…12 A9 …97 A 9 …2650 A

Features

  • Mini-contactors
  • Uniform panel mounting dimensions
  • Panel mounting or mounting on 35 mm DIN Rail
  • AC or DC coil control
  • Made of environmentally friendly materials
  • Panel mounting or mounting on 35 mm DIN Rail
  • AC or DC coil control
  • Reversible coil terminals (line or load side)
  • Common accessories
  • Made of environmentally friendly materials
  • Panel mounting or mounting on 35 mm DIN Rail
  • E09…E370 AC/DC electronic coil; with optional PLC interface on E116…E370 E400…E2650 AC/DC with PLC interface
  • Made of environmentally friendly materials Contacts
  • 3 power poles with internal N.O. or N.C. auxiliary contact, or 4 power poles.
  • Optional front-mounted 2- or 4-pole external auxiliary contact block.
  • 3 power poles with internal N.O. or N.C. auxiliary contact or 4 power poles (9…23 A).
  • Optional front- or side-mounted 1-, 2- or 4-pole external auxiliary contact block.
  • 3 main poles with 2 auxiliary contacts (1 N.O. and 1 N.C.) on E116…E2650
  • Optional side- or front-mounted external auxiliary contact block. Coil Voltages AC = 24…600V, 50/60Hz DC = 12…250V AC = 12…600V, 50/60Hz DC = 9…250V 20…500V 50/60 Hz/DC Optional Overload Relays Electronic or bimetallic Electronic or bimetallic Electronic Optional Accessories
  • Front-mount auxiliary contacts
  • Surge suppressors
  • Electronic timers
  • Mechanical interlocks
  • Front or side-mount auxiliary contacts
  • Surge suppressors
  • Electronic or pneumatic timers
  • Mechanical interlocks
  • Mechanical latches
  • Side- or front-mount auxiliary contacts
  • Mechanical interlocks
  • Terminal lugs
  • Terminal shields
  • C o n n e c t i n g b a r s Standards/ Certifications
  • U L
  • C S A
  • I E C
  • C E M a r k e d
  • CCC
  • U L
  • C S A
  • I E C
  • C E M a r k e d
  • C C C
  • E N / I E C
  • C E M a r k e d
  • c U L u s
  • CCC
  • E A C
  • C - t i c k
  • K C

4 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

Product Line Overview Safety Contactors Safety Contactors Bulletin No. 100S-C/104S-C 100S-E Screw Terminals 3 Thru-hole Max.Current Ie 97 A 750 A Current Rating 9…97 A 9…750 A

  • Positively guided/mechanically linked auxiliary contacts
  • Front-mounted auxiliary contacts: –P e r m a n e n t l y f i x e d – Protective cover to prevent manual operation – Red contact housing for easy identification – Incorporates IEC 947-5-1 “Mechanically Linked” symbol – Optional gold-plated bifurcated versions
  • AC and DC operating coils
  • SUVA third-party certification
  • Mirror contact performance on auxiliary contacts
  • Red N.C. low-power auxiliary cont acts used for feedback circuit
  • SUVA third-party certification
  • AC/ DC operating coils
  • "Mirror Contact" symbol on front Contacts 3 main poles with N.C. mechanically linked or mirror feedback contacts 3 main poles with N.C. mirror feedback contacts Coil Voltages AC = 12…600V, 50/60Hz DC = 12…250V 20…500V 50/60 Hz/DC Optional Accessories
  • Side-mount auxiliary contacts
  • Surge suppressors
  • Electronic timers
  • Mechanical interlocks
  • Side-mount auxiliary contacts
  • Terminal shields
  • Terminal lugs
  • Terminal enlargements
  • Terminal extensions
  • Connection bars for 140G molded case circuit breakers, 140MG motor protection circuit breakers, and 140MG motor circuit protectors Standards Compliance
  • EN/IEC 60947-4
  • IEC 60947-5-1 Annex L — Mechanically Linked Contacts
  • IEC 60947-4-1 Annex H — Mirror Contacts
  • U L 5 0 8
  • CSA C22.2 No. 14
  • E N 5 0 2 0 5
  • EN/IEC 60947-4-1
  • IEC 60947-4-1, Annex F — Mirror Contacts
  • U L 6 0 9 4 7 - 4 - 1
  • CSA C22.2, No. 60947-4-1 Certifications
  • cULus Listed (File No. E3125; Guide NLDX, NLDX7)
  • SUVA Third-Party Certified
  • C E M a r k e d
  • cULus Listed (File No. E4 1850; Guide No. NLDX, NLDX7)
  • C E M a r k e d
  • CCC
  • U L
  • C S A
  • E A C
  • R C M ( C - t i c k )
  • SUVA Third-Party Certified
  • K C

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 5 100-K/104-K Miniature Contactors Product Selection

  • 3-Pole AC- and DC-operated contactors
  • Compact size
  • Same dimensions for AC and DC
  • Full-voltage non-reversing and reversing contactors
  • 5, 9, and 12 A contactors rated at 690V
  • IP2X finger protection
  • Optional integrated surge suppressor
  • Compatible with Bulletin 193-K bimetallic overload relay
  • Mirror contacts per IEC 60947-4-1 and mechanically linked contacts per IEC 60947-5-1 on main unit Bulletin 100-K miniature contactors are designed for commercial and light industrial applications where panel space is at a premium. These miniature devices, while 45 mm wide, are shallower and have less panel depth requirements than standard IEC contactors. The miniature contactors have been designed with flexibility in mind. They are available with AC or DC operating coils, several contact ratings, and optional 2- or 4-pole adder decks in a variety of auxiliary contact configurations.  Coil voltage code — see page 6. 3-Pole AC- and DC-operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts Pkg. Qty.(1) (1) May be ordered in package quantities of 20. Ad d letter M to the end of the cat. no. Example: 100-K09ZJ10M. Cat. No.3-phase kW (50 Hz) Hp (60 Hz) 40 °C (104 °F) 230V 400/415V 500V 690V 1-Phase 3-Phase AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C. Screw Terminals 5 20 1.5 2.2 2.2 2.2 1/2 1 1-1/2 1-1/2 3 3 10 1 100-K0510 01 1 100-K0501 9 20 3 4 4 4 1/2 1-1/2 2 2 5 5 10 1 100-K0910 01 1 100-K0901 12 20 3 5.5 5.5 5.5 3/4 2 3 3 7-1/2 7-1/2 10 1 100-K1210 01 1 100-K1201 Spring Clamp Terminals 5 10 1.5 2.2 2.2 2.2 1/3 3/4 1-1/2 1-1/2 3 3 10 1 100-KR0510 01 1 100-KR0501 91 0 2 . 2 4 4 4 1 / 3 1 2 2 5 5 10 1 100-KR0910 01 1 100-KR0901 100-K Miniature Contactor 104-K Reversing Miniature Contactor

6 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Product Selection Coil Voltage Codes 4-Pole AC- and DC-operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Contact Configuration, Main Poles Pkg. Qty.(1) (1) May be ordered in package quantities of 20. Ad d letter M to the end of the cat. no. Example: 100-K09ZJ400M. Cat. No.3-phase kW (50 Hz) Hp (60 Hz) 40 °C (104 °F) 230V 400/ 415V 500V 690V 1-Phase 3-Phase AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C. 5 20 1.5 2.2 2.2 2.2 1/2 1 1-1/2 1-1/2 3 3 401 100-K05400 311 100-K05300 221 100-K05200 9 20 3 4 4 4 1/2 1-1/2 2 2 5 5 401 100-K09400 311 100-K09300 221 100-K09200 12 20 3 5.5 5.5 5.5 3/4 2 3 3 7-1/2 7-1/2 401 100-K12400 311 100-K12300 221 100-K12200 Reversing AC- and DC-operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts per Contactor(1) (1) Used for electrical interlocking Cat. No.(2) (2) Bulletin 104-K reversing contactors are factory assembled and include contactors, mechanical interlock (Cat. No. 100-KMCH) and wiring kit (Cat. No. 100-KPR) for power and control circuit (electrical interlock). 3-phase kW (50 Hz) Hp (60 Hz) 40 °C (104 °F) 230V 400/415V 500V 690V 1-Phase 3-Phase AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C. 5 20 1.5 2.2 2.2 2.2 — — 1-1/2 1-1/2 3 3 0 1 104-K0502 9 2 0 3 4 44— —2255 0 1 104-K0902 12 20 3 5.5 5.5 5.5 — — 3 3 7-1/2 7-1/2 0 1 104-K1202 Screw type terminal versions AC Voltages [V] 24 110 120 230 240 400 480 600 DC Voltages [V] 12 24 110 125 220 250

50 Hz — D — — — — — — Standard ZQ ZJ ZD ZS ZA ZT

60 Hz — — D — — — B VC with Integrated Diode — DJ — — — —

50/60 Hz KJ — — KF KA KN — — Spring clamp type terminal versions AC Voltages [V] 24 110 120 230 DC Voltages [V] 24 110

50 Hz — D — — Standard ZJ ZD

60 Hz — — D — with Integrated Diode DJ —

50/60 Hz KJ — — KF

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 7 100-K/104-K Miniature Contactors Product Selection Assignment of Contacts Table valid for: AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C (-13…140 °F), normal position (horizontal rail mounting) Device Combinations in Accordance with IEC 60947-1 / -4-1 Auxiliary Contact Blocks(1) 100-K Miniature Contactors (AC and DC Control) Circuit Diagram Control 100-K0510 100-K0910 100-K1210 100-K0501 100-K0901 100-K1201 100-K05400 100-K09400 100-K12400 100-K05300 100-K09300 100-K12300 100-K05200 100-K09200 100-K12200 100-KFC02 AC/DC 10 + 02 = 12 — 00 + 02 = 02 00 + 02 = 02 (3) — 100-KFB11 AC/DC 10 + 11 = 21 — 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 100-KFC11 AC/DC 10 + 11 = 21 (2) 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 100-KFC20 AC/DC 10 + 20 = 30 (2) 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 100-KFC04 AC/DC 10 + 04 = 14 (3) — 00 + 04 = 04 (3) —— 100-KFC13 AC/DC 10 + 13 = 23 (2)(3) 00 + 13 = 13 00 + 13 = 13 (3) — 100-KFB22 AC/DC 10 + 22 = 32 — 00 + 22 = 22 00 + 22 = 22 (3) — 100-KFC22 AC/DC 10 + 22 = 32 (2)(3) 00 + 22 = 22 00 + 22 = 22 (3) — 100-KFA31Z AC/DC (2) — (2)(4) —— 5A1 5A1 5A1 R7A1 R7A1 51 61 6252 21 31 3222 53 61 54 62 23 31 24 32 53 63 54 64 23 33 24 34 71 81 82 72 51 61 62 52 41 51 52 42 21 31 32 22 53 61 71 7254 62 23 314 1 4224 32 53 83 61 71 7254 84 62 43 53 21 31 3244 54 22 23 53 31 41 4224 54 32 73 83 61 74 84 62

8 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Accessories Accessories 100-KFC31 AC/DC 10 + 31 = 41 (4) — 00 + 31 = 31 (4) —— 100-KFA40E AC/DC (2) (2) (2) (2) 100-KFC40 AC/DC 10 + 40 = 50 (2) 00 + 40 = 40 00 + 40 = 40 00 + 40 = 40 (1) For other operating limits, please contact your local Rock well Automation sales office or Allen-Bradley distributor (2) Combination possible but not recommended, due to repeating or not consecutive sequence numbering (3) T amb max. +40 °C (104 °F) (4) T amb max. +40 °C (104 °F) and only allowed for coil voltage 24V DC or 230V AC Auxiliary Contact Blocks Description Connection Diagrams For Use With Pkg. Qty. Cat. No. N.O. N.C. Screw Type Terminals Spring Clamp Terminals Front-mounted Auxiliary Contacts

  • Auxiliary contact blocks 2- and 4-pole versions
  • Choice of contact configurations
  • Snap on, no tools required
  • Electronic-compatible bifurcated contacts for signals down to 15V/2 mA
  • Mirror Contact performance per IEC 60947-4-1 02 1 0 0 - K 0 5 … K 1 2 1 100-KFC02 100-KRFC02 11 1 0 0 - K 0 5 … K 1 21 100-KFC11 100-KRFC11 20 1 0 0 - K 0 5 … K 1 2 1 100-KFC20 100-KRFC20 04 1 0 0 - K 0 5 … K 1 2 1 100-KFC04 100-KRFC04 13 1 0 0 - K 0 5 … K 1 21 100-KFC13 100-KRFC13 31 1 0 0 - K 0 5 … K 1 21 100-KFC31 100-KRFC31 22 1 0 0 - K 0 5 … K 1 2 1 100-KFC22 100-KRFC22 40 1 0 0 - K 0 5 … K 1 2 1 100-KFC40 100-KRFC40 Device Combinations in Accordance with IEC 60947-1 / -4-1 (Continued) Auxiliary Contact Blocks(1) 100-K Miniature Contactors (AC and DC Control) Circuit Diagram Control 100-K0510 100-K0910 100-K1210 100-K0501 100-K0901 100-K1201 100-K05400 100-K09400 100-K12400 100-K05300 100-K09300 100-K12300 100-K05200 100-K09200 100-K12200 5A1 5A1 5A1 R7A1 R7A1 43 53 31 44 54 32 53 63 738 3 8454 64 74 23 33 43 53 5424 34 44 21 31 3222 23 31 24 32 23 33 24 34 41 51 52 42 21 31 32 22 23 314 1 4224 32 43 53 31 44 54 32 23 53 31 41 4224 54 32 23 33 43 53 5424 34 44

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 9 100-K/104-K Miniature Contactors Accessories Front-mounted Auxiliary Contacts Auxiliary contact blocks 2- and 4-pole versions

  • Choice of contact configurations
  • Snap on, no tools required
  • Electronic-compatible bifurcated contacts for signals down to 15V/2 mA
  • Mirror Contact performance per IEC 60947-4-1 02 100/104-K, 700-K 1 100-KFA02E 100-KRFA02E 11 100/104-K, 700-K 1 100-KFA11E 100-KRFA11E 20 100/104-K, 700-K 1 100-KFA20E 100-KRFA20E 04 100/104-K, 700-K 1 100-KFA04E 100-KRFA04E 13 100/104-K, 700-K 1 100-KFA13E 100-KRFA13E 22 100/104-K, 700-K 1 100-KFA22Z 100-KRFA22Z 31 100/104-K, 700-K 1 100-KFA31Z 100-KRFA31Z 40 100/104-K, 700-K 1 100-KFA40E 100-KRFA40E Control Modules Description Connection Diagrams For Use With Pkg. Qty. Cat. No. Mechanical Interlock
  • For interlocking of two adjacent contacto rs No added width to contactor assembly
  • Front mount plug-in type
  • Optional auxiliary contact blocks and suppressor modules mount onto the interlock 100/104-K/-KR, 700-K/-KR 1 100-KMCH Surge Suppressor
  • Plug-in type
  • Limits surge voltage on coil drop- off RC Suppressor 24…48V AC 100/104-K/-KR, 700-K/-KR 1(1) (1) May be ordered in package quantities of 10. Add lett er M to the end of the cat. no. Example: 100-KFSC50M. 100-KFSC50 110…280V AC 1(1) 100-KFSC280 380…480V AC 1(1) 100-KFSC480 MOV Suppressor 12…55V AC, 12…77V DC 100/104-K/-KR, 700-K/-KR 1(1) 100-KFSV55 56…136V AC, 78…180V DC 1(1) 100-KFSV136 137…277V AC, 181…250V DC 1(1) 100-KFSV277 Diode Suppressor 12…250V DC 100/104-K/-KR, 700-K/-KR 1(1) 100-KFSD250 Timers Description Connection Diagrams For Use With Pkg. Qty. Cat. No. Solid-State Timing Element
  • 1 1 0 … 2 5 0 V A C o r D C
  • Includes 35 mm Hat Rail adapter On-Delay, 0.1…3 s 100/104-K, 700-K 10 100-KT3S On-Delay, 1…30 s 100-KT30S Auxiliary Contact Blocks (Continued) Description Connection Diagrams For Use With Pkg. Qty. Cat. No. N.O. N.C. Screw Type Terminals Spring Clamp Terminals 51 61 6252 53 61 54 62 53 63 54 64 71 81 82 72 51 61 62 52 53 61 71 7254 62 53 83 61 71 7254 84 62 73 83 61 74 84 62 53 63 738 3 8454 64 74 N O / I

10 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Accessories Connecting Components Description For Use With Pkg. Qty. Cat. No. ECO Connecting Module — 12 A

  • For DOL and reversing starters
  • Eco-starters mount on single DIN Rail (140M on DIN Rail)
  • Electrical and mechanical interconnection of 140M and 100-K contactors Connects: 140M-C circuit breakers with 100-K contactors 140M-C to 100-K 1 (1) (1) May be ordered in package quantities of 10. Add lett er M to the end of the cat. no. Example: 140M-C-PEK12M. 140M-C-PEK12 Power Wiring Kit
  • For Reversing and Star/Delta combinations. Star-point bridge not included.
  • Min. interruption time 50 ms 100-K 1 100-KPR Feeder Terminal for Compact Bus Bars
  • Max. current 34 A Supply of compact bus bars 100-K 1 100-KWT Three-phase Compact Bus Bars
  • Max. current 34 A
  • For 100-K, 5…12 A contactors 45 mm spacing (3 connections) (2) 100-K, 5…12 A 1 100-KW453 45 mm spacing (4 connections)(2) 100-K, 5…12 A 1 100-KW454 Marking Systems Description Pkg. Qty. Cat. No. Label Sheet
  • 105 self-adhesive paper labels each, 6 x 17 mm 10 100-FMS Snap-In Marker Card 5 1492-M6X12 2 46 1 35 K1M 2 46 1 35 K2M - (L2)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 11 100-K/104-K Miniature Contactors Specifications Specifications Table 1 - Main Circuits 100-KR 100/104-K 05 09 05 09 12 AC-1 Active Power Load (50 Hz); Ambient temperature 40 °C (104 °F) Rated Operational Current, Ie ≤ 5 0 0 V [ A ] 1 0 1 02 02 02 0 6 9 0 V [ A ] 1 0 1 02 02 02 0 Rated Operational Power, P e 230V [kW] 4 4 8 8 8 240V [kW] 4 4 8.3 8.3 8.3 400V [kW] 6.9 6.9 14 14 14 415V [kW] 7 7 14 14 14 500V [kW] 8.7 8.7 17 17 17 690V [kW] 12 12 24 24 24 AC-1 Active Power Load (50 Hz); Ambient temperature 60 °C (140 °F) Rated Operational Current, Ie ≤ 500V [A] 10 10 16 16 16 690V [A] 10 10 16 16 16 Rated Operational Power, P e 230V [kW] 4 4 6.4 6.4 6.4 240V [kW] 4 4 6.7 6.7 6.7 400V [kW] 6.9 6.9 11 11 11 415V [kW] 7 7 12 12 12 500V [kW] 8.7 8.7 14 14 14 690V [kW] 12 12 19 19 19 Switching of 3-phase Motors; (50 Hz) Ambient temperature 60 °C (140 °F), AC-2, AC-3 Rated Operational Current, Ie Rated Operational Power, Pe 230V [kW] 1.5 2.2 1.5 3 3 240V [kW] 1.5 2.2 1.5 3 3 400V [kW] 2.2 4 2.2 4 5.5 415V [kW] 2.2 4 2.2 4 5.5 500V [kW] 2.2 4 2.2 4 5.5 690V [kW] 2.2 4 2.2 4 5.5 Load Carrying Capacity per UL/CSA General Purpose Current (enclosed) [A] 9 9 12 15 18 Rated current (enclosed), 1-phase 230V [A] 6.9 8 8 10 12 Rated power (enclosed), 1-phase 115V [Hp] 1/3 1/3 0.5 0.5 0.75 230V [Hp] 3/4 1 1 1.5 2 Rated current (enclosed), 3-phase 200V [A] 6.9 7.8 6.9 7.8 11 230V [A] 6 6.8 6 6.8 9.6 460V [A] 4.8 7.6 4.8 7.6 11 575V [A] 3.9 6.1 3.9 6.1 9 Rated power (enclosed), 3-phase 200V [Hp] 1.5 2 1.5 2 3 230V [Hp] 1.5 2 1.5 2 3 460V [Hp] 3 5 3 5 7.5 575V [Hp] 3 5 3 5 7.5 Table 2 - Main Circuits 100/104-K 05 09 12 Switching of 3-phase Motors, (50 Hz); Ambient temperature 60 °C (140 °F), AC-4 Rated Operational Current, Ie 230V [A] 6.3 11.3 11.3 240V [A] 6.3 11.3 11.3 400V [A] 4.9 8.5 11.5 415V [A] 4.9 8.5 11.5 500V [A] 3.9 6.8 9.2 690V [A] 2.8 4.9 6.7 Rated Operational Power, Pe 230V [Hp] 1.5 3 3 240V [Hp] 1.5 3 3 400V [Hp] 2.2 4 5.5 415V [Hp] 2.2 4 5.5 500V [Hp] 2.2 4 5.5 690V [Hp] 2.2 4 5.5 AC-4 at approximately 200,000 operations Rated Operational Current, Ie 230V [A] 2.3 3.9 3.9 240V [A] 2.3 3.9 3.9 400/415V [A] 2 3.6 3.6 500V [A] 1.9 3.2 3.2 Rated Operational Power, Pe 230V (1) (1) Power ratings at 50 Hz: Preferred values according to IEC 60072-1 240V (1) [Hp] 0.37 0.75 0.75 Max. switching frequency Ops/hour 250 250 250 Wye-Delta (60 Hz) Rated Operational Power, Pe 200V [Hp] 2.2 3 5 230V [Hp] 2.2 3 5 460V [Hp] 5 7.5 10 575V [Hp] 5 7.5 10 Star-Delta Starting (50 Hz) Rated Operational Current, Ie ≤ 230V [A] 11.3 20 20 ≤ 240V [A] 11.3 20 20 400V [A] 8.5 15.5 15.5 415V [A] 8.5 15.5 15.5 500V [A] 6.8 12.4 12.4 690V [A] 4.9 8.9 8.9 Rated Operational Power, Pe

12 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Specifications Table 3 - Main Circuits 100/104-K 05 09 12 Switching of Power Transformers, AC-6a (50 Hz) n= 30 Apparent Power 230V [kVA] 1.2 2 2 240V [kVA] 1.2 2 2 400V [kVA] 1.7 2.8 3.4 415V [kVA] 1.7 2.8 3.4 500V [kVA] 1.7 2.8 3.4 690V [kVA] 2 4 5 Switching of Lamps Gas discharge lamps AC-5a, 40 °C (104 °F) open [A] 18 18 18 enclosed [A] 14.5 14.5 14.5 Individually compensated: Max. capacitance at expected Short-circuit current of 10 kA [µF] 750 750 750 20 kA [µF] 400 400 400 Filament AC-5b 230/240V [A] 5 9 9 Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz) AC-7a 2 3 0 V [ A ] 2 02 02 0 4 0 0 V [ A ] 2 02 02 0 Switching of Motor Load for Home Appliances (50 Hz) AC-7b 230V [A] 6 11 11 400V [A] 6 11 11 Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz) AC-8a 400V [A] 11 18 18 500V [A] 10 15 15 Switching of DC Loads Non-inductive or slightly inductive loads or resistance furnaces 1 pole 24V [A] 6 9 9 110V [A] 0.6 1 1 220V [A] 0.2 0.3 0.3 440V [A] 0.08 0.1 0.1 2 poles in series 24V [A] 6 9 9 48/60V [A] 6 8 8 110V [A] 4 6 6 220V [A] 0.8 1.2 1.2 440V [A] 0.2 0.3 0.3 3 poles in series 24V [A] 6 9 9 48/60V [A] 6 9 9 110V [A] 6 9 9 220V [A] 3 4 4 440V [A] 0.4 0.6 0.6 Inrush Current Rated transformer current = n Shunt-wound Motors Starting, reverse current braking, reversing, stepping DC-3, 60 °C (140 °F) 3 poles in series 24V [A] 5 9 9 48/60V [A] 4 6 6 110V [A] 2 3 3 220V [A] 0.8 1.2 1.2 440V [A] 0.15 0.2 0.2 Series-wound Motors Starting, reverse current braking, reversing, stepping DC-5, 60 °C (140 °F) 3 poles in series 24V [A] 5 9 9 48/60V [A] 2 3 3 110V [A] 0.6 1 1 220V [A] 0.1 0.1 0.1 Short Time Withstand I CW, 60 °C (140 °F 10 s [A] 60 96 96 Resistance and Power Dissipation Main current circuit resistance [mΩ] 2.2 2.2 2.2 Power dissipation by all circuits at Ie AC-3/ 400V [W] 0.3 0.9 0.9 Total power dissipation At Ie AC-3/400V AC control [W] 2.1 2.7 2.7 DC control (electronic) [W] 2.9 3.5 3.5 Lifespan Mechanical AC control [Million operations] 15 15 15 Mechanical DC control [Million operations] 15 15 15 Electrical AC-3 (400 V) [Million operations] 0.7 0.7 0.7 Weight AC Non-Rev. [kg (lbs.)] 0.16 (0.35) Rev. [kg (lbs.)] 0.4 (0.88) DC Non-Rev. [kg (lbs.)] 0.2 (0.44) Rev. [kg (lbs.)] 0.48 (1.06) Table 4 - Conductors 100-KR 100/104-K 05 09 05 09 12 Conductor Cross Sections - Main Contacts Terminal type (1) (1) Pozidriv No. 2 / Blade No. 3 screw 1 conductor [mm2] 0.50…2.5 0.75…2.5 2 conductors [mm2] 0.50…2.5 0.75…2.5 1 conductor [mm2] 0.75…2.5 (2) (2) Fine- or coarse-stranded only 1…4 2 conductors [mm2] 0.75…2.5 (2) 1…2.5+ 1…4 Recommended torque [N•m] — 1.2 Cross section per UL/CSA [AWG] 18…14(2) 18…12 Recommended torque [lb•in] — 10.6 Table 3 - Main Circuits (Continued) 100/104-K 05 09 12

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 13 100-K/104-K Miniature Contactors Specifications Table 5 - Short-Circuit Coordination Data(1) (1) See the Rockwell Automation Global SCCR Tool at rok.auto/sccr for complete short- circuit current ratings. 100/104-K 05 09 12 Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1 (contactor and fuses only) DIN Fuses- gG, gL 50 kA Available Fault Current Type "1" (690V) [A] 35 35 35 Type "2" (400V) [A] 16 20 20 Per UL 508 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only) UL Class K5 and RK5 Fuses 5 kA Available Fault Current UL Listed Combination (600V) [A] 40 40 40 UL Class CC and CSA HRCI-MISC Fuses 50 kA Available Fault Current UL Listed Combination (600V) [A] 30 30 30 UL Class J and CSA HRCI-J Fuses 50 kA Available Fault Current UL Listed Combination (600V) [A] 30 30 30 Table 6 - Coil Data 100/104-K 05 09 12 Operating Limits

50 Hz, 60 Hz, 50/60 Hz

pick-up [x Us] 0.85…1.1 dropout [x Us] 0.2…0.75 DC (conventional) pick-up [x Us] 0.8…1.1 0.7…1.25(1) (1) For 9, 12, 24, and 110V DC coils dropout [x Us] 0.1…0.75 Coil Consumption

50 Hz, 60 Hz, 50/60 Hz pick-up [VA] 35

hold-in [VA/W] 5/1.8 DC (conventional) pick-up [W] cold 3.0, warm 2.6 hold-in [W] cold 3.0, warm 2.6 Operating Times AC closing delay [ms] 15…40 opening delay [ms] 15…33 With RC module closing delay [ms] 15…28 DC (conventional) opening delay [ms] 18…40 closing delay [ms] 6…12 With integrated diode opening delay [ms] 8…12 With external diode opening delay [ms] 35…50 Table 7 - Auxiliary Contacts and Auxiliary Contact Blocks Conventional Coils Internal Front mounted Switching of AC Loads AC-12 Ith at 40 °C (104 °F) [A] 10 10 at 60 °C (140 °F) [A] 6 6 AC-15 at rated voltage of 24V [A] 6 3 42/48V [A] 6 3 120V [A] 6 3 230V [A] 3 2 240V [A] 3 2 400V [A] 1.8 1.2 415V [A] 1.8 1.2 500V [A] 1.4 1.0 690V [A] 1.0 0.6 Switching of DC Loads DC-12 L/R < 1 ms resistive loads at 24V DC [A] 6 — 48V DC [A] 4 — 110V DC [A] 0.6 — 220V DC [A] 0.2 — 440V DC [A] 0.08 — DC-14L/R <15 ms inductive loads with economy resistor in series at 24V DC [A] 4 — 48V DC [A] 2.5 — 110V DC [A] 0.4 — 220V DC [A] 0.12 — 440V DC [A] 0.05 — DC-13 switching electromagnets at 24V DC [A] 2.8 2.3 48V DC [A] 1.2 1 110V DC [A] 0.55 0.55 220V DC [A] 0.27 0.27 440V DC [A] 0.15 0.15 Fuse gG [A] 10 10 [A] 10 10 Min. switching capacity according to IEC 60947-5-4 15V/ 10 mA 15V/ 2 mA Load Carrying Capacity per UL/CSA Rated voltage AC [V] max.600 Continuous rating at 40 °C (104 °F) [A] 10 Switching capacity AC [A] A600 B600 Rated voltage DC [V] max.600 Switching capacity DC [A] Q600

14 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Specifications Table 8 - General Attribute Value Rated Isolation Voltage Ui IEC [V] 690 UL, CSA [V] 600 Rated Impulse Voltage Withstand Uimp [kV] 6 Rated Voltage Ue AC 50/60 Hz [V] 230, 240, 400, 415, 460, 500, 575, 690 DC [V] 24, 48, 110, 220, 440 Insulation Class of the Coil Class F per IEC 60085 Class 105 insulation system per UL 508 Rated coil frequency AC 50/60 Hz, DC Ambient Temperature Operation at rated voltage [ °C ( °F)] -25…+60 (-13…140) at 70 °C (158 °F) 15% current reduction against 60 °C (140 °F) values Climatic Withstand IEC60068-2-30 Max. Altitude of Installation Site [m] 2000 NN, per IEC60947-4 Protection Class IP2X Single contactor cover — Contactor with frame terminal block — Auxiliary contact IP2X Protection against Accidental Contact — Resistance to Shock IEC60068-2 Resistance to Vibration IEC60068-2 Mechanically Linked Contacts IEC60947-5-1,AnnexL 100-K… (on main device) Mirror Contacts IEC60947-4 Annex F 100-K…+100-KF… Table 9 - Standards Compliance and Certifications Standards Compliance Certifications IEC/EN 60947-1,-4-1,-5-1,-5-4 CE Marked UL 508 CCC CSA 22.2. No. 14 cULus Listed (File No. E41850, Guide NLDX, NLDX7)NF F 62-000 Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS

16 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-K/104-K Miniature Contactors Approximate Dimensions Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. Figure 3 - 100-K Miniature Contactor with 193-K Overload Relay Figure 4 - Mounting Position 49 (1-15/16) 56 (2-13/64) 54 (2-1/8) 35 (1-25/64) 44.9 (1-25/32) 50 (1-31/32) 63.5 (2-1/2) 78.7 (3-7/64) 35.2 (1-25/64) 49.2 (1-15/16) 36.9 (1-29/64) 25° 25° -Minimum distance to grounded parts or walls 180°

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 17 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100-C/104-C Contactors

  • Compact sizes from 4… 55 kW/5…75 Hp (9…97 A)
  • Common accessories for all contactor sizes
  • Front and side mounting of auxiliary contacts
  • Electronic and pneumatic timing modules
  • Space-saving coil-mounted control modules
  • Reversible coil terminations (line or load side)
  • All devices can be attached to 35 mm DIN mounting Rail
  • Environmentally friendly materials The Bulletin 100-C/104-C IEC contactor family, along with a wide range of common accessories and Bulletin 193 solid-state overload relays, provides the most compact and flexible starter component system available.  Coil voltage code and terminal position—see page 19 3-Pole AC- and DC-operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts Cat. No.(1) (1) For screwless terminals on 100-C09…C16, add an “R” after the letter “C” in the catalog number. Example: Cat. No. 100-C09 10 becomes 100-CR0910. The AC-1 rating for the 100-CR is limited to 25 A. 3-phase kW (50 Hz) Hp (60 Hz) 40 °C (104 °F) 230V 400/415V 500V 690V 1-Phase 3-Phase AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C. 9 32 3 4 4 4 1/2 1-1/12 2 2 5 7-1/12 10 100-C0910 01 100-C0901 12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 10 100-C1210 01 100-C1201 16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 10 100-C1610 01 100-C1601 23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 10 100-C2310 01 100-C2301 30 65 10 15 15 15 2 5 7-1/2 10 20 25 00 100-C3000 10 100-C3010 01 100-C3001 3 7 6 5 1 1 1 8 . 5 / 2 0 2 0 1 8 . 53 5 1 0 1 02 53 0 00 100-C3700 10 100-C3710 01 100-C3701 43 85 13 22 25 22 3 7-1/2 10 15 30 30 00 100-C4300 10 100-C4310 01 100-C4301 55 85 15 30 30 30 5 10 15 20 40 40 00 100-C5500 10 100-C5510 01 100-C5501 60 100 18.5 32 37 32 5 10 15 20 40 50 00 100-C6000 10 100-C6010 01 100-C6001 72 100 22 40 45 40 5 15 20 25 50 60 00 100-C7200 10 100-C7210 01 100-C7201 85 100 25 45 55 45 7-1/2 15 25 30 60 60 00 100-C8500 10 100-C8510 01 100-C8501 9 7 1 3 0 3 0 5 5 5 55 51 02 03 03 07 57 5 00 100-C9700 10 100-C9710 01 100-C9701 100-C Contactor 104-C Reversing Contactor

18 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100-C/104-C Contactors  Coil voltage code and terminal position— see page 19.  Coil voltage code and terminal position— see page 19. 4-Pole AC- and DC-Operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Contact Configuration, Main Poles Cat. No.(1) (1) For screwless terminals on 100-C09…C16, add an “R” after the letter “C” in the catalog number. Example: Cat. No. 100-C09 10 becomes 100-CR0910. The AC-1 rating for the 100-CR is limited to 25 A. 3-phase kW (50 Hz)(2) (2) Three-phase ratings apply only to contactors with at least three N.O. power poles. Hp (60 Hz) 40 °C (104 °F) 230V 400/415V 500V 690V 1-Phase 3-Phase(2) AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C. 9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 40 100-C09400 31 100-C09300 22 100-C09200 12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 40 100-C12400 31 100-C12300 22 100-C12200 16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 10 40 100-C16400 31 100-C16300 22 100-C16200 23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 40 100-C23400 31 100-C23300 22 100-C23200 37 75 11 18.5/20 20 18.5 3 5 10 10 25 30 40 100-C40400 22 100-C40200 85 130 25 45 55 45 7-1/2 15 25 30 60 50 40 100-C90400 22 100-C90200 Reversing AC- and DC-Operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts per Contactor Cat. No.3-phase kW (50 Hz) Hp (60 Hz) 40 °C (104 °F) 230V 400/415V 500V 690V 1-Phase 3-Phase AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C. (1) (1) The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock. 9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 1 1 104-C0922 12 32 4 5.5 5.5 5.5 1 2 3 3 7-1/2 10 1 1 104-C1222 16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 1 1 104-C1622 23 32 7.5 11 13 10 2 3 5 7-1/2 15 20 1 1 104-C2322 30 65 10 15 15 15 2 5 7-1/2 10 20 25 01 104-C3002 11 104-C3022 37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 01 104-C3702 11 104-C3722 43 85 13 22 25 22 3 7.5 10 15 30 30 01 104-C4302 11 104-C4322 55 85 15 30 30 30 5 10 15 20 40 40 01 104-C5502 11 104-C5522 60 100 18.5 32 37 32 5 10 15 20 40 50 01 104-C6002 11 104-C6022 72 100 22 40 45 40 5 15 20 25 50 60 01 104-C7202 11 104-C7222 85 100 25 45 55 45 7-1/2 15 25 30 60 60 01 104-C8502 11 104-C8522 97 130 30 55 55 55 10 15 30 30 75 75 01 104-C9702 11 104-C9722

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 19 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100-C/104-C Contactors Coil Voltage Codes 100-C0910 becomes Cat. No.100-C09D10. Coil Terminal Position All contactors are delivered with the coil terminals located on the line side. For load side coil terminations, insert a “U” prior to the coil voltage code. Ordering example: Cat. No. 100-C09UD10. AC Voltages [V] 12 24 32 36 42 48 100 100… 110 110 120 127 200 200… 220 208 208… 240

50 Hz R K V W X Y KP — D P S KG L — —

60 Hz Q J — V — X — KP — D — — KG H L

50/60 Hz — KJ — — — KY KP — KD — — KG KL(1) (1) Not available on 100/104-C90 or -C97 contactors. — — AC Voltages [V] 220… 230 230 230… 240 240 277 347 380 380… 400 400 400… 415 440 480 500 550 600

50 Hz F — VA T — — — N — G B — M C —

50/60 Hz KL(1) (1) Not available on 100/104-C90 or -C97 contactors. DC Voltages [V] 9 12 24 24 36 36…48 48 48…72 60 64 100-C09…C55 Electronic with Integrated Diode — EQ EJ QJ(1) (1) “QJ” coil has faster dropout time (16…21 ms). — EW — EY — — 100-C60…C97 with Integrated Diode DR DQ DJ — DW — DY — DZ DB DC Voltages [V] 72 80 110 110…125 115 125 220 220…250 230 250 100-C09…C55 Electronic with 100-C60…C97 with Integrated Diode DG DE DD — DP DS DA — DF DT Cat. No.100-C0910 Line Side Cat. No.100-C09U10 Load Side

20 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100-C/104-C Contactors Assignment of Contacts Table valid for: AC / DC = 0.85…1.1 x Us, Tamb = -25 °C…+60 °C (-13…140 °F), normal position (horizontal rail mounting) Device Combinations in Accordance with IEC 60947-1 / -4-1 Auxiliary Contact Blocks 100-C Contactors (AC and DC Control) Circuit Diagram Control 100-C09_10 100-C12_10 100-C16_10 100-C23_10 100-C09_01 100-C12_01 100-C16_01 100-C23_01 100-C30_00 100-C37_00 100-C43_00 100-C55_00 100-C60_00 100-C72_00 100-C85_00 100-C97_00 100-C09_400 100-C12_400 100-C16_400 100-C23_400 100-C40_400 100-C90_400 100-C09_300 100-C12_300 100-C16_300 100-C23_300 100-C09_200 100-C12_200 100-C16_200 100-C23_200 100-C40_200 100-C90_200 Side Mounting (1) 100-SB01 AC/DC 10 + 01 = 11 01 + 01 = 02 (2) (2) Double numbering: because of double numbering only left-side mounting is recommended. 00 + 01 = 01 00 + 01 = 01 00 + 01 = 01 00 + 01 = 01 100-SB10 AC/DC 10 + 10 = 20 (2) 01 + 10 = 11 00 + 10 = 10 00 + 10 = 10 00 + 10 = 10 00 + 10 = 10 100-SB02 AC/DC 10 + 02 = 12 (2) — 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 100-SB11 AC/DC 10 + 11 = 21 (2) 01 + 11 = 12 (2) 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 100-SB20 AC/DC 10 + 20 = 30 (2) 01 + 20 = 21 (2) 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 100-SBL11 (3) (3) Early make and/or late break. AC/DC 10 + L11 = L21 (2) 01 + L11 = L12 (2) 00 + L11 = L11 00 + L11 = L11 00 + L11 = L11 00 + L11 = L11 5A1 5A1 5A1 5A1 R7A1 R5A1 2132 42 32 3141 44 32 3143 2344 34 3343 25361748 18472635

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 21 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100-C/104-C Contactors Device Combinations in Accordance with IEC 60947-1 / -4-1 Auxiliary Contact Blocks 100-C Contactors (AC and DC Control) Circuit Diagram Control 100-C09_10 100-C12_10 100-C16_10 100-C23_10 100-C09_01 100-C12_01 100-C16_01 100-C23_01 100-C30_00 100-C37_00 100-C43_00 100-C55_00 100-C60_00 100-C72_00 100-C85_00 100-C97_00 100-C09_400 100-C12_400 100-C16_400 100-C23_400 100-C40_400 100-C90_400 100-C09_300 100-C12_300 100-C16_300 100-C23_300 100-C09_200 100-C12_200 100-C16_200 100-C23_200 100-C40_200 100-C90_200 Front Mounting (1) 100-FA02, 100-FAB02 AC/DC 10 + 02 = 12 01 + 02 = 03 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 100-FA11, 100-FAB11 AC/DC 10 + 11 = 21 01 + 11 = 12 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 100-FB11, 100-FBB11 AC/DC — — 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 00 + 11 = 11 100-FC11, 100-FCB11 AC/DC 10 + 11 = 21 — — — — — 100-FA20, 100-FAB20 AC/DC 10 + 20 = 30 01 + 20 = 21 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 100-FBL11 (2) (2) Early make and/or late break. AC/DC — — 00 + L11 = L11 00 + L11 = L11 00 + L11 = L11 00 + L11 = L11 100-FA22, 100-FAB22 AC/DC 10 + 22 = 32 01 + 22 = 23 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22 100-FB22, 100-FBB22 AC/DC — — 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22 00 + 22 = 22 100-FC22, 100-FCB22 AC/DC 10 + 22 = 32 — — — — — 100-FA31, 100-FAB31 AC/DC 10 + 31 = 41 01 + 31 = 32 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31 100-FA40, 100-FAB40 AC/DC 10 + 40 = 50 01 + 40 = 41 00 + 40 = 40 00 + 40 = 40 00 + 40 = 40 00 + 40 = 40 100-FAL22 (2) AC/DC 10 + L22 = L32 01 + L22 = L23 00 + L22 = L22 00 + L22 = L22 00 + L22 = L22 00 + L22 = L22 100-FA04, 100-FAB04 AC/DC 10 + 04 = 14 01 + 04 = 05 00 + 04 = 04 00 + 04 = 04 00 + 04 = 04 00 + 04 = 04 100-FA13, 100-FAB13 AC/DC 10 + 13 = 23 01 + 13 = 14 00 + 13 = 13 00 + 13 = 13 00 + 13 = 13 00 + 13 = 13 100-FB02, 100-FBB02 AC/DC 10 + 02 = 12 01 + 02 = 03 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 00 + 02 = 02 100-FB20, 100-FBB20 AC/DC 10 + 20 = 30 01 + 20 = 21 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 00 + 20 = 20 100-FC31, 100-FCB31 AC/DC 10 + 31 = 41 01 + 31 = 32 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31 00 + 31 = 31 5A1 5A1 5A1 5A1 R7A1 R5A1 51 61 6252 53 61 54 62 13 21 14 22 23 31 24 32 53 63 54 64 17 25 2618 53 61 71 7254 62 13 21 31 3214 22 4331 21 22 4432 53 61 54 62 53 63 73 83 8454 64 74 53 61 75 7654 62 51 61 71 81 8252 62 72 53 61 71 81 8254 62 72 11 21 22 12 13 23 2414 23 31 43 53 5424 32 44

22 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors Product Selection—100S-C/104S-C Safety Contactors Bulletin 100S-C/104S-C safety contactors provide mechanically linked positively guided contacts, required in feedback circuits of modern safety applications. The mechanically linked N.C. auxiliary contacts do not change state when a power pole welds. In addition, the gold- plated bifurcated auxiliary contacts are ideally suited for low-energy applications or feedback control circuits with multiple series- connected N.C. auxiliary contacts.  Coil voltage code and terminal position— see page 25.

  • Mechanically linked N.C. auxiliary contacts
  • Front-mounted auxiliary contacts - Gold bifurcated - Protective cover to prevent manual operation - Permanently fixed - Red contact housing for easy identification - “Mechanically Linked” or “Mirror Contact” symbol
  • AC and DC operating coils
  • SUVA Third-party certification
  • Reversing contactors: - 3 Main contacts - Include reversing power wiring
  • Include mechanical/electrical Interlock 3-Pole AC- and DC-operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts Cat. No.(1) (2) (1) For other contact configurations and full product details, plea se contact your local Rockwell Automation sales office or Allen-Bradley distributor. (2) If standard cross-stamped fron t-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C0905BC becomes Cat. No. 100S-C0905C. 3-phase kW (50 Hz) Hp (60 Hz) 40 °C (104 °F) 230V 400/415V 500V 690V 1-Phase 3-Phase AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C. 9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 05 100S-C0905BC 14 100S-C0914BC 12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 05 100S-C1205BC 14 100S-C1214BC 16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 05 100S-C1605BC 14 100S-C1614BC 23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 05 100S-C2305BC 14 100S-C2314BC 30 65 10 15 15 15 2 5 7-1/2 10 20 25 04 100S-C3004BC 14 100S-C3014BC 37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 04 100S-C3704BC 14 100S-C3714BC 43 85 13 22 25 22 3 7-1/2 10 15 30 30 04 100S-C4304BC 14 100S-C4314BC 55 85 15 30 30 30 5 10 15 20 40 40 04 100S-C5504BC 14 100S-C5514BC 60 100 18.5 32 37 32 5 10 15 20 40 50 04 100S-C6004BC(3) (3) Front- and side-mount auxiliary cont acts on Cat. Nos. 100S-C60…C97 conform to mirror contact performance only. 14 100S-C6014BC(3) 72 100 22 40 45 40 5 15 20 25 50 60 04 100S-C7204BC(3) 14 100S-C7214BC(3) 85 100 25 45 55 45 7-1/2 15 25 30 60 60 04 100S-C8504BC(3) 14 100S-C8514BC(3) 97 130 30 55 55 55 10 15 30 30 75 75 04 100S-C9704BC(3) 14 100S-C9714BC(3) 100S-C Safety Contactor 104S-C Reversing Safety Contactor

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 23 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors  Coil voltage code and terminal position— see page 25. 4-Pole AC- and DC-operated Contactors Rated Operational Current Ie [A] Ratings for Switching AC Motors Contact Configuration Cat. No.(1) (2) (1) For other contact configurations and full product details, please contact your local Rockwell Automation sales office or All en-Bradley distributor. (2) If standard cross-stamped fron t-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 100S-C09404BC becomes Cat. No. 100S-C09404C. AC-2, AC-3, AC-4 Hp (60 Hz) 3-Phase kW (50 Hz)(3) (3) Three-phase ratings only apply to contactors with at least three N.O. power poles. Main Pole Auxiliary Contacts 40 °C (104 °F) 230V 400V/ 415V 500V 690V 1-Phase 3-Phase(3) 9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 4004 100S-C09404BC 310 4 100S-C09304BC 12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 4004 100S-C12404BC 310 4 100S-C12304BC 16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 4004 100S-C16404BC 310 4 100S-C16304BC 23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 4004 100S-C23404BC 310 4 100S-C23304BC

24 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors  Coil voltage code and terminal position— see page 25. Reversing AC- and DC-operated Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3, AC-4 Auxiliary Contacts Cat. No.(1) (2) (1) For other contact configurations and full product details, please contact your local Rockwell Automation sales office or All en-Bradley distributor. (2) If standard cross-stamped fron t-mount auxiliary contacts are required, remove the letter "B" before the letter "C" in the cat. no. Example: Cat. No. 104S-C0905BC becomes Cat. No. 104S-C0905C. 3-phase kW (50 Hz) Hp (60 Hz) 40 °C (104 °F) 230V 400/ 415V 500V 690V 1-Phase 3-Phase AC-3 AC-1 115V 230V 200V 230V 460V 575V N.O. N.C.(3) (3) One of the N.C. auxiliary contacts is supplied as part of th e mechanical/electrical interlock. 9 32 3 4 4 4 1/2 1-1/2 2 2 5 7-1/2 06 104S-C09012BC 15 104S-C09210BC 12 32 4 5.5 5.5 5.5 1/2 2 3 3 7-1/2 10 06 104S-C12012BC 15 104S-C12210BC 16 32 5.5 7.5 7.5 7.5 1 3 5 5 10 15 06 104S-C16012BC 15 104S-C16210BC 23 32 7.5 11 13 10 2 3 5 7-1/2 15 15 06 104S-C23012BC 15 104S-C23210BC 30 65 10 15 15 15 2 5 7-1/2 10 20 25 05 104S-C30010BC 15 104S-C30210BC 37 65 11 18.5/20 20 18.5 3 5 10 10 25 30 05 104S-C37010BC 15 104S-C37210BC 43 85 13 22 25 22 3 7-1/2 10 15 30 30 05 104S-C43010BC 15 104S-C43210BC 55 85 15 30 30 30 5 10 15 20 40 40 05 104S-C55010BC 15 104S-C55210BC 60 100 18.5 32 37 32 5 10 15 20 40 50 05 104S-C60010BC(4) (4) Front- and side-mount auxiliary cont acts on Cat. Nos. 104S-C60…C97 conform to mirror contact performance only. 15 104S-C60210BC(4) 72 100 22 40 45 40 5 15 20 25 50 60 05 104S-C72010BC(4) 15 104S-C72210BC(4) 8 51 0 02 54 55 54 5 7 - 1 / 2 1 5 2 5 3 0 6 0 6 0 05 104S-C85010BC(4) 15 104S-C85210BC(4) 9 7 1 3 03 05 55 55 5 1 0 1 5 3 0 3 0 7 5 7 5 05 104S-C97010BC(4) 15 104S-C97210BC(4)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 25 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors Coil Voltage Codes 100S-C0905BC becomes Cat. No.100S-C09D05BC. Coil Terminal Position All contactors are delivered with the coil terminals located on the line side. For load side coil terminations, insert a “U” prior to the coil voltage code. Ordering example: Cat. No. 100S-C09UD05BC. AC Voltages [V] 12 24 32 36 42 48 100 100… 110 110 120 127 200 200… 220 208 208… 240 50/60 Hz — KJ — — — KY KP — KD — — KG KL(1) (1) Not available on 100S/104S-C97 contactors. — — AC Voltages [V] 220… 230 230 230… 240 240 277 347 380 380… 400 400 400… 415 440 480 500 550 600 50/60 Hz KL(1) (1) Not available on 100S/104S-C97 contactors. DC Voltages [V] 9 12 24 24 36 36…48 48 48…72 60 64 100S-C09…C55 Electronic with Integrated Diode — EQ EJ QJ(1) (1) “QJ” coil has faster dropout time (16…21 ms). — EW — EY — — 100S-C60…C97 with Integrated Diode DR DQ DJ — DW — DY — DZ DB DC Voltages [V] 72 80 110 110…125 115 125 220 220…250 230 250 100S-C09…C55 Electronic with 100S-C60…C97 with Integrated Diode DG DE DD — DP DS DA — DF DT Cat. No.100S-C0905CLine Side Cat. No.100S-C09U05CLoad Side

26 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors Assignment of Contacts Figure 5 - Safety Contactors with 3 Main Contacts and Standard Front-mount Auxiliary Contacts Figure 6 - Safety Contactors with 4 Main Contacts and Standard Front-mount Auxiliary Contacts 100S-C09⊗05C…C23⊗ 05C 100S-C09⊗14C…C23⊗ 14C 100S -C09⊗23C…C23⊗ 23C 100S-C30⊗04C…C55⊗ 04C 100S-C30⊗22C…C55⊗ 22C 100S -C30⊗14C…C55⊗ 14C 100S-C60⊗04C…C97⊗ 04C 100S-C60⊗22C…C97⊗ 22C 100S -C60⊗14C…C97⊗ 14C 100S-C09⊗404C…C23⊗ 404C 100S -C09⊗304C…C23⊗ 304C 100S-C09⊗322C…C23⊗ 322C100S-C09⊗422C…C23⊗ 422C

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 27 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors Figure 7 - Safety Reversing Contactors with 3 Main Contacts and Standard Front-mount Auxiliary Contacts 104S-C09⊗012C…C23⊗ 012C 104S-C30⊗010C…C55⊗ 010C 104S-C09⊗210C…C23⊗ 210C 104S-C30⊗210C…C55⊗ 210C 104S-C60⊗010C…C97⊗ 010C 104S-C60⊗210C…C97⊗ 210C

28 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors Figure 8 - Safety Contactors with 3 Main Contacts and Bifurcated Front-mount Auxiliary Contacts Figure 9 - Safety Contactors with 4 Main Contacts and Bifurcated Front-mount Auxiliary Contacts 100S-C09⊗05BC…C23⊗ 05BC 100S-C09⊗14BC…C23⊗ 14BC 100S -C09⊗23BC…C23⊗ 23BC 100S-C30⊗04BC…C55⊗ 04BC 100S-C30⊗22BC…C55⊗ 22BC 100S -C30⊗14BC…C55⊗ 14BC 100S-C60⊗04BC…C97⊗ 04BC 100S-C60⊗22BC…C97⊗ 22BC 100S-C60⊗14BC…C97⊗ 14BC 100S-C09⊗404BC…C23⊗ 404BC 100S -C09⊗304BC…C23⊗ 304BC 100S-C09⊗322BC…C23⊗ 322BC100S-C09⊗422BC…C23⊗ 422BC

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 29 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100S-C/104S-C Safety Contactors Figure 10 - Safety Reversing Contactors with 3 Main Contacts and Bifurcated Front-mount Auxiliary Contacts 104S-C09⊗012BC…C23⊗ 012BC 104S-C30⊗010BC…C55⊗ 010BC 104S-C09⊗210BC…C23⊗ 210BC 104S-C30⊗210BC…C55⊗ 210BC 104S-C60⊗010BC…C97⊗ 010BC 104S-C60⊗210BC…C97⊗ 210BC

30 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Product Selection—100Q-C Capacitor-switching Contactors Product Selection—100Q-C Capacitor-switching Contactors

  • Compact sizes
  • Limits high inrush currents
  • AC and DC coil control
  • Reversible coil terminals
  • Panel or 35 mm DIN Rail mounting
  • Environmentally friendly materials The Bulletin 100Q-C Capacitor-Switching contactors are designed for switching banks of capacitors. The unique design uses front-mounted resistor elements that limit the severely high inrush currents seen in these applications. This reduces stress to the contactors and the capacitors, as well as allowing a more compact and economical design without the use of air-core reactors. Coil Voltage Codes 100Q-C1611 becomes Cat. No.100Q-C16D11. Maximum Operational Rates
  • 100Q-C16 200 operations/hour
  • 100Q-C37 100 operations/hour For Applications per IEC 60947-4 (AC-6b) Ratings for Switching Capacitor Banks @ 40 °C (104 °F) 20 100Q-C1620 8 8.5 14 14.5 17.5 24 14 14 25 25 30 40 11 100Q-C3711 20 100Q-C3720 For Applications per UL/CSA Ratings for Switching Capacitor Banks 20 100Q-C1620 3.6 7.5 11 12.5 20 25 11 100Q-C3711 20 100Q-C3720 AC Voltages [V] 12 24 32 36 42 48 100 100…110 110 120 127 200 200…220 208 208…240

AC Voltages [V] 220…230 230 230…240 240 277 347 380 380…400 400 400…415 440 480 500 550 600 50 Hz DC Voltages [V] 9 12 24 36 48 60 64 72 80 110 110…125 115 125 220 220…250 230 250 Electronic with Integrated Diode — EQ EJ — — — — — — — ED — — — EA — —

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 31 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories Accessories Auxiliary Contact Blocks Description(1) (1) Max. number of auxiliary co ntacts that may be mounted: Connection Diagrams For Use With Cat. No. N.O. N.C. Standard Auxiliary Contact(2) Bifurcated Auxiliary Contact Auxiliary Contact Blocks for Front Mounting

  • 2- and 4-pole
  • Quick and easy mounting without tools
  • Electronic-compatible contacts down to 17V, 5mA
  • Mechanically linked performance between N.O. and N.C. poles and to the main contactor poles (except for L types)
  • Models with equal function with several terminal numbering choices
  • 1L = Late break N.C. / early make N.O.
  • Bifurcated version for switching down to 5V, 3 mA also available 02 100-C all 100-FA02 100-FAB02 C3000...C9700 100-FB02 100-FBB02 100-C all 100-FA11 100-FAB11 C3000...C9700 100-FB11 100-FBB11 C0910...C2310 100-FC11 100-FCB11 20 100-C all 100-FA20 100-FAB20 C3000...C9700 100-FB20 100-FBB20 1L 1L 100-C all 100-FAL11 — 04 1 0 0 - C a l l 100-FA04 100-FAB04 13 1 0 0 - C a l l 100-FA13 100-FAB13 100-C all 100-FA22 100-FAB22 C3000...C9700 100-FB22 100-FBB22 C0910...C2310 100-FC22 100-FCB22 31 100-C all 100-FA31 100-FAB31 C0910...C2310 100-FC31 100-FCB31 40 1 0 0 - C a l l 100-FA40 100-FAB40 1 + 1L 1+1L 100-C all 100-FAL22 — Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations
  • 1 - a n d 2 - p o l e
  • Two-way numbering for right or left mounting on the contactor
  • Quick and easy mounting without tools
  • Electronic-compatible contacts down to 17V, 10 mA
  • Mirror contact performance to the main contactor poles
  • 1L = Late break N.C. / early make N.O. 01 1 0 0 - C a l l 100-SA01 — 10 1 0 0 - C a l l 100-SA10 — 02 1 0 0 - C a l l 100-SA02 — 11 1 0 0 - C a l l 100-SA11 — 20 1 0 0 - C a l l 100-SA20 — 1L 1L 100-C all 100-SAL11 — Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations
  • 1 - a n d 2 - p o l e
  • Two-way numbering for right or left mounting on the contactor
  • Quick and easy mounting without tools
  • Electronic-compatible contacts down to 17V, 10 mA
  • Mirror contact performance to the main contactor poles
  • 1L = Late break N.C. / early make N.O. 01 1 0 0 - C 100-SB01 — 10 100-C(3) 100-SB10 — 02 100-C(3) 100-SB02 — 11 100-C(3) 100-SB11 — 20 100-C(3) 100-SB20 — 1L 1L 100-C(3) 100-SBL11 —

32 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories Control Modules 120V, 60 Hz: Cat. No. 100-FL11 becomes Cat. No.100-FL11D Timers Description Connection Diagrams For Use With Cat. No. Pneumatic Timing Modules

  • Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay On-Delay 0.3…30 s 100-C or 700-CF with AC or 24V DC electronic coils(1) (1) Cannot be used with side-mounted auxiliary contacts on 700-CF DC relays. 100-FPTA30 2...180 s 100-FPTA180 Off-Delay 0.3...30 s 100-C all, 700-CF all 100-FPTB30 2...180 s 100-FPTB180 Electronic Timing Modules — On-delay
  • Delay of the contactor or control relay solenoid. The contactor or control relay is energized at the end of the delay time. 0.1...3 s 100-C or 700-CF with coils 100-ETA3 1...30 s 100-ETA30 10...180 s 100-ETA180 0.1...3 s 100-C or 700-CF with 24VDC coils 100-ETAZJ3 1...30 s 100-ETAZJ30 10...180 s 100-ETAZJ180 Electronic Timing Modules — Off-delay
  • Delay of the contactor or control relay solenoid. After interruption of the control signal, the contactor or control relay is de-energized at the end of the delay time. 0.3...3 s 100-C09...C37 or 700- CF with 24V 50/60Hz 100-ETBKJ3 1...30 s 100-ETBKJ30 10...180 s 100-ETBKJ180 0.3...3 s 100-C or 700-CF with 110...240V 50/60Hz coils 100-ETB3 1...30 s 100-ETB30 10...180 s 100-ETB180 Electronic Timing Modules
  • Delay of the contactor solenoid. Contactor K 3(Y) is de- energized (off) and K 2 () is energized (on) after the end of the set Y end time. (Switching delay at 50 ms.)
  • Continuous adjustment range
  • High repeat Transition Time Y Contactor 1...30 s 100-C with 110...240V 50/60Hz coils 100-ETY30 Mechanical Interlocks
  • For interlocking of two contactors.
  • Common interlock for most Bul. 100-C contactor sizes
  • Interlocking of different sizes possible
  • Mechanical and electrical in terlocking possible in one module by means of integrated auxiliary contacts
  • 9 mm dovetail connector included Mechanical only, without auxiliary contacts 100-C (except 100- C40, -C90) 100-MCA00 Mechanical/ electrical interlock with 2 N.C. auxiliary contacts 100-C (except 100- C40, -C90) 100-MCA02 Mechanical Latch
  • Following contactor latching, the contactor coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66).
  • Electrical or manual release
  • 1 N.O. + 1 N.C. auxiliary contacts
  • Suitable for all Bul. 100-C contactor sizes, 9...97 A Maximum command duration 0.03...10 s 100-C with AC or 24V DC electronic coils (except 100-C90) 100-FL11 AC Voltages V (1) For special voltages, consult your local Rockwell Au tomation sales office or Allen-Bradley distributor.

50 Hz K Y KP D — VA KA — N G B —

60 Hz J — — — D — KA T — — N B

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 33 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories Additional Control Modules Description Voltage Range Connection Diagrams For Use With Cat. No. DC Interface (Electronic)

  • Interface between the DC control signal (PLC) and the AC operating mechanism of the contactor.
  • Requires no additional surge suppression on the relay coils. Input: 12V DC Output: 110...240V AC 100-C with AC coils 110...240V AC 100-JE12 Input: 18...30V DC Output: 110...240V AC 100-JE Input: 48V DC Output: 110...240V AC 100-JE48 Surge Suppressors
  • For limitation of coil switching transients.
  • Plug-in, coil mounted.
  • Suitable for 100-C contactor sizes, 9...97 A.
  • RC, varistor, and diode versions. RC Module AC operating mechanism 24...48V AC, 50/60 Hz 100-C with Coils 100-FSC48(1) 110...280V AC, 50/60 Hz 100-FSC280(1) 380...480V AC, 50/60 Hz 100-FSC480(1) Varistor Module AC/DC operating mechanism 100-C with AC coils or 100-C09...-C43 with DC coils 100-FSV55(1) 278...575V AC 100-FSV575(1) Diode Module DC operating mechanism 1...30 s 10...180 s 100-C09...-C43 with DC coils 100-FSD250(1) Assembly Components (For 100-C09...C97 contactors) Description For Use With Pkg. Qty. Cat. No. Dovetail Connectors
  • For use in contactor and starter assemblies
  • Single Connector — 0 mm spacing 100-C 10 100-S0 Dovetail Connectors
  • For use in contactor and starter assemblies
  • Single Connector — 9 mm spacing 10 100-S9 Protective Covers
  • Provides protection against unintended manual operation
  • For contactors and front-mounted auxiliary contacts, pneumatic timers, and latches 100-C all 1 100-SCCA 100-FA, -FB, -FC, -FP, -FL 10 100-SCFA Reversing Power Wiring Kits
  • For reversing connection with a solid-state or thermal overload relay 100-C09...C23 1 105-PW23 100-C30...C37 1 105-PW37 100-C43…C55 1 105-PW55 100-C60...C97 1 105-PW85 DIN (#3) symmetrical hat rail
  • 35 x 7.5 x 1 m 140M-D 140M-F 100-C all 199-DR1

34 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories Wye-Delta/Star-Delta Starter Kits Wye-Delta power wiring kits are designed to aid in the field assembly of open-transition Wye-delta starters that use Bulletin 100-C contactors. These kits include line, load, and start-point (shorting) connections. Assembling a Wye-delta starter requires the following additional components:

  • Contactors
  • O v e r l o a d R e l a y
  • Cat. No. 100-MCA02 Mechanical/Electrical In terlock Cat. No. 100-ETY30 Electronic Y-Timer
  • Cat. No. 100-S9 Base Coupler for 1M to 2M contactor (optional) 3-Phase Rating Pkg 230V 380/ 415V 500V 690V 200V 230V 460V 575V Delta Wye 1M 2M 1S 5.5 7.5 7.5 7.5 5 5 10 10 C09 C09 C09 1 170-PW23 7.5 11 11 10 5 7.5 15 15 C12 C12 C09 1 170-PW23 10 15 15 13 7.5 10 20 20 C16 C16 C12 1 170-PW23 13 22 22 18.5 7.5 10 25 25 C23 C23 C12 1 170-PW23 17 25 25 25 10 15 30 30 C30 C30 C16 1 170-PW37 20 37 32 32 15 20 40 40 C37 C37 C23 1 170-PW37 22 40 40 40 20 25 50 50 C43 C43 C30 1 170-PW55 30 45 45 45 25 30 60 60 C55 C55 C37 1 170-PW55 32 55 55 55 30 40 75 75 C60 C60 C37 1 170-PW72 40 63 63 63 40 50 100 100 C72 C72 C43 1 170-PW72 50 80 80 80 50 60 125 125 C85 C85 C60 1 170-PW85 50 90 90 90 50 60 125 125 C97 C97 C60 1 170-PW85 Marking Systems (For 100-C09...C97 contactors) Description Pkg. Qty.(1) (1) Must be ordered in multiples of package quantities Cat. No. Label Sheet
  • 105 self-adhesive paper labels each, 6 x 17 mm 10 100-FMS Marking Tag Sheet
  • 106 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover 10 100-FMP Transparent Cover
  • To be used with marking tag sheets 100 100-FMC Marking Tag Adapters
  • To be used with 1492W marking tag system 100 100-FMA2

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 35 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Accessories Terminal Kits (For 100­C09…C97 contactors) Description Max. Current Ratings and Wire Sizes Pkg. Qty(1) (1) Must be ordered in multiples of the package quantity. Cat. No. Stab Connector Kit

  • Dual stab (0.250 in.) for 100-C coil terminals
  • For 100-C09…C97 contactors 20 199-SC2 Stab Connector Kit
  • Dual stab (0.250 in.) for 100-C power terminals
  • For 100-C09…C23 contactors 100 199-SC10 3-Pole Terminal Lug Kit
  • For Cat. No. 100-C09…C23 (Line side) IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

45 A (4…16 mm

2, fine stranded w/ ferrule)(2)

45 A (4…25 mm2, coarse stranded/solid)

40 A (#10…4 AWG, stranded/solid)

(2) 16 mm 2 max. according to IEC 60947; actual max. 25 mm2 1 100-CTN23 3-Pole Terminal Lug Kit

  • For Cat. No. 100-C09…C23 (Load side) IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

2, fine stranded w/ ferrule)

  • For Cat. No. 100-C30…C37 (Line and load side) IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

60 A (4…16 mm

2, fine stranded w/ ferrule)

60 A (4…25 mm2, coarse stranded/solid)

55 A (#10…4 AWG, stranded/solid)

  • For Cat. No. 100-C43 IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

90 A (6…35 mm

2, fine stranded w/ ferrule)

90 A (6…50 mm2, coarse stranded/solid)

75 A (#8…2 AWG, stranded/solid)

  • For Cat. No. 100-C60…C97 IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

130 A (10…70 mm

2, fine stranded w/ ferrule)

130 A (10…95 mm2, coarse stranded/solid)

130 A (#8…2/0 AWG, stranded/solid)

  • For Cat. No. 100-C09…C23 IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

100 A (35…70 mm

2, fine stranded w/ ferrule)

100 A (35…95 mm2, coarse stranded/solid)

100 A (#0…2/0 AWG, stranded/solid)

  • For Cat. No. 100-C30…C37 IEC @ 40 °C IEC @ 40 °C UL/CSA (Encl.)

150 A (35…70 mm

2, fine stranded w/ ferrule)

150 A (35…95 mm2, coarse stranded/solid)

150 A (#0…2/0 AWG, stranded/solid)

SEMI-F47 Voltage Sag Immunity Module Description Input Voltage For Use With(1) (1) Contactor must have DC coil at the same voltage as AC input. Example: for 24V AC control, select Cat. No. 100-C09ZJ10 (24V DC coil). Options Cat. No. SEMI-F47 Module

  • Meets SEMI-F47 voltage sag immunity requirements
  • Direct mounting to coil terminals of 10 0-C contactors and 700-CF control relays
  • Requires DC coil contactor
  • Optional 1…30 s ON-delay timer version 24…240V AC 100-C60…C97 without timer 100-CSF47 110…240V AC 100-C60…C97 with 1…30 s ON-delay timer 100-CSF47A30

36 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Renewal Parts Renewal Parts Replacement Coils for AC Contactors AC Standard Control Voltages [V] AC Coil Code 100-C09…100-C16 100-C23…100-C37, 100L-C20 100-C40…100-C55 100-C60…100-C85 100-C90…100-C97 —1 2 — Q TA006 TC006 TD006 TE006 TF006 12 — — R TA404 TC404 TD404 TE404 TF404 —2 4 — J TA013 TC013 TD013 TE013 TF013 24 — — K TA407 TC407 TD407 TE407 TF407 ——2 4 K J TA855 TC855 TD855 TE855 TF855 32 36 — V TA481 TC481 TD481 TE481 TF481 36 42 — W TA410 TC410 TD410 TE410 TF410 42 48 — X TA482 TC482 TD482 TE482 TF482 48 — — Y TA414 TC414 TD414 TE414 TF414 ——4 8 K Y TA860 TC860 TD860 TE860 TF860 100 100…110 100 KP TA861 TC861 TD861 TE861 TF861 110 120 — D TA473 TC473 TD473 TE473 TF473 ——1 1 0 K D TA856 TC856 TD856 TE856 TF856 120 — — P TA425 TC425 TD425 TE425 TF425 127 — — S TA428 TC428 TD428 TE428 TF428 200 200…220 200 KG TA862 TC862 TD862 TE862 TF862 —2 0 8 — H TA049 TC049 TD049 TE049 TF049 200…220 208…240 — L TA296 TC296 TD296 TE296 TF296 — — 200…230 KL TA864 TC864 TD864 TE864 — 220 240 — A TA474 TC474 TD474 TE474 TF474 220…230 260 — F TA441 TC441 TD441 TE441 TF441 —— 2 3 0 K F TA851 TC851 TD851 TE851 TF851 230…240 — — VA TA440 TC440 TD440 TE440 TF440 240 277 — T TA480 TC480 TD480 TE480 TF480 —— 2 4 0 K A TA858 TC858 TD858 TE858 TF858 —3 4 7 — I TA065 TC065 TD065 TE065 TF065 —3 8 0 — E TA067 TC067 TD067 TE067 TF067 380…400 440 — N TA071 TC071 TD071 TE071 TF071 —— 4 0 0 K N TA863 TC863 TD863 TE863 TF863 400…415 — — G TA457 TC457 TD457 TE457 TF457 440 480 — B TA475 TC475 TD475 TE475 TF475 — — 440 KB TA859 TC859 TD859 TE859 TF859 500 — — M TA479 TC479 TD479 TE479 TF479 550 600 — C TA476 TC476 TD476 TE476 TF476

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 37 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Renewal Parts Replacement Coils for DC Contactors DC Control Voltage [V] DC Coil Code 100-C09…100-C16, 100Q-C16 100-C23…100-C37, 100Q-C37 100-C40…100-C55 (Series A) 100-C40…100-C55 (Series B) 100-C60…100-C85 100-C90…100-C97 9V Diode(1) (1) Voltage operating range: 0.65…1.3 U s DR — — — — TE766M TF766M 12V Electronic(2) (2) Voltage operating range: 0.7…1.25 U s EQ TC708E TC708E TD708E TD708E2 — — 12V Diode DQ — — — — TE708M TF708M 24V Electronic(2) EJ TC714E TC714E TD714E TD714E2 — — 24V Electronic (3) (3) Faster drop-out time (16…21 ms) QJ TC714Q TC714Q TD714Q TD714Q2 — — 24V Diode(2) DJ — — — — TE714M TF714M 36…48V Electronic(2) EW TC719E TC719E TD719E TD719E2 — — 36V Diode DW — — — — TE719M TF719M 48…72V Electronic EY TC724E TC724E TD724E TD724E2 — — 48V Diode DY — — — — TE724M TF724M 60V Diode DZ — — — — TE774M TF774M 64V Diode DB — — — — TE727M TF727M 72V Diode DG — — — — TE728M TF728M 80V Diode DE — — — — TE729M TF729M 110…125V Electronic (4) (4) Voltage operating range: 0.7…1.25 U s at 110V DC ED TC733E TC733E TD733E TD733E2 — — 110V Diode DD — — — — TE733M TF733M 115V Diode DP — — — — TE734M TF734M 125V Diode DS — — — — TE737M TF737M 220…250V Electronic EA TC747E TC747E TD747E TD747E2 — — 220V Diode DA — — — — TE747M TF747M 230V Diode DF — — — — TE749F TF749F 250V Diode DT — — — — TE751F TF751F

38 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Specifications Table 10 - Main Circuits 100/104-C, 100S/104S-C 09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97 Coil Type: Conventional X X X X X X X X X X X X X X X X Electronic — EI X X X X X X X X X X — — — — — — AC-1 Active Power Load (50 Hz); Ambient temperature 40 °C (104 °F) Rated Operational Current, Ie ≤500V [A] 32 32 32 32(40)(1) (1) Values in () with increase d cross-section and cable lug. 65 65 75 75 85 85 100 100 100 130 130 130 6 9 0 V [ A ] 3 23 23 2 32(40)(1) 65 65 75 75 85 85 100 100 100 130 130 130 Rated Operational Power, P e 230V [kW] 13 13 13 13 26 26 30 30 34 34 40 40 40 52 52 52 240V [kW] 13 13 13 13 27 27 31 31 35 35 42 42 42 54 54 54 400V [kW] 22 22 22 22 45 45 52 52 59 59 69 69 69 90 90 90 415V [kW] 23 23 23 23 47 47 54 54 61 61 72 72 72 93 93 93 500V [kW] 28 28 28 28 56 56 65 65 74 74 87 87 87 113 113 113 690V [kW] 38 38 38 38 78 78 90 90 102 102 120 120 120 155 155 155 AC-1 Active Power Load (50 Hz); Ambient temperature 60 °C (140 °F) Rated Operational Current, Ie ≤500V [A] 32 32 32 32 65 65 60 60 75 75 100 100 100 110 110 110 6 9 0 V [ A ] 3 23 23 2 3 2 6 56 5 6 0 6 0 7 57 5 1 0 0 1 0 0 1 0 01 1 0 1 1 0 1 1 0 Rated Operational Power, P e 230V [kW] 13 13 13 13 26 26 24 24 25 25 40 40 40 44 44 44 240V [kW] 13 13 13 13 27 27 25 25 26 26 42 42 42 46 46 46 400V [kW] 22 22 22 22 45 45 42 42 44 44 69 69 69 76 76 76 415V [kW] 23 23 23 23 47 47 43 43 45 45 72 72 72 79 79 79 500V [kW] 28 28 28 28 56 56 52 52 55 55 87 87 87 95 95 95 690V [kW] 38 38 38 38 78 78 72 72 75 75 120 120 120 131 131 131 Switching of 3-phase Motors; (50 Hz) Ambient temperature 60 °C (140 °F), AC-2, AC-3 Rated Operational Current, Ie 230V [A] 12 15 20 26.5 35 38 38 38 44 56 62 72 85 85 85 96 240V [A] 12 15 20 26.5 35 38 38 38 44 56 62 72 85 85 85 95 400V [A] 9 12 16 23 30 37 37 37 43 55 60 72 85 85 85 97 415V [A] 9 12 16 23 30 37 37 37 43 55 60 72 85 85 85 97 500V [A] 7 10 14 20 25 30 29 30 38 44 55 67 80 80 80 78 690V [A] 5 7 9 12 18 21 9 21 25 25 34 42 49 22 49 57 Rated Operational Power, Pe 230V [kW] 3 4 5.5 7.5 10 11 11 11 13 15 18.5 22 25 25 25 30 240V [kW] 3 4 5.5 7.5 10 11 11 11 13 15 18.5 22 25 25 25 30 415V [kW] 4 5.5 7.5 11 15 20 20 20 22 30 32 40 45 45 45 55 500V [kW] 4 5.5 7.5 13 15 20 18.5 20 25 30 37 45 55 55 55 55 Load Carrying Capacity per UL/CSA General Purpose Current (enclosed) [ A ] 2 5 2 5 3 03 05 5 6 06 0 6 07 5 7 5 9 0 9 0 1 0 0 1 2 51 3 0 1 2 0 Rated current (enclosed), 1-phase 115V [A] 9.8 9.8 16 24 24 34 34 34 34 56 56 56 80 80 80 100 2 3 0 V [ A ] 1 0 1 2 1 7 1 7 2 8 2 8 2 82 8 4 0 5 0 5 0 6 8 6 8 6 86 8 8 8 Rated power (enclosed), 1-phase 230V [Hp] 1.5 2 3 3 5 5 5 5 7.5 10 10 15 15 15 15 20 Rated current (enclosed), 3-phase 230V [A] 6.8 9.6 15.2 22 28 28 28 28 42 54 54 68 80 80 80 80 460V [A] 7.6 11 14 21 27 34 34 34 40 52 52 65 77 65 77 96 575V [A] 9 11 17 17 27 32 17 32 32 41 52 62 62 22 52 77 Rated power (enclosed), 3-phase 2 0 0 V [ H p ] 235 57 . 5 1 01 0 1 01 0 1 5 1 5 2 0 2 5 2 5 2 53 0 230V [Hp] 2 3 5 7.5 10 10 10 10 15 20 20 25 30 30 30 30 460V [Hp] 5 7.5 10 15 20 25 25 25 30 40 40 50 60 50 60 75 5 7 5 V [ H p ] 7 . 51 0 1 5 1 5 2 53 0 1 5 3 0 3 04 05 06 06 0 2 0 5 0 7 5

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 39 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 11 - Main Circuits 100/104-C, 100S/104S-C 09 12 16 23 30 37 43 55 60 72 85 97 Coil Type: Conventional X X X X X X X X X X X X Electronic — EI X X X X X X X X — — — — Switching of 3-phase Motors, (50 Hz); Ambient temperature 60 °C (140 °F), AC-4 Rated Operational Current, Ie 2 3 0 V [ A ] 1 2 1 52 0 2 6 . 5 3 53 8 4 4 5 6 6 27 28 59 6 2 4 0 V [ A ] 1 2 1 52 0 2 6 . 5 3 53 8 4 4 5 6 6 27 28 59 5 400V [A] 9 12 16 23 30 37 43 55 60 72 85 97 415V [A] 9 12 16 23 30 37 43 55 60 72 85 97 500V [A] 7 10 14 20 25 30 38 44 55 67 80 78 690V [A] 5 7 9 12 18 21 25 25 34 42 49 57 Rated Operational Power, P e 230V [kW] 3 4 5.5 7.5 10 11 13 15 18.5 22 25 30 240V [kW] 3 4 5.5 7.5 10 11 13 15 18.5 22 25 30 400V [kW] 4 5.5 7.5 11 15 18.5 22 30 32 40 45 55 415V [kW] 4 5.5 7.5 11 15 20 22 30 32 40 45 55 500V [kW] 4 5.5 7.5 13 15 20 25 30 37 45 55 55 690V [kW] 4 5.5 7.5 10 15 18.5 22 22 32 40 45 55 AC-4 at approximately 200,000 operations Rated Operational Current, I e 230V [A] 4.3 6.6 9 9 12 14 16.5 22 25.5 31 38 44 240V [A] 4.3 6.6 9 9 12 14 16.5 22 25.5 31 38 44 400/415V [A] 4.3 6.6 9 9 12 14 16.5 22 25.5 31 38 44 500V [A] 4.3 6.6 9 9 12 14 16.5 22 25.5 31 38 44 690V [A] 4.3 6.6 9 9 12 14 16.5 22 25.5 31 38 44 Rated Operational Power, P e 230V (1) (1) Power ratings at 50 Hz: Preferred values according to IEC 60072-1 400V (1) [kW] 1.8 3 4 4 5.5 6.3 7.5 11 13 15 20 22 415V (1) [kW] 1.8 3 4 4 5.5 6.3 7.5 11 13 17 20 22 690V (1) [kW] 3 5.5 7.5 7.5 10 11 15 18.5 22 25 32 37 Max. switching frequency Ops/hour 250 250 220 200 200 200 200 200 120 120 120 120 Wye-Delta (60 Hz) Rated Operational Power 200V [Hp] 5 5 7-1/2 7-1/2 10 15 20 25 30 40 50 50 230V [Hp] 5 7-1/2 10 10 15 20 25 30 40 50 60 60 460V [Hp] 10 15 20 25 30 40 50 60 75 100 125 125 575V [Hp] 10 15 20 25 30 40 50 60 75 100 125 125 UL/CSA Elevator Duty Rated Operational Current UL/CSA Elevator Duty Rated Operational Power 2 0 0 V[ H p ] 2335 7 - 1 / 2 7 - 1 / 2 1 0 T B D 1 0 1 5 2 0 T B D 230V [Hp] 2 3 5 5 7-1/2 10 10 TBD 15 20 25 TBD 460V [Hp] 5 7-1/2 10 15 20 20 25 TBD 30 40 50 TBD 575V [Hp] 5 7-1/2 10 15 20 25 30 TBD 40 50 60 TBD

40 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 12 - Main Circuits 100/104-C, 100S/104S-C 09 12 16 23 30 37 43 55 60 72 85 97 Coil Type: Conventional X X X X X X X X X X X X Electronic — EI X X X X X X X X — — — — Star-Delta Starting (50 Hz) Rated Operational Current, Ie ≤ 230V [A] 21 26 35 46 61 66 76 96 107 125 147 166 ≤ 240V [A] 21 26 35 46 61 66 76 96 107 125 47 165 400V [A] 16 21 28 40 52 64 74 95.3 104 125 147 168 415V [A] 16 21 28 40 52 64 74 95.3 104 125 47 168 500V [A] 12 17 24 35 43 52 66 76.2 95 116 139 135 690V [A] 8.6 12 16 21 31 36 43 55.4 59 73 85 99 Rated Operational Power, P e 230V (1) (1) Power ratings at 50 Hz: Preferred values according to IEC 60072-1 [kW] 5.5 7.5 10 13 17 20 22 30 32 37 45 50 240V (1) [kW] 5.5 7.5 10 13 18.5 20 22 30 32 40 50 50 400V (1) [kW] 7.5 10 13 20 25 32 40 45 55 63 80 90 415V (1) [kW] 7.5 11 15 22 25 32 40 45 55 63 80 90 500V (1) [kW] 7.5 11 15 22 25 32 45 45 63 80 90 90 690V (1) [kW] 7.5 10 13 18.5 25 32 40 45 55 63 80 90 Switching of Power Transformers, AC-6a (50 Hz)) n= 30 Apparent Power 5 0 0 V[ k V A ] 9 . 4 9 . 4 9 . 4 9 . 41 7 1 7 2 0 2 0 3 53 53 54 2 6 9 0 V[ k V A ] 1 31 31 31 32 4 2 42 7 2 74 9 4 9 4 9 5 8 n = 1 5 ≤ 6 9 0 V [ A ] 2 22 22 22 24 04 0 4 6 4 6 8 28 28 29 7

60 Hz Peak Inrush/peak rated transformer current

Rated transformer current = n

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 41 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 13 - Main Circuits 100/104-C, 100S/104S-C 09 12 16 23 30 37 43 55 60 72 85 97 Coil Type: Conventional X X X X X X X X X X X X Electronic — EI X X X X X X X X — — — — n = 1 5 [ A ] 2 22 22 22 24 04 0 4 6 4 6 8 28 28 29 7 Apparent Power Table 14 - Main Circuits 100/104-C, 100S/104S-C 09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97 Coil Type: Conventional X X X X X X X X X X X X X X X X Electronic — EI X X X X X X X X X X — — — — — — Switching of 3-phase Capacitors, AC-6b (50 Hz)(1) (1) Inductance of leads between capacitors in paralle l: min. 6 µH (100-C09…C30 contactors: min 30 µH) Single capacitor 40 °C (104 °F) 230V [kVAR] 8 8 8.5 9 14 14 — — 24 24 28 28 28 — — 28 240V [kVAR] 8 8 8.5 9 14 14 — — 25 25 29 29 29 — — 29 400V [kVAR] 8 8 10 12.5 20 24 — — 35 35 48 48 48 — — 48 415V [kVAR] 8 8 10 12.5 20 25 — — 35 35 50 50 50 — — 50 500V [kVAR] 8 8 10 12.5 20 25 — — 35 35 50 55 60 — — 60 690V [kVAR] 8 8 10 12.5 20 25 — — 35 35 50 55 60 — — 60 Single capacitor 60 °C (140 °F) 230V [kVAR] 8 8 8.5 9 12.5 12.5 — — 18 18 28 28 28 — — 28 240V [kVAR] 8 8 8.5 9 12.5 12.5 — — 18 18 29 29 29 — — 29 400V [kVAR] 8 8 10 12.5 20 21.5 — — 30 30 42 48 48 — — 48 415V [kVAR] 8 8 10 12.5 20 22 — — 30 30 42 50 50 — — 50 500V [kVAR] 8 8 10 12.5 20 25 — — 30 30 42 50 55 — — 55 690V [kVAR] 8 8 10 12.5 20 25 — — 30 30 42 50 55 — — 55 Group capacitors 40 °C (104 °F) 230V [kVAR] 5 5 8 9 12.5 14 — — 20 20 28 28 28 — — 28 240V [kVAR] 5 5 8 9 12.5 14 — — 20 20 29 29 29 — — 29 400V [kVAR] 5 5 8 10 15 20 — — 25 25 40 48 48 — — 48 415V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50 500V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50 690V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50 Group capacitors 60 °C (140 °F) 230V [kVAR] 5 5 8 9 12.5 12.5 — — 18 18 28 28 28 — — 28 240V [kVAR] 5 5 8 9 12.5 12.5 — — 18 18 29 29 29 — — 29 400V [kVAR] 5 5 8 10 15 20 — — 25 25 40 48 48 — — 48 415V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50 500V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50 690V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50

60 Hz Single Capacitor

— 40 °C (104 °F) 200V [kVAR] 5 5 8 9 12.5 14 — — 20 20 28 28 28 — — 28 230V [kVAR] 5 5 8 9 12.5 14 — — 20 20 29 29 29 — — 29 460V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50 600V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50

60 Hz Group

Capacitors — 40 °C (104 °F) 200V [kVAR] 5 5 8 9 12.5 12.5 — — 18 18 28 28 28 — — 28 230V [kVAR] 5 5 8 9 12.5 12.5 — — 18 18 29 29 29 — — 29 460V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50 600V [kVAR] 5 5 8 10 15 20 — — 25 25 40 50 50 — — 50

42 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 15 - Main Circuits 100/104-C, 100S/104S-C 09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97 Coil Type: Conventional X X X X X X X X X X X X X X X X Electronic — EI X X X X X X X X X X — — — — — — Switching of Lamps Gas discharge lamps AC-5a, 40 °C (104 °F) open [A] 22.5 25 28 29 40.5 45 65 65 77 77 81 85 90 115 115 115 enclosed [A] 22.5 25 28 29 37 41 54 54 57 57 77 81 90 95 95 100 Individually compensated: Max. capacitance at expected Short-circuit current of 10 kA [µF] 1000 1000 1000 1000 2700 2700 — — 3200 3200 4000 4000 4700 — — 4700 20 kA [µF] 500 500 500 500 1350 1350 — — 1600 1600 2000 2000 2350 — — 2350 50 kA [µF] 200 200 200 200 540 540 — — 640 640 800 800 940 — — 940 Filament AC-5b 230/240V [A] 12 16 18 22 30 37 18 25 43 51 60 70 76 60 75 90 Switching of Low Inductive Loads in Home Appliances and Similar Applications per IEC 61095 (50 Hz) AC-7a 2 3 0 V [ A ] 3 23 23 23 24 54 5 — — 6 36 3 — — — — — — 4 0 0 V [ A ] 3 23 23 23 24 54 5 — — 6 36 3 — — — — — — 440V [A] 32 32 32 32 45 45 — — 63 63 — — — — — — Switching of Motor Load for Home Appliances (50 Hz) AC-7b Switching of Hermetically Sealed Cooling Compressor Motors - manual reset of overload release (50 Hz) AC-8a 400V [A] 12 16 22 32 38 45 — — 63 63 72 85 100 — — 115 500V [A] 12 16 22 32 38 45 — — 63 63 72 85 100 — — 115 690V [A] 8 10 14 20 28 35 — — 42 42 56 67 80 — — 90 - automatic reset of overload release AC-8b 400V [A] 5.5 7 9.3 12 13 14 — — 16 16 24 30 35 — — 35 500V [A] 5.5 7 9.3 12 13 14 — — 16 16 24 30 35 — — 35 690V [A] 5.5 7 9.3 12 13 14 — — 16 16 24 30 35 — — 35 Switching of DC Loads Non-inductive or slightly inductive loads or resistance furnaces DC-1, 60 °C (140 °F) 1 pole 24V [A] 25 25 32 32 45 45 45 45 50 50 70 80 80 80 80 80 4 8 / 6 0 V [ A ] 2 02 02 02 02 52 5 2 5 2 5 3 03 04 04 04 0 4 0 4 0 4 0 1 1 0 V [ A ] 666688 1 0 1 0 991 11 11 1 1 1 1 1 1 1 2 poles in series 24V [A] 25 25 32 32 45 45 45 45 50 50 70 80 80 80 80 80 4 8 / 6 0 V [ A ] 2 52 53 23 24 54 5 4 5 4 5 5 05 07 08 08 0 8 0 8 0 8 0 1 1 0 V [ A ] 2 52 53 23 24 54 5 4 5 4 5 5 05 07 08 08 0 8 0 8 0 8 0 220V [A] 8 8 8 10 10 10 10 10 10 10 15 15 15 15 15 15 3 poles in series 24V [A] 25 25 32 32 45 45 — 45 63 63 90 90 100 — 100 100 4 8 / 6 0 V [ A ] 2 52 53 23 24 54 5 — 4 5 6 36 39 09 0 1 0 0 — 1 0 01 0 0 1 1 0 V [ A ] 2 52 53 23 24 54 5 — 4 5 6 36 39 09 0 1 0 0 — 1 0 01 0 0 220V [A] 25 25 32 32 45 45 — 45 50 50 70 80 80 — 80 80 4 4 0 V [ A ] 3333 3 . 5 3 . 5— 3 . 544555 — 5 5

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 43 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 16 - Main Circuits 100/104-C, 100S/104S-C 09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97 Coil Type: Conventional X X X X X X X X X X X X X X X X Electronic — EI X X X X X X X X X X — — — — — — Switching of DC Loads, Continued Shunt-wound Motors, Starting, reverse current braking, reversing, stepping DC-3, 60 °C (140 °F) 3 poles in series 24V [A] 25 25 32 32 45 45 — — 63 63 90 90 100 — — 100 48/60V [A] 25 25 32 32 45 45 — — 50 50 70 70 80 — — 80 110V [A] 20 20 25 25 30 30 — — 35 35 70 70 80 — — 80 220V [A] 6 6 6 10 15 15 — — 20 20 25 25 30 — — 30 Series-wound Motors, Starting, reverse current braking, reversing, stepping DC-5, 60 °C (140 °F) 3 poles in series 24V [A] 25 25 32 32 45 45 — — 63 63 90 90 100 — — 100 48/60V [A] 25 25 32 32 45 45 — — 50 50 70 70 80 — — 80 110V [A] 20 20 25 25 30 30 — — 35 35 70 70 80 — — 80 220V [A] 6 6 6 10 15 15 — — 20 20 25 25 30 — — 30 Short Time Withstand ICW, 60 °C (140 °F) 10 s [A] 170 170 170 215 300 304 304 304 375 375 700 700 700 700 700 840 Resistance and Power Dissipation Main current circuit Power dissipation by all circuits at I Total power dissipation At I e AC-3/400V AC DC control (conv.) DC control (elect.) Lifespan Mechanical AC control [ M i l l i o n o p s . ] 1 31 31 31 31 31 3 1 0 1 0 1 21 2 6 6 6 6 6 6 Mechanical DC control [ M i l l i o n o p s . ] 1 31 31 31 31 31 3 1 0 1 0 1 31 3 6 6 6 6 6 6 Electrical AC-3 Weight AC Non- Rev. [kg (lbs)] 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.39 (0.86) 0.48 (1.06) 0.49 (1.08) 0.63 (1.39) 0.63 (1.39) 0.51 (1.12) 0.51 (1.12) 1.45 (3.20) 1.45 (3.20) 1.45 (3.20) —— 1.45 (3.20) Rev. [kg (lbs)] 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 0.85 (1.89) 1.08 (2.39) 1.08 (2.39) —— 1.15 (2.54) 1.15 (2.54) 3.14 (6.92) 3.14 (6.92) 3.14 (6.92) —— 3.14 (6.92) DC Non- Rev. [kg (lbs)] 0.6 (3.24) 1.47 (3.24) 1.47 (3.24) —— 1.4 (3.24) Rev. [kg (lbs)] 1.27 (7.1) 3.22 (7.1) 3.22 (7.1) —— 3.22 (7.1) DC (Electronic-EQ, EJ) Non- Rev. [kg (lbs)] — 0.40 (0.88) 0.40 (0.88) 0.40 (0.88) 0.40 (0.88) 0.49 (1.08) 0.49 (1.08) 0.57 (1.25) 0.57 (1.25) 0.57 (1.25) 0.57 Rev. [kg (lbs)] — 0.87 (1.91) 0.87 (1.91) 0.87 (1.91) 0.87 (1.91) 1.08 (2.39) 1.08 (2.39) —— 1.27 (2.79) 1.27 DC (Electronic- EW, EY, ED, EA) Non- Rev. [kg (lbs)] — 0.43 (0.95) 0.43 (0.95) 0.43 (0.95) 0.43 (0.95) 0.52 (1.14) 0.52 (1.14) 0.60 (1.32) 0.60 (1.32) 0.60 (1.32) 0.60 Rev. [kg (lbs)] — 0.93 (2.05) (2.05) 0.93 (2.05) 0.93 (2.05) 1.14 (2.51) 1.14 (2.51) —— 1.33 (2.93) 1.33

44 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 17 - Conductors 100/104-C, 100S/104S-C 09 12 16 23 30 37 40 43 55 60 72 85 90 97 Coil Type: Conventional X X X X X X X X X X X X X X Electronic — EI X X X X X X X X X — — — — — Conductor Cross Sections - Main Contacts Terminal type (1) (1) Pozidriv No. 2 / Blade No. 3 screw (2) (2) Pozidriv No. 2 / Blade No. 4 screw (3) (3) Hexagonal socket screw 1 conductor [mm2] 1…4 2.5…10 2.5…16 2.5…35 2 conductors [mm2] 1…4 2.5…10 2.5…10 2.5…25 1 conductor [mm2] 1.5…6 2.5…16 2.5…25 2.5…50 2 conductors [mm2] 1.5…6 2.5…16 2.5…16 2.5…35 Cross section per UL/CSA [AWG] 16…10 14…4 14…6 14…4 14…1 Recommended torque [lb•in] 13.3…17.7 22…31 22…31 40…53 Conductor Cross Sections - Coil Terminal type (1) 1 conductor [mm2] 1…2.5 2 conductors [mm2] 1…2.5 1 conductor [mm2] 1…4 2 conductors [mm2] 1…4 Recommended torque [N•m] 1…1.5 Cross section per UL/CSA [AWG] 16…12 Recommended torque [lb•in] 9…13

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 45 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 18 - Short-Circuit Coordination Data(1) (1) See the Rockwell Automation Global SCCR Tool at rok.auto/sccr for complete short-circuit current ratings. 100/104-C, 100S/104S-C 09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97 Coil Type: Conventional X X X X X X X X X X X X X X X X Electronic - EI X X X X X X X X X X — — — — — — Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1 (contactor and fuses only) DIN Fuses- gG, gL 50 kA Available Fault Current Type"1"(690V) [A] 50 50 50 80 125 125 160 160 160 160 250 250 250 250 250 250 Type"2"(400V) [A] 25 35 35 40 80 80 63 80 100 100 160 160 160 160 100 200 Type"2"(690V) [A] 25 35 35 40 80 80 63 80 100 100 160 160 160 160 100 200 BS88Fuses 65kA Available Fault Current Type"1"(415V) [A] 25 32 40 50 63 80 — — 80 TBD 100 160 160 — — TBD Type"2"(415V) [A] 20 25 32 50 63 80 — — 80 TBD 100 125 160 — — TBD Per UL 508 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only) UL Class K5 and RK5 Fuses UL Listed Combination (600V) 5 kA Available Fault Current [A] 35 40 70 90 110 125 125 125 150 200 200 — — — — — 10 kA Available Fault Current UL Class CC and CSA HRCI-MISC Fuses UL verified combination to IEC60947-4-1 "Type2" 100 kA Available Fault Current [A] 20 (2) (2) 15 A max. fuse for Type 2 coordination. UL Class J and CSA HRCI-J Fuses UL verified combination to IEC60947-4-1 "Type 2" 100 kA Available Fault Current [A] 20 (2) 20 30 40 50 50 — — 70 80 80 100 150 — — 175 UL Inverse-time Circuit Breaker UL Listed Combination (480V) 5 kA Available Fault Current [ A ] 3 03 05 05 0 1 2 5 1 2 5 — — 1 2 5 1 5 0 2 5 0— — — — — UL Listed Combination (600V) 10 kA Available Fault Current 18 kA Available Fault Current UL Listed Combination (600Y/347V) 25 kA Available Fault Current [A] 30 (3) (3) Ratings apply when used with Bull etin 140U-D circuit breakers only. (4) Minimum enclosure size 12 -3/8 x 7-5/8 s 7-1/4 inches UL Listed Combination (600V) [A] — — — — 100 (5) (5) Minimum enclosure size 20 x 12 x 8 inches with two latches. UL Listed Combination (480V) 50 kA Available Fault Current [A] — — — — 50 UL Listed Combination (480Y/ 277V) 65 kA Available Fault Current [A] 30 UL Listed Combination (480V) [A] — — — — 100

46 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 19 - Coil Data 100/104-C, 100S/104S-C 09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97 Coil Type: Conventional X X X X X X X X X X X X X X X X Electronic - EI X X X X X X X X X X — — — — — — Operating Limits

50 Hz, 60 Hz,

DC (conventional) pick-up [x Us] —— 0 . 8 … 1 . 1 dropout [x Us] — — 0.1…0.6 DC (electronic—EQ, EJ, EW, QJ) pick-up [x U s] 0.7…1.25 — dropout [x Us] 0.3…0.4 — DC (electronic—EY) pick-up [x Us] 0.8…1.25 — dropout [x Us] 0.3…0.4 — DC (electronic—ED) pick-up [x Us] 0.7…1.12(1) — dropout [x Us] 0.3…0.4 — DC (electronic—EA) pick-up [x Us] 0.8…1.1 — dropout [x Us] 0.3…0.4 — Coil Consumption pick-up [VA] 75 105 135 235 400 DC (conventional) pick-up [W] — — — 200 325 hold-in [W] — — — 4 5 DC (electronic—EQ, EJ, QJ) pick-up (avg/peak) [W] 10/17 16/25 — — hold-in [W] 1.7 2.5 — — DC (electronic—EY, EW) pick-up (avg/peak) [W] 10/17 16/25 — — hold-in [W] 1.9 2.7 — — DC (electronic—ED) pick-up (avg/peak) [W] 12/19 16/26 — — hold-in [W] 2.1 2.8 — — DC (electronic—EA) pick-up (avg/peak) [W] 14/22 18/29 — — hold-in [W] 3.0 4.0 — — Operating Times AC closing delay [ms] 15…30 15…30 15…30 15…30 20…40 20…40 opening delay [ms] 10…60 10…60 10…60 10…60 10…60 20…40 With RC module closing delay [ms] 1 0…60 10…60 10…60 10…60 10…60 10…60 20…40 DC (conventional) opening delay [ms] — — — — 50…80 20…40 15…25 20…25 20…25 closing delay [ms] — — — — 7…15 20…40 15…25 20…25 20…25 With integrated diode opening delay [ms] — — — — 17…23 ≤ 220V 20…35 ≤ 220V 20…35 With external diode opening delay [ms] — — — — — 80…125 — — DC (electronic—EQ, EJ) closing delay [ms] 20…50 — — — opening delay [ms] 20…50 — — — Max. Ripple ±15% — — — min. OFF time [ms] 50 — — — DC (electronic—EW, EY, ED, EA) closing delay [ms] 20…50 — — — opening delay [ms] 23…33 — — — Max. Ripple ±15% — — — min. OFF time [ms] 50 — — —

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 47 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications DC (electronic—QJ) c losing delay [ms] 20…50 — — — opening delay [ms] 16…21 — — — Max. Ripple ±15% — — — min. OFF time [ms] 50 — — — (1) 0.7…1.25 at 110V DC Table 20 - Auxiliary Contacts, Auxiliary Contact Blocks, and Pneumatic Timers Internal Front mounted Front mounted (Bifurcated) Side-mounted Switching of AC Loads AC-12 Ith at 40 °C (104 °F) [A] 20 10 10 10 at 60 °C (140 °F) [A] 20 6 6 6 AC-15 at rated voltage of 24V [A] 10 6 3 6 42/48V [A] 10 6 3 6 120V [A] 10 6 3 6 230V [A] 10 5.5 3 5.5 240V [A] 10 5 3 5 400V [A] 6 3 2 3 415V [A] 6 3 2 3 500V [A] 2.5 1.6 1.2 1.6 690V [A] 1 1 0.7 1 Switching of DC Loads DC-12 L/R < 1 ms resistive loads at 24V DC [A] 12 12 6 6 48V DC [A] 9 9 3.2 3.2 110V DC [A] 3.5 3.5 1 1 220V DC [A] 0.55 0.55 0.5 0.5 440V DC [A] 0.2 0.2 0.2 0.2 DC-14L/R <15 ms inductive loads with economy resistor in series at 24V DC [A] 9 9 2 2 48V DC [A] 5 5 1.6 1.6 110V DC [A] 2 2 0.3 0.3 220V DC [A] 0.4 0.4 0.12 0.12 440V DC [A] 0.16 0.16 0.05 0.05 DC-13 switching electromagnets at 24V DC [A] 5 5 2.5 5 48V DC [A] 3 3 1.5 2.5 110V DC [A] 1.2 1.2 0.6 0.68 220V DC [A] 0.6 0.6 0.3 0.32 440V DC [A] 0.3 0.15 0.15 0.15 Fuse gG Short-circuit protection with no welding of contacts per IEC 60947-5-1 [A] 2 0 1 01 01 0 [A] 2 0 1 01 01 0 Protective Separation per IEC 60947-1, Annex N between load and auxiliary circuit 320V between load and auxiliary circuit 440V Min. switching capacity according to IEC 60947-5-4 17V/10mA 17V/5mA 5V/3mA 17V/10mA Load Carrying Capacity per UL/CSA Rated voltage AC [V] max.600 Continuous rating 40 °C (104 °F) [A] 10 10 10 10 Switching capacity AC [A] A600 Rated voltage DC [V] max.600 Switching capacity DC [A] P600 Q600 Q600 Table 19 - Coil Data (Continued) 100/104-C, 100S/104S-C 09 12 16 23 30 37 40*200 40*400 43 55 60 72 85 90*200 90*400 97 Coil Type: Conventional X X X X X X X X X X X X X X X X Electronic - EI X X X X X X X X X X — — — — — —

48 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Specifications Table 21 - General Specifications Attribute Value Rated Isolation Voltage Ui IEC [V] 690 UL, CSA [V] 600 Rated Impulse Voltage Withstand Uimp [kV] 6 Rated Voltage Ue AC 50/60 Hz [V] 115, 200, 230, 240, 400, 415, 460, 500, 575, 690 DC [V] 24, 48, 110, 220, 440 Insulation Class of the Coil Class F per IEC 60085, UL Class 105 Rated coil frequency AC 50/60Hz, DC Ambient Temperature Operation at rated voltage [ °C ( °F)] -40…+60 (-40…140) at 70 °C (158 °F) 15% current reduction against 60 °C (140 °F) values Climatic Withstand IEC 60068-2-1/-2/-30 Max. Altitude of Installation Site [m] 2000 NN, per IEC60947-1 Protection Class 100-C09…C23: IP2X from all directions 100-C30…C55: IP2X from front with front (upper) terminal wired 100-C60…C97: IP2X from front with front (upper) terminal wired (min. wire size 16 mm2 or #6 AWG) Single contactor cover — Contactor with frame terminal block — Auxiliary contact IP2X Protection against Accidental Contact Finger- and back-of-hand proof per VDE0106, part100 Resistance to Shock IEC60068-2-27 Resistance to Vibration IEC60068-2-6 Mechanically Linked Contacts IEC60947-5-1,Annex L 100-/100S-C09…C55+100-FA/-FB/-FC, (e xcept L11, L22),100-/100S-C09…C55+ 100-FAB/-FBB/-FCB Mirror Contacts IEC60947-4 Annex F 100-/100S-C09…C97+100-FA/-FB/-FC, (except L11, L22),100-/100S-C09…C97+ 100-SA/SB, 100-/100S-C09…C97+100-FAB/-FBB/-FCB Table 22 - Standards Compliance and Certifications Standards Compliance Certifications Standards Compliance Certifications 100-C IEC Contactors 100Q-C Capacitor-switching Contactors EN/IEC 60947-4-1, 60947-5-1 CE Marked IEC 60947-4 CE Marked IEC 60947 Type “2” Coordination CCC CSA C22.2 No. 14 cULus Listed (File No. E 41850, Guide NLDX, NLDX7) CSA 22.2. No. 14 cULus Listed (File No. E3125; Guide NLDX, NLDX7) UL 508 UL 508 Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS 100S-C IEC Safety Contactors EN50205 CE Marked CSA C22.2 No. 14 SUVA Third-Party Certified UL 508 cULus Listed (File No. E3125; Guide NLDX, NLDX7) EN/IEC 60947-4 IEC 60947-4-1 Annex F — Mirror Contacts IEC 60947-5-1 Annex L — Mechanically Linked Contacts Meets the material restrictions for European Directive 2002/95/IEC-EU-RoHS

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 49 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves Life-Load Curves Bulletin 100-C/104-C IEC contactors are designed for superior performance in a wide variety of applications. When selecting IEC products, the user must give consideration to the specific load, utilization category, and required electrical life of the application. The life-load curves shown here are based on Rockwell Automation tests according to the requirements defined in IEC 60947-4-1. Since contact life in application is dependent on environmental conditions and duty cycle, actual application contact life may vary from that indicated by the curves shown here. To find the estimated electrical life of the contactor, follow these guidelines: 1. Identify the appropriate utilization category from Table 23. 2. Choose the graph for the utilization category selected. 3. Locate the intersection of the life-load curve for the appropriate contactor with the application’s operational current (Ie) found on the horizontal axis. 4. Read the estimated contact life along the vertical axis. Contact Life for Mixed Utilization Categories AC-3 and AC-4: In many applications, the utilization category cannot be defined as either purely AC-3 or AC-4. In those applications, the electrical life of the contactor can be estimated from the following equation: Lmixed = Lac3/[1 + Pac4*(Lac3/Lac4 – 1)], where: Lmixed = Approximate contact life in operations for a mixed AC-3/AC-4 utilization category application Lac3 = Approximate contact life in operations for a pure AC-3 utilization category (from the AC-3 life-load curves) Lac4 = Approximate contact life in operations for a pure AC-4 utilization category (from the AC-4 life-load curves) Pac4 = Percentage of AC-4 operations Table 23 - Utilization Category Determination Test Conditions Making Breaking I/Ie U/Ue cos Ic/Ie Ur/Ue cos AC-1 Resistance Furnaces: Non inductive or slightly inductive loads 11 0 . 9 5 11 0 . 9 5 AC-2 Slip-ring motors: Starting and reversing 2.5 1 0.65 2.5 1 0.65 AC-3 Squirrel-cage motors: Starting and stopping of running motors I e < 17 A Ie > 17 A 0.65 0.35 0.17 0.17 0.65 0.35 AC-4 Squirrel-cage motors: Starting, plugging (1), inching(2) (1) Plugging is understood as stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running. (2) Inching (jogging) is understood as energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism. Ie < 17 A Ie > 17 A 0.65 0.35 0.65 0.35 AC-15 Solenoids: Contactors, valves and lifting magnets 10 1 0.7 1 1 0.4

  • I e Rated operational current • Ic Breaking Current • U e Rated voltage
  • I Making Current • U Off-load voltage •U r Recovery voltage

50 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves Figure 11 - AC-1, 40 °C (104 °F) Non- or slightly inductive loads, resistance furnaces; Ue = 230…690V Figure 12 - AC-2, Switching of slip-ring motors; Ue = 230…400…460V 10E+04 01E+06 10E+06 0 0010 0 10 11 Rated operating current Ie AC-1 [A] Operating cycles C09 C12 C37 C23 C16 C60 C43 C90 C40 C30 C72 C85 C97 / C90 10E+04 01E+06 10E+06 0 0 1011 Rated operating current I e AC-2 [A] Operating cycles C09 C85C72C60 C43C37C30C23C16 C12 C97

52 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves Figure 15 - AC-3, Switching of squirrel-cage motors while starting; Ue = 690V Figure 16 - AC-4, Switching of squirrel-cage motors; Ue = 230…690V 10E+04 01E+06 10E+06 0 0 10 11 Rated operational current Ie AC-3 [A] Operating cycles C09 C12 C16 C23 C30 C37 C43 C60 C72 C85 C97 01E+04 10E+04 01E+06 10E+06 0 01011 Rated operating current Ie AC-4 [A] Operating cycles C09 C85 C72 C60 C43 C37 C30 C23 C16 C12 C97

54 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Life-Load Curves Maximum Operating Rates Figure 19 - AC-1, 40 °C (104 °F) Non- or slightly inductive loads, resistance furnaces; Ue = 230…690V Figure 20 - AC-2, Stepping of slip-ring motors; Ue = 230…460V 00E+00 05E+02 10E+02 15E+02 20E+02 25E+02 30E+02 0 1 02 03 04 05 06 07 08 09 0 1 0 0 P/Pn [%] Permissible switching rate [ops/hr] C09/C12/C16/C23 C30/C37 C40/43 C60/C72/C85 C90/C97 01E+02 10E+02 01E+04 0 1 02 03 04 05 06 07 08 09 0 1 0 0 P/Pn [%] Permissible switching rate [ops/hr] C09/C12/C16 C23/C30/C37/C43 C60/C72 C85/C97

56 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Approximate Dimensions Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. Bulletin 100-C/104-C, 100S-C/104S-C Approximate Dimensions Figure 23 - Bulletin 100-C/100S-C Contactors and Accessories Figure 24 - Mounting Position — 100-C Contactors; 100S-C AC Contactors and DC Contactors with Electronic Coils Figure 25 - Mounting Position — 100S-C DC Contactors with Conventional Coils c

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 57 100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Approximate Dimensions Table 24 - AC Contactors and DC Contactors with 12V or 24V Electronic Coils Cat. No. a b c c1 c2 Ød d1 d2 Table 25 - DC Contactors with Conventional Coils Cat. No. a b c c1 c2 Ød d1 d2 Table 26 - DC Contactors with 36…48V, 48…72V, 110…125V, or 200…250V DC Electronic Coils Cat. No. a b c c1 c2 Ød d1 d2 Table 27 - 100-C/104-C Accessories Contactors with mm (inches) Auxiliary contact block for front mounting 2- or 4-pole c/c1 + 39 (c/c1 + 1-37/64) Auxiliary contact block for side mounting 1- or 2-pole a + 9 (a + 23/64) Pneumatic Timing Module c/c1 + 58 (c/c1 + 2-23/64) Electronic Timing Module on coil terminal side b + 24 (b + 15/16) Mechanical Interlock on side of contactor a + 9 (a + 23/64) Mechanical Latch c/c1 + 61 (c/c1 + 2-31/64) Interface Module on coil terminal side b + 9 (b + 23/64) Surge Suppressor on coil terminal side b + 3 (b + 1/8) Labeling with… label sheet + 0 (+ 0) marking tag sheet with clear cover + 0 (+ 0) marking tag adapter for System Bul. 1492W + 5.5 (+ 7/32) Terminal Lug Kit 100-C30…C37 b + 44 (b + 1-47/64) Paralleling Links 100-C09…C23 b + 78 (b + 3-1/16) c + 9/5 (c + 3/8) 100-C30…C37 b + 85 (b + 3-11/32) Auxiliary contact block for side mounting 1- or 2-pole a + 9 (a + 23/64) Electronic Timing Module on coil terminal side b + 24 (b + 15/16)

58 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-C/104-C, 100S-C/104S-C, 100Q-C Contactors Approximate Dimensions Bulletin 100Q-C Approximate Dimensions Figure 26 - Bulletin 100Q- Contactors Mechanical Interlock on side of contactor a + 9 (a + 23/64) Interface Module on coil terminal side b + 9 (b + 23/64) Surge Suppressor on coil terminal side b + 3 (b + 1/8) Labeling with label sheet + 0 (+ 0) marking tag sheet with clear cover + 0 (+ 0) marking tag adapter for System Bul. 1492W + 5.5 (+ 7/32) Table 28 - AC Contactors and DC Contactors with 12V or 24V Electronic Coils Cat. No. a b c c1 c2 Ød d1 d2 Table 29 - DC Contactors with Conventional Coils Cat. No. a b c c1 c2 Ød d1 d2 Table 30 - DC Contactors with 36…48V, 48…72V, 110…125V, or 200…250V DC Electronic Coils Cat. No. a b c c1 c2 Ød d1 d2 Table 27 - 100-C/104-C Accessories (Continued) Contactors with mm (inches) c

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 59 100-E/104-E, 100S-E/104S-E Contactors Product Selection—100-E/104-E Contactors The Bulletin 100-E/104-E contactor family, along with a wide range of accessories, provides the most compact and flexible contactor system available.  Coil voltage code and terminal position—see page 61

  • 4 … 5 6 0 k W @ 4 0 0 V •D i r e c t-on-line or reversing
  • 5…900 Hp @ 460V • 3 Main contacts
  • AC-1 ratings up to 2650 A • Co mplete range of accessories
  • Compact dimensions • Environmentally friendly
  • Electronic coils -A C / D C -W i d e v o l t a g e r a n g e - Low power pick-up and hold-in - Optional PLC interface 3-Pole AC- and DC-operated Direct-on-line Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Auxiliary Contacts Cat No.60 °C 40 °C kW (50 Hz) Hp (60 Hz) AC-3 (400V) AC-1 (690V) 220-240V 380-400V 415V 440V 500V 690V 1000V 200V 230V 460V 575V N.O. N.C. 9 25 2.2 4 4 4 5.5 5.5 — 2 2 5 7.5 10 100-E0910 01 100-E0901 01 100-E1201 1 6 3 0 4 7 . 5 9999— 55 1 0 1 5 10 100-E1610 01 100-E1601 2 6 4 5 6 . 5 1 1 1 11 51 51 5—7 . 5 7 . 5 1 5 2 0 0 0 100-E2600 32 50 9 15 15 18.5 18.5 18.5 — 10 10 20 25 0 0 100-E3000 38 50 11 18.5 18.5 22 22 22 — 10 10 25 30 0 0 100-E3800 40 70 11 18.5 22 22 22 22 — 10 15 30 40 0 0 100-E4000 52 100 15 22 30 30 30 30 — 15 20 40 50 0 0 100-E5200 6 5 1 0 5 1 8 . 5 3 0 3 73 73 73 7—2 02 55 06 0 0 0 100-E6500 8 0 1 2 5 2 2 3 7 4 54 54 54 53 52 53 06 07 5 0 0 100-E8000 9 6 1 3 0 2 5 4 5 5 55 55 55 54 03 03 06 07 5 0 0 100-E9600 116 160 37 55 55 75 75 63 55 30 40 75 100 1 1 100-E11611 (1) (1) To order with built-in terminal lugs, add the letter " L" to the end of the catalog number (example: 100-E11611L) 146 225 45 75 75 90 90 90 75 40 50 100 125 1 1 100-E14611 (1) 190 275 55 90 90 110 110 132 110 50 60 125 150 1 1 100-E19011 205 350 55 110 110 132 132 160 132 60 75 150 200 1 1 100-E20511 265 400 75 132 132 160 160 200 160 75 100 200 250 1 1 100-E26511 305 500 90 160 160 160 200 250 185 100 125 250 300 1 1 100-E30511 370 600 110 200 200 200 250 315 200 125 150 300 350 1 1 100-E37011 400 600 110 200 220 220 250 315 220 125 150 350 400 1 1 100-E40011 460 700 132 250 250 250 315 355 280 150 200 400 500 1 1 100-E46011 580 800 160 315 355 355 400 500 355 200 250 500 600 1 1 100-E58011 750 1050 220 400 425 450 530 600 400 250 300 600 700 1 1 100-E75011 860 1350 250 475 500 560 630 800 555 — 400 800 1000 1 1 100-E86011 1060 1650 315 560 630 710 710 1000 600 — 450 900 1150 1 1 100-E106011 100-E116 Contactor 100-E860 Contactor 100-E09 Contactor

60 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Product Selection—100-E/104-E Contactors  Coil voltage code and terminal position—see page 61  Coil voltage code and terminal position—see page 61 4-Pole AC- and DC-operated Direct-on-line Contactors Rated Current at 40 °C [A] Main Poles Auxiliary Contacts Cat No. Ie UL General Use (enclosed) 25 25 4000 100-E09400 2200 100-E09200 30 30 4000 100-E16400 2200 100-E16200 45 45 4000 100-E26400 2200 100-E26200 55 55 4000 100-E38400 2200 100-E38200 70 60 4000 100-E40400 2200 100-E40200 100 80 4 0 0 0 100-E52400 125 105 4000 100-E80400 2200 100-E80200 3-Pole AC- and DC-operated Reversing Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Auxiliary Contacts Cat No.60 °C 40 °C kW (50 Hz) Hp (60 Hz) AC-3 (400V) AC-1 (690V) 220-240V 380-400V 415V 440V 500V 690V 1000V 200V 230V 460V 575V N.O. N.C. 9 25 2.2 4 4 4 5.5 5.5 — 2 2 5 7.5 01 104-E0902 1 1(1) (1) The N.C. auxiliary contact is supplied as part of the mechanical/electrical interlock. 104-E0922(2) (2) For AC control voltages only. 01 104-E1202 16 30 4 7.5 9 9 9 9 — 5 5 10 15 01 104-E1602 2 6 4 5 6 . 5 1 1 1 11 51 51 5—7 . 5 7 . 5 1 52 0 0 1(1) 104-E2602(2) 11 104-E2622 32 50 9 15 15 18.5 18.5 18.5 — 10 10 20 25 0 1(1) 104-E3002(2) 11 104-E3022 38 50 11 18.5 18.5 18.5 22 22 — 10 10 25 30 0 1(1) 104-E3802(2) 11 104-E3822 40 70 11 18.5 22 22 22 22 — 10 15 30 40 1 1 104-E4022 5 2 1 0 0 1 5 2 2 3 03 03 03 0 — 1 5 2 04 05 0 1 1 104-E5222 65 105 18.5 30 37 37 37 37 — 20 25 50 60 1 1 104-E6522 8 0 1 2 5 2 2 3 7 4 54 54 54 53 52 53 06 07 5 1 1 104-E8022 9 6 1 3 0 2 5 4 5 5 55 55 55 54 03 03 06 07 5 1 1 104-E9622 116 160 55 55 55 75 75 63 55 30 40 75 100 1 1 104-E11622(3) (3) To order with built-in terminal lugs, add the letter "L" to the end of the catalog number (Example: 104-E11622L) 146 225 75 75 75 90 90 90 75 40 50 100 125 1 1 104-E14622(3) 190 275 90 90 90 110 110 132 110 50 60 125 150 1 1 104-E19022 205 350 110 110 110 132 132 160 132 60 75 150 200 1 1 104-E20522 265 400 132 132 132 160 160 200 160 75 100 200 250 1 1 104-E26522 305 500 160 160 160 160 200 250 185 100 125 250 300 1 1 104-E30522 370 600 200 200 200 200 250 315 200 125 150 300 350 1 1 104-E37022 400 600 200 200 220 220 250 315 220 125 150 350 400 1 1 104-E40022 460 700 250 250 250 250 315 355 280 150 200 400 500 1 1 104-E46022 580 800 315 315 355 355 400 500 355 200 250 500 600 1 1 104-E58022 750 1050 400 400 425 450 530 600 400 250 300 600 700 1 1 104-E75022

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 61 100-E/104-E, 100S-E/104S-E Contactors Product Selection—100-E/104-E Contactors Coil Voltage Codes For 3-Pole Contactors For 3-Pole Reversing Contactors PLC Interface For 4-Pole Contactors Electronic Coils V(1) (1) AC voltages are at 50/60 Hz 12-20V DC 24V DC 24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC 100-E09…100-E370 Standard AC/DC — — KJ KY KD KN 100-E09…100-E38 Low Consumption AC/DC EQ — EJ — — — 100-E09…100-E38 Low Consumption/ Faster Drop-out DC — QJ — — — — 100-E116…100-E370(2) (2) When ordering coil with PLC input, the PLC input must be used Standard AC/DC with PLC Input — — — — ED EN 100-E400…100-E750, 100-E1260 — — EJ (3) (3) 24V…60V DC only EY ED EN 100-E860…100-1060, 100-E2050…100-E2650 — — — — ED — Electronic Coils V(1) (1) AC voltages are at 50/60 Hz 12-20V DC 24V DC 24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC 104-E09…104-E370 Standard AC/DC — — KJ KY KD KN 104-E09…104-E38 Low Consumption AC/DC EQ — EJ — — — 104-E09…104-E38 Low Consumption/ Faster Drop-out DC — QJ — — — — 104-E116…104-E370(2) (2) When ordering coil with PLC input, the PLC input must be used Standard AC/DC with PLC Input — — — — ED EN 100-E400…104-E750, 104-E1260 — — EJ (3) (3) 24V…60V DC only EY ED EN 104-E860…104-1060, 104-E2050…104-E2650 — — — — ED — Electronic Coils V(1) (1) AC voltages are at 50/60 Hz 12-20V DC 24V DC 24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC 100-E09…100-E80 Standard AC/DC — — KJ KY KD KN 100-E09…100-E38 Low Consumption AC/DC EQ — EJ — — — 100-E09…100-E38 Low Consumption/Faster Drop-out DC — QJ — — — — Supply voltage Contactor A1 A224V COMMON OFF_N ON ON OFF

62 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Product Selection—100S-E Safety Contactors Product Selection—100S-E Safety Contactors

  • E l e c t r o n i c C o i l s
  • 3 Main Contacts
  • Direct-on-line
  • Low-power auxiliary contacts for feedback circuit
  • Mirror contact performance 3-Pole AC- and DC-operated Safety Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Auxiliary contacts per contactor Direct-on-line Contactor60 °C 40 °C kW (50 Hz) Hp (60 Hz) AC-3 (400V) AC-1 (690V) 220- 240V 380- (1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance. Cat No. 9 25 2.2 4 4 4 5.5 5.5 — 2 2 5 7.5 005 100S-E0905C 203 100S-E0923C 104 100S-E0914C 302 100S-E0932C 005 100S-E1205C 203 100S-E1223C 104 100S-E1214C 302 100S-E1232C 1 6 3 0 4 7 . 59999— 5 5 1 0 1 5 005 100S-E1605C 203 100S-E1623C 104 100S-E1614C 302 100S-E1632C 26 45 6.5 11 11 15 15 15 — 7.5 7.5 15 20 004 100S-E2604C 103 100S-E2613C 202 100S-E2622C 301 100S-E2631C 32 50 9 15 15 18.5 18.5 18.5 — 10 10 20 25 004 100S-E3004C 103 100S-E3013C 202 100S-E3022C 301 100S-E3031C 38 50 11 18.5 18.5 22 22 22 — 10 10 25 30 004 100S-E3804C 103 100S-E3813C 202 100S-E3822C 301 100S-E3831C 40 70 11 18.5 22 22 22 22 — 10 15 30 40 004 100S-E4004C 103 100S-E4013C 202 100S-E4022C 301 100S-E4031C 5 2 1 0 0 1 5 2 2 3 03 03 03 0 — 1 5 2 0 4 0 5 0 004 100S-E5204C 103 100S-E5213C 202 100S-E5222C 301 100S-E5231C 100S-E09 Contactor 100S-E80 Contactor

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 63 100-E/104-E, 100S-E/104S-E Contactors Product Selection—100S-E Safety Contactors 3-Pole AC- and DC-operated Safety Contactors (Continued) Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Auxiliary contacts per contactor Direct-on-line Contactor60 °C 40 °C kW (50 Hz) Hp (60 Hz) AC-3 (400V) AC-1 (690V) 220- 240V 380- (1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance. Cat No. 5 2 1 0 0 1 5 2 2 3 03 03 03 0 — 1 5 2 0 4 0 5 0 004 100S-E5204C 103 100S-E5213C 202 100S-E5222C 301 100S-E5231C 6 5 1 0 5 1 8 . 5 3 0 3 73 73 73 7 —2 0 2 5 5 0 6 0 004 100S-E6504C 103 100S-E6513C 202 100S-E6522C 301 100S-E6531C 8 0 1 2 5 2 2 3 7 4 54 54 54 53 52 5 3 0 6 0 7 5 004 100S-E8004C 103 100S-E8013C 202 100S-E8022C 301 100S-E8031C 9 6 1 3 0 2 5 4 5 5 55 55 55 54 0 3 0 3 0 6 0 7 5 004 100S-E9604C 103 100S-E9613C 202 100S-E9622C 301 100S-E9631C 116 160 37 55 55 75 75 55 55 30 40 75 100 1 1 1 100S-E11612C (2) (2) To order with built-in terminal lugs, add the letter " L" to the end of the catalog number (example: 100S-E11612CL) 146 225 45 75 75 90 90 90 75 40 50 100 125 1 1 1 100S-E14612C (2) 1 9 0 2 7 5 5 5 9 0 9 01 1 09 01 3 21 1 05 06 0 1 2 5 1 5 01 1 1 100S-E19012C 205 350 55 110 110 132 110 160 132 60 75 150 200 1 1 1 100S-E20512C 265 400 75 132 132 160 160 200 132 75 100 200 250 1 1 1 100S-E26512C 305 500 90 160 160 160 200 250 132 100 125 250 300 1 1 1 100S-E30512C 370 600 110 200 200 200 220 315 132 125 150 300 350 1 1 1 100S-E37012C 400 600 110 200 220 220 250 315 220 125 150 350 400 1 1 1 100S-E40012C 460 700 132 250 250 250 315 355 280 150 200 400 500 1 1 1 100S-E46012C 580 800 160 315 355 355 400 500 355 200 250 500 600 1 1 1 100S-E58012C 750 1050 220 400 425 450 530 600 400 250 300 600 700 1 1 1 100S-E75012C

64 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Product Selection—100S-E Safety Contactors 4-Pole AC- and DC-operated Safety Contactors Rated Operational Current Ie [A] Main Poles per contactor Auxil iary contacts per contactor Direct-on-line Contactor 40 °C AC-1 UL General Use (Enclosed) (1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance. Cat No. 25 25 4 0 04 100S-E09404C 13 100S-E09413C 22 100S-E09422C 31 100S-E09431C 30 30 4 0 04 100S-E16404C 13 100S-E16413C 22 100S-E16422C 31 100S-E16431C 45 45 4 0 04 100S-E26404C 13 100S-E26413C 22 100S-E26422C 31 100S-E26431C 70 60 4 0 2 2 100S-E40422C 100 80 4 0 2 2 100S-E52422C 125 105 4 0 2 2 100S-E80422C 3-Pole AC- and DC-operated Reversing Safety Contactors Rated Operational Current Ie [A] Ratings for switching AC motors - AC-2, AC-3 Auxiliary contacts per contactor Direct-on-line Contactor60 °C 40 °C kW (50 Hz) Hp (60 Hz) AC-3 (400V) AC-1 (690V) 220- 240V 380- 400V 415V 440V 500V 690V 1000V 200V 230V 460V 575V N.O. N.C.(1) (1) The N.C. contact meets IEC 60947-4-1 Annex F requirements for mirror contact performance. Cat No. 9 25 2.2 4 4 4 5.5 5.5 — 2 2 5 7.5 1 4 104S-E0928C 1 6 3 0 4 7 . 59999— 5 5 1 0 1 51 4 104S-E1628C 26 45 6.5 11 11 15 15 15 — 7.5 7.5 15 20 3 3 104S-E2666C 32 50 9 15 15 18.5 18.5 18.5 — 10 10 20 25 3 3 104S-E3066C 38 50 11 18.5 18.5 18.5 22 22 — 10 10 25 30 3 3 104S-E3866C 40 70 11 18.5 22 22 22 22 — 10 15 30 40 33 104S-E4066C 15 104S-E40210C 5 2 1 0 0 1 5 2 2 3 03 03 03 0 — 1 5 2 0 4 0 5 0 33 104S-E5266C 15 104S-E52210C 6 5 1 0 5 1 8 . 5 3 0 3 73 73 73 7 —2 0 2 5 5 0 6 0 33 104S-E6566C 15 104S-E65210C 8 0 1 2 5 2 2 3 7 4 54 54 54 53 52 5 3 0 6 0 7 5 33 104S-E8066C 15 104S-E80210C 9 6 1 3 0 2 5 4 5 5 55 55 55 54 0 3 0 3 0 6 0 7 5 33 104S-E9666C 15 104S-E96210C

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 65 100-E/104-E, 100S-E/104S-E Contactors Product Selection—100S-E Safety Contactors Coil Voltage Codes For 3-Pole Safety Contactors For 3-Pole Reversing Safety Contactors For 4-Pole Safety Contactors Electronic Coils V(1) (1) AC voltages are at 50/60 Hz 12-20V DC 24V DC 24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC 100S-E09…100S-E370 Standard AC/DC — — KJ KY KD KN PLC Interface 100S-E09…100S-E38 Low Consumption AC/DC EQ — EJ — — — 100S-E09…100S-E38 Low Consumption/ Faster Drop-out DC — QJ — — — — 100S-E116…100S-E370(2) (2) When ordering coil with PLC input, the PLC input must be used Standard AC/DC with 24V DC PLC Interface — — — — ED EN 100S-E400…100S-E750, 100S-E1260 — — EJ (3) (3) 24V…60V DC only EY ED EN 100S-E860…100S-E1060, 100S-E2050…100S-E2650 — — — — ED — Electronic Coils V(1) (1) AC voltages are at 50/60 Hz 12-20V DC 24V DC 24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC 104S-E09…104S-E96 Standard AC/DC — — KJ KY KD KN 104S-E09…104S-E38 Low Consumption AC/DC EQ — EJ — — — Electronic Coils V(1) (1) AC voltages are at 50/60 Hz 12-20V DC 24V DC 24-60V AC, 20-60V DC 48-130V AC/DC 100-250V AC/DC 250-500V AC/DC 100S-E09…100S-E96 Standard AC/DC — — KJ KY KD KN 100S-E09…100S-E38 Low Consumption AC/DC EQ — EJ — — — 100S-E09…100S-E38 Low Consumption/ Faster Drop-out DC — QJ — — — — Supply voltage Contactor A1 A224V COMMON OFF_N ON ON OFF

66 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Accessories Accessories Auxiliary Contact Blocks with Standard Auxiliary Contacts Description Connection Diagrams For Use With Cat. No. N.O. N.C. Auxiliary Contact Blocks for Front Mounting

  • 1 - p o l e
  • Quick and easy mounting without tools
  • Screw connection terminals
  • Switching down to 12V, 3mA
  • Mirror contact performance to the main contactor poles
  • L= Late break N.C./early make N.O. 100-E09…100-E96 100-EFA10 01 100-EFA01 1L 0 100-E09…100-E96 100-EFAL10

01 L 100-EFAL01

Auxiliary Contact Blocks for Front Mounting

  • 4 - p o l e
  • Quick and easy mounting without tools
  • Screw connection terminals
  • Switching down to 12V 3mA
  • Mirror contact performance to the main contactor poles 100-E0910…100-E1610 100-EFC22 31 100-EFC31 13 100-EFC13 04 100-EFC04 100-E2600…100-E9600 100-E09400…100-E80400 100-E09200…100-E80200 100-EFB22 31 100-EFB31 40 100-EFB40 04 100-EFB04 Auxiliary Contact Blocks for Front Mounting
  • 4 - p o l e
  • Quick and easy mounting without tools
  • Screw connection terminals
  • Switching down to 12V 3mA
  • Mirror contact performance to the main contactor poles 100-E09…100-E96 100-EFA22 31 100-EFA31 40 100-EFA40 13 100-EFA13 04 100-EFA04 -4 -2 NO NC -8 -6 NO NC 22 32 NC NO NC NO 22 34 NC NO NO NO 22 32 NC NC NONC 22 32 NC NC NC NC 14 22 NC NCNO NO 14 22 NC NO NONO 14 24 NO NONONO 12 22 NC NC NC NC 54 62 NC NCNO NO 54 62 NC NO NONO 54 64 NO NONONO 54 62 NC NO NC NC 52 62 NC NC NC NC

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 67 100-E/104-E, 100S-E/104S-E Contactors Accessories Auxiliary Contact Blocks for Front Mounting with A1/A2 Coil T erminal Blocks

  • 2 - p o l e
  • Quick and easy mounting without tools
  • Screw connection terminals
  • Switching down to 12V, 3mA
  • Mirror contact performance to the main contactor poles 11 1 0 0 - E 0 910…100-E1610 100-EFC11T 100-E2600…100-E6500 100-E09400…100-E52400 100-E09200…100-E40200 100-EFB11T Auxiliary Contact Blocks for Side Mounting
  • 2 - p o l e
  • Two-way numbering for right or left mounting on the contactor
  • With or without sequence terminal designations
  • Quick and easy mounting without tools
  • Screw connecting terminals
  • Switching down to 12V, 3mA
  • Mirror contact performance to the main contactor poles 1 1 100-E26…100-E96 100-ESB11 1 1 100-E09…100-E96 100-ESA11 Auxiliary Contact Blocks for Front Mounting for Severe Industrial Applications
  • 1 - p o l e
  • Available in two IP degr ees of ingress protection – B, B2 with built-in microswitch, IP40 degree of protection – (IP20 terminals) – B3, B4 with built-in microswitch, IP67 degree of protection – (IP20 terminals), 250V, 2 A max.
  • Available in two voltage and current ratings – B, B3: 125V, 0.1 A max., 3V, 1 mA min. – B2, B4: 250V, 2 A max., 17V, 1 mA min. 100-E09…100-E96 100-ESA10B 01 100-ESA01B 10 100-ESA10B2 01 100-ESA01B2 10 100-ESA10B3 01 100-ESA01B3 10 100-ESA10B4 01 100-ESA01B4 Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations
  • 2 - p o l e
  • Two-way numbering for right or left mounting on the contactor
  • Quick and easy mounting without tools
  • Mirror contact performance to the main contactor poles
  • Low power switching down to 24V 50 mA 11 100-E116…E370, left or right inside mounting 100-ES1-11 11 100-E116…E370, left or right outside mounting 100-ES2-11 Low-power Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations (1)
  • 1 - p o l e
  • Two-way numbering for right or left mounting on the contactor
  • Quick and easy mounting without tools
  • Mirror contact performance to the main contactor poles
  • Electronic compatible, 3V 1 mA 100-E116…E370, left or right inside or outside mounting 100-ES1-B10 100-E116…E370, left or right inside or outside mounting 100-ES1-B01 Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations
  • 2 - p o l e
  • Two-way numbering for right or left mounting on the contactor
  • Quick and easy mounting without tools
  • Mirror contact performance to the main contactor poles
  • Low power switching down to 24V 50 mA 11 100-E400…E2650, left or right inside mounting 100-ES3-11 11 100-E400…E2650, left or right outside mounting 100-ES4-11 Low-power Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations (1)
  • 1 - p o l e
  • Two-way numbering for right or left mounting on the contactor
  • Quick and easy mounting without tools
  • Mirror contact performance to the main contactor poles
  • Electronic compatible, 3V 1 mA 100-E400…E2650, left or right inside or outside mounting 100-ES3-B10 100-E400…E2650, left or right inside or outside mounting 100-ES3-B01 (1) No auxiliary contacts blocks can be mounted on th e outside of the 100-ES1-B* or 100-ES3-B* devices. Auxiliary Contact Blocks with Standard Auxiliary Contacts (Continued) Description Connection Diagrams For Use With Cat. No. N.O. N.C. NC NO NC NO NC NO NC NO -4 -2 NO NC NO 14 NO 13 NC 22 NC 21NO 44 NC 32 NC 31NO 43 NO 54 NO 53 NC 62 NC 61NO 84 NC 72 NC 71NO 83 NO 18 NO 17NO 28 NO 27 NC 16 NC 15NC 26 NC 25 NO 14 NO 13 NC 22 NC 21NO 44 NC 32 NC 31NO 43 NO 54 NO 53 NC 62 NC 61NO 84 NC 72 NC 71NO 83 NO 18 NO 17NO 28 NO 27 NC 16 NC 15NC 26 NC 25

68 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Accessories Mechanical Interlocks Description Connection Diagrams For Use With Cat. No. Mechanical Interlock

  • For interlocking of two contactors
  • Two fixing clips included Mechanical only, without auxiliary contacts 100-E09…100-E38 (3 pole), 100-E09400…100-E38400 100-EMCA00A(1) (1) Must be ordered in multiples of 10 pieces. 100-E40…100-E96 (3 pole), 100-E40400…100-E80400 100-EMCA00B(1) Mechanical Interlock
  • For interlocking of two contactors.
  • Interlocking of different sizes possible Mechanical only, without auxiliary contacts 100-EM1-00100-E190...100-E205 to 100-E190...100-E205 100-EM4-00 to 100-E265...100-E370 100-EM5-00 100-E400…100-E750, 100-E1260 (2) (2) Mounting plate ordered separately 100-EM2-00 100-E860…100-E1060, 100-E2050…100-E2650 (3) (3) Mounting plate included 100-EM3-00 Rod for vertical mounting 100-E400…E750 reversing contactors 100-EVR750 Mechanical and Electrical Interlock
  • For interlocking of two contactors
  • Two fixing clips, a mechanical interlock and an electrical interlock block with A2- A2 connection included
  • Front-face connection of the electrical interlock block connects the 2 built-in N.C. interlocking contacts with the two coils
  • The electrical diagram is used with the A2-A2 connection Mechanical/electrical interlock 100-E09…100-E38 (3 pole), 100-E09400…100-E38400 100-EMCA02 Electronic Timers Description Connection Diagrams For Use With Cat. No. N.O. N.C. Electronic Timing Module—ON-Delay
  • Delay of the contactor solenoid
  • The contactor is energized at the end of the delay time ON-Delay 0.1…1 s 1…10 s 10…100 s 1 1 100-E09…100-E96 100-ETA Electronic Timing Module—OFF-Delay
  • Delay of the contactor solenoid
  • After interruption of the control signal, the contactor is de-energized a the end of the delay time OFF-Delay 0.1…1 s 1…10 s 10…100 s 1 1 100-E09…100-E96 100-ETB DC Interface Module Description For Use With Pkg. Qty. Cat. No. DC Interface
  • Receives 24V DC signals from PLCs or other low output power sources and switches AC control power to operate the coils of the contactor
  • Coil voltage: 24…250V AC 50/60 Hz
  • Rated control circuit voltage U c: 24VDC 100-E09…100-E96 1 100-EJE 10 100-EJEM KM1 KM2 01NC 01NC A2 A2 KM1 55NC 67NO 56NC 68NO KM1 55NC 67NO 56NC 68NO

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 69 100-E/104-E, 100S-E/104S-E Contactors Accessories Mechanical Latch Description Rated Voltage [V] Connection Diagram For Use With Cat. No.V AC, 50/60 Hz V DC Mechanical Latch

  • Ensures contactor or contactor relay is switched on even if there is a voltage failure
  • Opening controlled either electrically by AC or DC impulse or manually by button
  • Front mounting 24…60 24…60 100-E09…100-E65 100-EFL11KJ 48…130 48…130 100-EFL11KY 100…250 100…250 100-EFL11KD 250…500 250…500 100-EFL11KN 24…60 24…60 100-E80, 100-E96 100-EFL12KJ 48…130 48…130 100-EFL12KY 100…250 100…250 100-EFL12KD 250…500 250…500 100-EFL12KN Additional Coil Terminal Block Description For Use With Pkg. Qty. Cat. No. Additional Coil Terminal Block
  • Allows bottom access to the coil terminals in addition to top access 100-E09…100-E96 10 100-ECT Protective Covers Description For Use With Pkg. Qty. Cat. No. Protective Cover
  • Provides protection against unintended manual operation
  • Sealable and Transparent 100-E09…100-E96 10 100-ESCCA 100-EF (4-pole only) 10 100-ESCFA Functional Markers Description For Use With Pkg. Qty. Cat. No. Functional Markers
  • 256 markers (16 per card) printable on HTP500 thermal transfer printer and AMS 500 marking table
  • 7 x 20 mm (0.276 x 0.787 in) 100-E09...100-E96 16 100-EFMS Terminal Block Description For Use With Pkg. Qty. Cat. No. Additional Terminal Blocks
  • Designed to increase wire size capacity of 3-pole contactors
  • 3-pole terminal blocks with IP20 terminals 100-E26…100-E38 2 100-ECT38 Terminal Shrouds Description No. of Poles For Use With Cat. No. Terminal Shrouds
  • IP20 terminal protection against accidental direct contact after wiring (EN 50274)
  • 3-pole and 4-pole 3-pole 100-E40…100-E65 100-ESC65 3-pole 100-E80, 100-E96 100-ESC96 4-pole 100-E40, 100-E52 100-ESC52 4-pole 100-E80 100-ESC80 Uc

70 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Accessories Paralleling Terminals Description For Use With Cat. No. Paralleling Terminals

  • To connect poles in parallel and thus incr ease the AC-1 load passing through the flow path made up of the parallel-connected poles 100-E09, 100-E12, 100-E16 100-ECP16 100-E26, 100-E30, 100-E38 100-ECP38 Terminal Lugs Description Wire Sizes For Use With Cat. No. Terminal Lug Kit
  • Standard on 100-E116*L…100-E146*L contactors
  • Set of two 2 x 6 AWG…3/0 AWG 100-E116…100-E146 100-ECL146 Terminal Lugs
  • Set of three

6 AWG…300 MCM 100-E190…100-E205 100-ETL205

4 AWG…400 MCM 100-E265…100-E370 100-ETL370

(2x) 4 AWG…500 MCM 100-E265…100-E370 100-ETL370B (2x) 2/0 AWG…500 MCM 100-E400…100-E460 100-ETL580 (3x) 2/0 AWG…500 MCM 100-E580...E750 100-ETL750 (4x) 4/0 AWG…500 MCM 100-E860 100-ETL860 (4x) 1/0 AWG…750 MCM 100-E1060 100-ETL1060 (6x) 1/0 AWG…750 MCM 100-E1060 100-ETL1060B Terminal Shrouds and Shields Description Wires with Compression Lugs Contactor with Terminal Lugs For Use With Cat. No. Terminal Shrouds

  • Not applicable when using 105-PW* or 170-PW* power wiring kits
  • P k g . Q t y : 2 X — 100-E116…100-E146 100-ETS146L — X 100-E190…100-E205 100-ETS205L X — 100-E190…100-E205 100-ETS205C —X 1 00-E265…100-E370 100-ETS370L(1) (1) Not applicable when using the 100-ETL370B lug kit. X— 1 00-E265…100-E370 100-ETS370C — X 100-E400…100-E460 100-ETS460L X — 100-E400…100-E460 100-ETS460C —X 1 0 0 - E 5 8 0 … 1 0 0 - E 7 5 0 100-ETS750L X — 100-E580…100-E750, 100-E1260 100-ETS750C IP20 terminal shield between contactor and 193-E overload relay on an assembled direct-on- line starter 100-E116…100-E146 100-ETC146 100-E190…100-E205 100-ETC205 IP20 terminal shield between contactor and 193-E overload relay on an assembled reversing starter 100-E116…100-E146 100-ETCR146 100-E190…100-E205 100-ETCR205

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 71 100-E/104-E, 100S-E/104S-E Contactors Accessories Power Wiring Kits Description For Use With Cat. No. Reversing Power Wiring Kits

  • Used to connect the main poles of two 3-pole contactors mounted side by side
  • 1 line-side paralleling and 1 load-side reversing connection
  • Insulated, solid copper bars 100-E09…100-E16 105-PW16 100-E26…100-E38 105-PW38 100-E40…100-E65 105-PW65 100-E80, 100-E96 105-PW96 Reversing Power Wiring Kits 100-E116…100-E146 105-PW146 100-E190…100-E205 105-PW205 (1) (1) Kits includes one set of terminal extensio ns. If 100-ETL* terminal lugs are to be used on line and load side of reversing contactor, and second set of 100-ETX terminal extensions is required. 100-E265…100-E370 105-PW370 (1) 100-E400…100-E460 105-PW460 (2) (2) If 100-ETL* terminal lugs are to be used on line and load side of reversing contactor, two sets of 100-ETX terminal extensions are also required. 100-E580…100-E750 105-PW750 (2) Wye-Delta Power Wiring Kits
  • Used to connect the main poles of the Line, Delta and Star contactors of a star-delta starter.
  • Connection sets are made up of: – Line contactor / delta contactor, line-side phase-to-phase connection – Delta contactor / star contactor, load-side connection in parallel – Star contactor: star point line-side – Insulated, solid copper bars Delta Contactor (1M/2M) Wye Contactor (1S) Cat. No. 100-E09…100-E16 100-E09…100-E16 170-PW16 100-E26…100-E38 100-E26…100-E38 170-PW38 100-E40…100-E65 100-E40…100-E65 170-PW65 100-E80, 100-E96 100-E80, 100-E96 170-PW96 Wye-Delta Power Wiring Kits Delta Contactor (1M/2M) Wye Contactor (1S) Cat. No. 100-E116…100-E146 100-E116…100-E146 170-PW146 100-E190…100-E205 100-E116…100-E146 170-PW190 100-E190…100-E205 100-E190…100-E205 170-PW205 100-E265…100-E370 100-E190…100-E205 170-PW265 100-E265…100-E370 100-E265…100-E370 170-PW370 100-E400…100-E460 100-E400…100-E460 170-PW460 100-E580…100-E750 100-E400…100-E460 170-PW580 100-E580…100-E750 100-E580…100-E750 170-PW750 Shorting Bars 100-E116…100-E146 170-PWY146 100-E190…100-E205 170-PWY205 100-E265…100-E370 170-PWY370 100-E400…100-E460 170-PWY460 100-E580…100-E750 170-PWY750 Mounting Plates Description For Use With Cat. No. For direct-on-line starters 100-E116…100-E146 100-EMS146 100-E190…100-E205 100-EMS205 For reversing contactors 100-E116…100-E146 100-EMR146 100-E190…100-E205 100-EMR205 100-E265…100-E370 100-EMR370 100-E400…100-E460 100-EMR460 100-E580…100-E750 100-EMR750 For reversing starters 100-E116…100-E146 100-EMRS146 100-E190…100-E205 100-EMRS205

72 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Accessories Connectors Description For Use With Circuit Breaker For Use With Contactor Cat. No. For connection to 140G or 140MG

  • Connection between contactors/starters and molded case circuit breakers.
  • These connection sets are solid copper bars. 140G-H, 140MG-H 100-E116…100-E146 100-PCE1 140G-I, 140MG-I 100-E116…100-E146 100-PCE2 140G-J, 140MG-J 100-E116…100-E146 100-PCE3 140G-J, 140MG-J 100-E190…100-E205 100-PCE4 140G-K, 140MG-K 100-E265…100-E370 100-PCE5 140G-M, 140MG-M 100-E400…100-E750 100-PCE6 140G-K, 140MG-K 100-E400…100-E750 100-PCE7 Terminal Accessories Description For Use With Contactor Cat. No. Terminal Enlargements
  • Enlargement pieces designed to increase th e width of the contactor terminal pads in order to allow larger connections to be mounted. 100-E116…100-E146 100-ETE146 100-E190…100-E205 100-ETE205 100-E265…100-E370 100-ETE370 100-E400…100-E460 100-ETE460 100-E580…100-E750 100-ETE750 100-E1260 100-ETE1260 Terminal Extensions
  • Extension pieces designed to extend the main terminals of contactors for combined mounting of contactors and connection sets 100-E116…100-E146 100-ETX146 100-E190…100-E205 100-ETX205 100-E265…100-E370 100-ETX370 100-E400…100-E460 100-ETX460 100-E580…100-E750 100-ETX750

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 73 100-E/104-E, 100S-E/104S-E Contactors Renewal Parts Renewal Parts Coil Modules Description For Use With Voltage Cat. No. Coil Modules 100-E116 24…60V AC/DC TG913 48…130V AC/DC TG914 100…250V AC/DC TG915 250…500V AC/DC TG916 100…250V AC/DC w/ PLC Interface TGE913 250…500V AC/DC w/ PLC Interface TGE914 100-E146 24…60V AC/DC TG901 48…130V AC/DC TG902 100…250V AC/DC TG903 250…500V AC/DC TG904 100…250V AC/DC w/ PLC Interface TGE903 250…500V AC/DC w/ PLC Interface TGE904 100-E190, 100-E205 24…60V AC/DC TG905 48…130V AC/DC TG906 100…250V AC/DC TG907 250…500V AC/DC TG908 100-E190 100…250V AC/DC w/ PLC Interface TGE915 250…500V AC/DC w/ PLC Interface TGE916 100-E205 100…250V AC/DC w/ PLC Interface TGE907 250…500V AC/DC w/ PLC Interface TGE908 100-E265, 100-E305, 100-E370 24…60V AC/DC TG909 48…130V AC/DC TG910 100…250V AC/DC TG911 250…500V AC/DC TG912 100-E265 100…250V AC/DC w/ PLC Interface TGE917 250…500V AC/DC w/ PLC Interface TGE918 100-E305 100…250V AC/DC w/ PLC Interface TGE919 250…500V AC/DC w/ PLC Interface TGE920 100-E370 100…250V AC/DC w/ PLC Interface TGE911 250…500V AC/DC w/ PLC Interface TGE912 100-E400, 100-E460 24…60V DC w/ PLC Interface THE901 48…130V AC/DC w/ PLC Interface THE902 100…250V AC/DC w/ PLC Interface THE903 250…500V AC/DC w/ PLC Interface THE904 100-E580, 100-E750, 100-E1260 24…60V DC w/ PLC Interface TJE901 48…130V AC/DC w/ PLC Interface TJE902 100…250V AC/DC w/ PLC Interface TJE903 250…500V AC/DC w/ PLC Interface TJE904 100-E860, 100-E1060, 100-E2050 100…250V AC/DC w/ PLC Interface TKE903 (1) (1) One set of two coils TKE904 (2) (2) Printed circuit board 100-E2650 100…250V AC/DC w/ PLC Interface TLE903 (1) TLE904 (2)

74 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Renewal Parts Contact Kits Description For Use With Cat. No. Contact Kits 100-E116 100-EA116 100-E146 100-EA146 100-E190 100-EA190 100-E205 100-EA205 100-E2650 100-EA265 100-E305 100-EA305 100-E370 100-EA370 100-E400 100-EA400 100-E460 100-EA460 100-E580 100-EA580 100-E750 100-EA750 100-E1260 100-EA1260 100-E860 100-EA860 100-E1060 100-EA1060 100-E2050 100-EA2050 100-E2650 (1) (1) Movable contacts only 100-EA2650 Arc Chutes 100-E400, 100-E460 100-EC460 100-E580, 100-E750, 100-E1260 100-EC750 100-E860, 1060, 100-E2050 100-EC1060 100-E2650 100-EC2650 Terminal and Mounting Hardware Kits Description For Use With Cat. No. Terminal and Mounting Hardware Kits 100-E116*L, 100-E146*L 100-EHS146(1) (1) Mounting hardware only. 100-E116, 100-E146 100-EHF146 100-E190, 100-E205 100-EHF205 100-E265, 100-E305, 100-E370 100-EHF370 100-E400, 100-E460 100-EHF460 100-E580, 100-E750, 100-E1260 100-EHF750 100-E860, 100-E1060, 100-E2050 100-EHF2050 100-E2650 100-EHF2650

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 75 100-E/104-E, 100S-E/104S-E Contactors Specifications Specifications Table 31 - General Specifications 100-E, 100S-E, 104-E, 104S-E09…65 100-E, 100S-E, 104S-E80…96, 104-E80…2650 Rated Isolation Voltage Ui IEC [V] 690 1000 UL, CSA [V] 600 600 Rated Impulse Voltage Withstand Uimp [kV] 6 8 Rated Voltage Ue AC 50/60 Hz [V] 115, 200, 230, 240, 400, 415, 460 500, 575, 690, 1000 DC [V] 24, 48, 110, 220, 440 Electromagnetic compatibility IEC 60947-1 - Environment A and B(1) (1) 100-E09…E38 only. Insulation Class of the Coil Class F per IEC 60947-4-1 Rated coil frequency AC 50/60 Hz, DC Ambient Temperature Operation at Max. Altitude of Installation Site [m] 3000 Climatic Withstand Category B according to IEC 60947-1, Annex Q Resistance to Shock IEC 60068-2-27 Resistance to Vibration IEC 60068-2-6 Protection Class Contactor main contacts IP2X(2) (2) 100-E40…E96 meet IP2X when used with 100-ESC… terminal shrouds. IP00 Contactor coil terminals IP2X (in connected state) Auxiliary contacts IP2X (in connected state) Functional Safety Data (100S-E116…-E750): Usable for ISO 13849-1 and IEC 62061. Data is based on the B10 value given and: - Mission time/Proof test interval of 20 years. 100S-E116…100S-E370 B10: 1.0E+06 operations at 50% max. AC-3 lo ad; failure ratio: 75% failure to open, 25% failure to close 100S-E116…100S-E205 B10: 5.0E+06 operations, mechanical only; failure ratio: 50% failure to open, 50% failure to close 100S-E265…100S-E370 B10: 2.5E+06 operations , mechanical only; failure ratio: 50% failure to open, 50% failure to close 100S-E400…100S-E750 B10: 5.0E+05 operations at 50% max. AC-3 load; failure ratio: 75% failure to open, 25% failure to close 100S-E400…100S-E460 B10: 3.0E+06 operations , mechanical only; failure ratio: 50% failure to open, 50% failure to close 100S-E570…100S-E750 B10: 7.0E+05 operations, mechanical only; failure ratio: 50% failure to open, 50% failure to close Table 32 - Standards Compliance and Certifications Standards Compliance Certifications

  • IEC/EN 60947-1, Low-voltage switchgear and controlgear • cULus, File No. E41850 / E196120 (contactors, reversing contactors)
  • IEC/EN 60947-4-1, Low-voltage switchgear and controlgear, Contactors and motor-starters • UL
  • IEC/EN 60947-5-1, Low-voltage switchgear and controlgear, Control circuit devices and switching elements
  • C S A
  • CCC
  • UL 60947-4-1, Industrial Control Equipment (USA) • EAC
  • CSA C22.2 No. 60947-4-1 Industrial Control Equipment (Canada). • RCM
  • Mechanically Linked Contacts: IEC 60947-5-1, Annex L (100/100S-E09…100/100S-E96 with all 100-E* front- and side-mounted N.C. auxiliary contacts)
  • R I N A
  • K C
  • Mirror Contacts: IEC 60947-4-1, Annex F (100/100S-E116…100/100S-E750 with all 100-ES* side-mounted N.C. auxiliary contacts)
  • C E
  • S U V A
  • SEMI-F47 (Conditions of use on request)

76 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications 9…96 A Contactor Specifications Table 33 - Main Circuits 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 AC-1 Active Power Load (50/60Hz); Ambient temperature 40 °C (104 °F) Rated Operational Current, Ie 690V [A] 25 28 30 45 50 50 70 100 105 125 130 Rated Operational Power, P e 2 3 0 [ k W ] 1 0 1 1 1 2 1 82 02 02 84 04 25 05 2 2 4 0 [ k W ] 1 0 1 2 1 2 1 9 2 1 2 1 2 94 24 45 25 4 4 0 0 [ k W ] 1 7 1 9 2 1 3 1 3 53 54 86 97 38 79 0 4 1 5 [ k W ] 1 82 02 23 23 63 65 07 27 59 09 3 500 [kW] 22 24 26 39 43 43 61 87 91 108 113 690 [kW] 30 33 36 54 60 60 84 120 125 149 155 Ambient temperature 60 °C (140 °F) Rated Operational Current, Ie 6 9 0 V [ A ] 2 52 83 04 04 24 26 08 09 0 1 0 0 1 0 5 Rated Operational Power, P e 230 [kW] 10 11 12 16 17 17 24 32 36 40 42 240 [kW] 10 12 12 17 17 17 25 33 37 42 44 4 0 0 [ k W ] 1 7 1 9 2 12 82 92 94 25 56 26 97 3 415 [kW] 18 20 22 29 30 30 43 58 65 72 75 500 [kW] 22 24 26 35 36 36 52 69 78 87 91 690 [kW] 30 33 36 48 50 50 72 96 108 120 125 Ambient temperature 70 °C (158 °F) Rated Operational Current, Ie 6 9 0 V [ A ] 2 22 42 63 23 73 75 07 08 08 59 0 Rated Operational Power, P e 230 [kW] 9 10 10 13 15 15 20 28 32 34 36 240 [kW] 9 10 11 13 15 15 21 29 33 35 37 400 [kW] 15 17 18 22 26 26 35 48 55 59 62 415 [kW] 16 17 19 23 27 27 36 50 58 61 65 5 0 0 [ k W ] 1 9 2 1 2 32 83 23 24 36 16 97 47 8 690 [kW] 26 29 31 38 44 44 60 84 96 102 108 With Conductor sizes [mm2] 4 6 6 1 01 01 02 5 3 5 3 5 5 0 5 0

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 77 100-E/104-E, 100S-E/104S-E Contactors Specifications Table 34 - Main Circuits 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 Switching of 3-phase Motors; (50Hz) Ambient temperature 60 °C (140 °F) AC-2, AC-3 Rated Operational Current, Ie 220-240V [A] 9 12 18 26 33 40 40 53 65 80 96 380-400V [A] 9 12 18 26 32 38 40 53 65 80 96 415V [A] 9 12 18 26 32 38 40 53 65 80 96 440V [A] 9 12 18 26 32 38 40 53 65 80 96 500V [A] 9.5 12.5 15 23 28 33 40 45 55 65 80 690V [A] 7 9 10.5 17 21 24 25 35 39 49 57 Rated Operational Power, P e 220-240V [kW] 2.2 3 4 6.5 9 11 11 15 18.5 22 25 415V [kW] 4.0 5.5 9 11 15 18.5 22 30 37 45 55 440V [kW] 4.0 5.5 9 15 18.5 22.0 22 30 37 45 55 500V [kW] 5.5 7.5 9 15 18.5 22.0 22 30 37 45 55 690V [kW] 5.5 7.5 9 15 18.5 22.0 22 30 37 45 55 Load Carrying Capacity per UL/CSA General Purpose Current (enclosed) 600V [A] 13.8 16.0 20 24 24.0 24.0 34 34 56 80 80 Rated Operational Current and Power (enclosed), 1-Phase 120V [A] 13.8 16.0 20 24 24.0 24.0 34 34 56 80 80 240V [A] 10.0 12.0 17 17 28.0 28.0 40 50 68 68 88 120V [Hp] 0.75 1 1.5 2 2 2 3 3 5 7.5 7.5 240V [Hp] 1.5 2 3 3 5 5 7.5 10 15 15 20 Rated Operational Current and Power (enclosed), 3-Phase 220-240 [A] 6.8 9.6 15.2 22.0 28 28 42 54 68 80 80 440-480 [A] 7.6 11 14 21.0 27 34 40 52 65 77 77 550-600 [A] 9 11 17 22.0 27 32 41 52 62 77 77 200-208 [Hp] 2 3 5 7.5 10 10 10 15 20 25 30 220-240 [Hp] 2 3 5 7.5 10 10 15 20 25 30 30 440-480 [Hp] 5 7.5 10 15.0 20 25 30 40 50 60 60 550-600 [Hp] 7.5 10 15 20.0 25 30 40 50 60 75 75 Rated Operational Current and Power (enclosed), with 3 poles in series 125V DC [A] 9.5 13.2 17 25.0 25 25 40 58 76 76 110 250V DC [A] 8.5 8.5 12.2 12.2 20 29 38 55 72 89 106 1 2 5 V D C [ H p ] 1 1 . 5 23335 7 . 5 1 0 1 0 1 5 250V DC [Hp] 2 3 3 5 7.5 7.5 10 15 20 25 30

78 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications Table 35 - Main Circuits 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 Wye-Delta (60 Hz) Rated Operational Power, Pe 2 0 0 V [ H p ] 3 57 . 5 1 01 51 51 52 5 3 0 4 0 5 0 2 3 0 V [ H p ] 3 5 7 . 51 0 1 5 1 5 2 53 04 05 05 0 4 6 0 V [ H p ] 7 . 51 0 1 5 2 53 04 05 06 07 5 1 0 0 1 0 0 575V [Hp] 10 15 25 30 40 50 60 75 100 125 125 Star-Delta Starting (50 Hz) Rated Operational Current, Ie ≥ 2 3 0 V [ A ] 9 1 2 1 8 2 63 34 04 05 36 58 09 6 ≥ 240V [A] 9 12 18 26 32 38 40 53 65 80 96 400V [A] 9 12 18 26 32 38 40 53 65 80 96 415V [A] 9 12 18 26 32 38 40 53 65 80 96 500V [A] 9.5 12.5 15 23 28 33 40 45 55 65 80 690V [A] 7 9 10.5 17 21 24 25 35 39 49 57 Rated Operational Power, P e 230V [kW] 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45 240V [kW] 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45 400V [kW] 7.5 7.5 15 22 30 30 37 45 55 75 90 415V [kW] 7.5 7.5 15 22 30 37 37 45 55 75 90 500V [kW] 7.5 11 15 22 30 37 45 45 55 75 90 690V [kW] 7.5 11 15 22 30 37 37 55 55 75 90 Table 36 - Main Circuits 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 UL/CSA Elevator Duty Rated Operational Current and Power, 500,000 electrical operations, 1-Phase 1 1 5 V A C [ A ] 5 . 8 7 . 2 0 — 2 02 42 43 43 43 45 65 6 1 1 5 V A C [ H p ] 0 . 2 5 0 . 3 3 — 1 . 5 2233355 230V AC [Hp] 0.50 0.75 — 3 3 5 5 7.5 10 10 10 Rated Operational Current and Power, 500,000 electrical operations 3-Phase 230V AC [A] 4.20 6.80 — 15.2 22 22 28 28 42 42 42 460V AC [A] 4.80 7.60 — 21.0 27 27 34 40 52 52 52 575V AC [A] 3.90 6.10 — 17 22 22 32 41 41 52 52 200V AC [Hp] 1 2 — 5 7.5 7.5 10 10 15 15 15 2 3 0 V A C [ H p ] 1 2 — 5 8 1 0 1 0 1 52 02 02 0 4 6 0 V A C [ H p ] 3 5 — 1 5 2 02 02 53 04 04 04 0 5 7 5 V A C [ H p ] 3 5 — 1 5 2 02 03 04 04 05 05 0 UL/CSA HVAC Applications Definite purpose rating (3-phase) FLA 600V [A] 20 25 30 45 50 50 60 80 90 105 115 LRA 200-208V AC [A] 120 150 180 270 300 300 360 480 540 630 690 220-240V AC [A] 120 150 180 270 300 300 360 480 540 630 690 440-480V AC [A] 120 150 180 270 300 300 360 480 540 630 690 550-600V AC [A] 80 100 120 180 200 200 240 320 360 420 460

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 79 100-E/104-E, 100S-E/104S-E Contactors Specifications Table 37 - Main Circuits 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 Switching of Power Transformers, AC-6a (50 Hz) n=30 Apparent Power 230V [kVA] 5 5 7 11 13 16 17 21 23 25 28 240V [kVA] 5 6 7 11 14 17 17 21 24 26 29 400V [kVA] 8 9 12 18 23 28 29 36 40 44 48 415V [kVA] 8 10 12 19 24 29 30 37 42 45 50 500V [kVA] 10 12 14 23 29 35 36 45 50 55 61 690V [kVA] 14 16 20 32 40 48 50 62 70 76 84 n=20 690V [A] 17.5 20 25 40 50 60 62.5 77.5 87.5 95 105 2 0 0 V [ k V A ] 4 5 6 9 1 21 41 41 82 0 2 2 2 4 208V [kVA] 4 5 6 10 12 14 15 19 21 23 25 240V [kVA] 5 6 7 11 14 17 17 21 24 26 29 480V [kVA] 10 11 14 22 28 33 35 43 48 53 58 6 0 0 V [ k V A ] 1 2 1 4 1 7 2 83 54 24 35 46 16 67 3 Apparent Power 200V [kVA] 6 7 9 14 17 21 22 27 30 33 36 208V [kVA] 6 7 9 14 18 22 22 28 31 34 38 2 4 0 V [ k V A ] 7 8 1 0 1 7 2 12 52 63 23 63 94 4 480V [kVA] 15 17 21 33 42 50 52 64 73 79 87 6 0 0 V [ k V A ] 1 8 2 12 64 25 26 26 58 09 1 9 9 1 0 9 Apparent Power 200V [kVA] 8 9 12 18 23 28 29 36 40 44 48 208V [kVA] 8 10 12 19 24 29 30 37 42 46 50 240V [kVA] 10 11 14 22 28 33 35 43 48 53 58 480V [kVA] 19 22 28 44 55 66 69 86 97 105 116 600V [kVA] 24 28 35 55 69 83 87 107 121 131 145 Switching of Lighting Loads (UL/CSA) Tungsten lamps 1-phase per pole 347V [A] 20 25 30 45 50 50 65 80 90 105 115 3-phase (break all lines) 6 0 0 V [ A ] 2 02 53 04 55 05 06 58 09 0 1 0 5 1 1 5 Electrical discharge lamps (ballast) 1-phase per pole 347V [A] 20 25 30 45 50 50 65 80 90 105 115 3-phase (break all lines) 6 0 0 V [ A ] 2 02 53 04 55 05 06 58 09 0 1 0 5 1 1 5 Inrush Current Rated transformer current = n

80 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications Table 38 - Main Circuits 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 3- or 4-Pole 3-Pole 4-Pole 3-Pole 3-Pole 4-Pole 3-Pole 3-Pole 3-Pole 3-Pole 3-Pole Switching of DC Loads—Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C 1 pole ≤ 72V [A] 25 27 30 45 45 50 50 55 70 100 105 125 130 2 poles in series ≤ 72V [A] 25 27 30 45 45 50 50 55 70 100 105 125 130 1 1 0 V [ A ] 2 52 73 04 54 55 05 05 57 0 1 0 0 1 0 5 1 2 5 1 3 0 3 poles in series ≤ 72V [A] 25 27 30 45 45 50 50 55 70 100 105 125 130 1 1 0 V [ A ] 2 52 73 04 54 55 05 05 57 0 1 0 0 1 0 5 1 2 5 1 3 0 2 2 0 V [ A ] 2 52 73 04 54 55 05 05 57 0 1 0 0 1 0 5 1 2 5 1 3 0 4 poles in series Shunt-wound Motors—Starting, reverse current breaking, reversing, stepping: DC-3 at 60 °C 1 pole ≤ 72V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 2 poles in series ≤ 72V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 110V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 3 poles in series ≤ 72V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 110V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 220V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 4 poles in series Series-wound Motors—Starting, reverse current breaking, reversing, stepping: DC-5 at 60 °C 1 pole ≤ 72V [A] 9 12 16 20 — 25 25 — 70 100 105 125 130 2 poles in series ≤ 72V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 110V [A] 10 15 20 45 — 50 50 — 70 100 105 125 130 3 poles in series ≤ 72V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 110V [A] 25 27 30 45 — 50 50 — 70 100 105 125 130 220V [A] 9 12 16 20 — 25 25 — 70 100 105 125 130 4 poles in series Short Time Withstand I CW 40 °C 3- Pole 1 s [A] 300 300 300 700 700 700 1000 1000 1000 1200 1200 10 s [A] 150 150 150 350 350 350 600 600 600 780 780 30 s [A] 80 80 80 225 225 225 350 350 350 450 450 1 min [A] 60 60 60 150 150 150 250 250 250 300 300 15 min [A] 35 35 35 50 50 50 110 110 110 140 140

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 81 100-E/104-E, 100S-E/104S-E Contactors Specifications Resistance and Power Dissipation Main cu Total Power dissipation at: Ie AC-3, 400V; Maximum Switching Frequency AC-1 ops/hr 600 cycles/h AC-3 ops/hr 1200 cycles/h AC-2, AC-4 ops/hr 300 cycles/h 150 cycles/h Weight: AC/DC (Electronic) [kg (lbs.)] 0.43 (0.95) 0.43 (0.95) 0.43 (0.95) 0.48 (1.06) 0.48 (1.06) 0.48 (1.06) 0.99 (2.18) 0.99 (2.18) 0.98 (2.16) 1.23 (2.7) 1.25 (2.76) Table 39 - Short-circuit Current Ratings 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1 DIN FUSES- gG 100 kA Available Fault Current Type "2" (400V) [A] 32 32 35 62 80 80 100 125 125 160 160 60 kA Available Fault Current Type "2" (690V) [A] 6 10 16 32 32 40 40 63 80 80 100 MCCB 70 kA Available Fault Current Type "2" (400V) [A] 28 28 28 56 56 240 520 800 800 880 880 Short Circuit Current Rating (Max. Fuse or Circuit Breaker Rating) Per UL 60947 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only) UL Class RK5 Fuses 5 kA Available Fault Current Type 1 Combination (600V) [A] 30 30 60 60 100 100 150 150 — — — UL Class RK5 Fuses 10 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] ————— — — — 1 5 0 2 0 0 2 0 0 UL Class J and CSA HRCI-J Fuses 100 kA Available Fault Current Type 1 Combination (600V) [A] 3 03 06 06 0 1 0 0 1 0 0 1 5 0 1 5 0 1 5 0 2 0 0 2 0 0 UL Inverse-Time Circuit Breaker 5 kA Available Fault Current Type 1 Combination (480V) [A] 60 60 60 100 125 125 250 250 — — — 10 kA Available Fault Current Type 1 Combination (480V) [A] 60 60 60 — — — — — 250 250 250 65 kA Available Fault Current Type 1 Combination (480V) [A] — — — 100 — — 250 250 250 250 250 100 kA Available Fault Current Type 1 Combination (480V) [A] — — — — 125 125 — — — 100 100 5 kA Available Fault Current Type 1 Combination (600V) [A] 60 60 — — 125 125 250 250 — — — 10 kA Available Fault Current Type 1 Combination (600V) [A] — — 60 — — — 250 250 250 250 250 25 kA Available Fault Current Type 1 Combination (600V) [A] — — — 100 — — — — — — — 35 kA Available Fault Current Type 1 Combination (600V) [A] — — — — 125 125 — — 250 — — 50 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] ————— — — — — 2 5 0 2 5 0 Table 38 - Main Circuits (Continued) 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 3- or 4-Pole 3-Pole 4-Pole 3-Pole 3-Pole 4-Pole 3-Pole 3-Pole 3-Pole 3-Pole 3-Pole

82 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications Table 40 - Coil Data 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 Operating Limits 50/60Hz pick-up [x Us] 0.85…1.1 dropout [x Us] ≤ 0.60 DC Control pick-up [x Us] 0.80…1.1 dropout [x Us] ≤ 0.60 Standard Coil 24-60V AC, 20-60V DC (KJ) pick-up [VA]/[W] 50/50 25/25 40/40 hold-in [VA]/[W] 2.2/2 4/2 4/2 48…130V AC/DC (KY) pick-up [VA]/[W] 50/50 25/25 40/40 hold-in [VA]/[W] 2.2/2 4/2 4/2 100…250V AC/DC (KD) pick-up [VA]/[W] 50/50 25/25 40/40 hold-in [VA]/[W] 2.2/2 4/2 4/2 250…500V AC/DC (KN) pick-up [VA]/[W] 50/50 25/25 40/40 hold-in [VA]/[W] 2.2/2 4/2 4/2 Operating Times closing delay [ms] 40…95 42…100 opening delay [ms] 11…95 17…100 Energy-efficient Coil 12-20V DC (EQ) pick-up [W] 12…16 — — — — — hold-in [W] 1.7 — — — — — 24-60V AC, 20-60V DC (EJ) pick-up [VA]/[W] 16/12…16 — — — — — hold-in [VA]/[W] 1.7/1.7 — — — — — Operating Times closing delay [ms] 40…95 — — — — — opening delay [ms] 11…95 — — — — — High Energy Efficient Coil 24V DC (QJ) pick-up [W] 6 — — — — — hold-in [W] 1.7 — — — — — Operating Times closing delay [ms] 27…53 — — — — — opening delay [ms] 17…29 — — — — —

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 83 100-E/104-E, 100S-E/104S-E Contactors Specifications 116…2650 A Contactors Table 41 - Main Circuits 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 AC-1 Active Power Load (50/60 Hz); Ambient temperature 40 °C (104 °F) Rated Operational Current, Ie 690V [A] 160 225 275 350 400 500 600 600 700 800 1050 1350 1650 1260 2050 2650 1000V [A] 160 225 250 275 350 375 400 600 700 800 1050 1350 1650 1260 2050 2650 Rated Operational Power, P e 230V [kW] 64 90 110 139 159 199 239 239 279 319 418 538 657 502 817 1056 240V [kW] 67 94 114 145 166 208 249 249 291 333 436 561 686 524 852 1102 400V [kW] 111 156 191 242 277 346 416 416 485 554 727 935 1143 873 1420 1836 415V [kW] 115 162 198 252 288 359 431 431 503 575 755 970 1186 906 1474 1905 500V [kW] 139 195 238 303 346 433 520 520 606 693 909 1169 1429 1091 1775 2295 690V [kW] 191 269 329 418 478 598 717 717 837 956 1255 1613 1972 1506 2450 3167 1000V [kW] 277 390 433 476 606 650 693 1039 1212 1386 1819 2338 2858 2182 3551 4590 Ambient temperature 60 °C (140 °F) Rated Operational Current, Ie 690V [A] 145 200 250 300 350 400 500 500 600 700 875 1150 1450 1040 1750 2350 1000V [A] 145 200 225 250 300 325 350 500 600 700 875 1150 1450 1040 1750 2350 Rated Operational Power, P e 230V [kW] 58 80 100 120 139 159 199 199 239 279 349 458 578 414 697 936 240V [kW] 60 83 104 125 145 166 208 208 249 291 364 478 603 432 727 977 400V [kW] 100 139 173 208 242 277 346 346 416 485 606 797 1005 721 1212 1628 415V [kW] 104 144 180 216 252 288 359 359 431 503 629 827 1042 748 1258 1689 500V [kW] 126 173 217 260 303 346 433 433 520 606 758 996 1256 901 1516 2035 690V [kW] 173 239 299 359 418 478 598 598 717 837 1046 1374 1733 1243 2091 2809 1000V [kW] 251 346 390 433 520 563 606 866 1039 1212 1516 1992 2511 1801 3031 4070 Ambient temperature 70 °C (158 °F) Rated Operational Current, Ie 690V [A] 130 175 200 240 290 325 400 400 480 580 720 1000 1270 875 1500 2120 1000V [A] 130 175 185 200 240 260 290 400 480 580 720 1000 1270 875 1500 2120 Rated Operational Power, P e 230V [kW] 52 70 80 96 116 129 159 159 191 231 287 398 506 349 598 845 240V [kW] 54 73 83 100 121 135 166 166 200 241 299 416 528 364 624 881 400V [kW] 90 121 139 166 201 225 277 277 333 402 499 693 880 606 1039 1469 415V [kW] 93 126 144 173 208 234 288 288 345 417 518 719 913 629 1078 1524 500V [kW] 113 152 173 208 251 281 346 346 416 502 624 866 1100 758 1299 1836 690V [kW] 155 209 239 287 347 388 478 478 574 693 860 1195 1518 1046 1793 2534 1000V [kW] 225 303 320 346 416 450 502 693 831 1005 1247 1732 2200 1516 2598 3672 With conductor sizes [mm2] 70 95 150 240 (1) (1) For currents above 275 A, use terminal extensions. 240 300 (2) (2) For currents above 450 A, use terminal extensions. 2x185 (2) 2x185 2x240 2x240 800 (3) (3) Maximum connection bar width 50 mm. 1000 (4) (4) Maximum connection bar width 100 mm. 1500 (4) 1000 (3) 2000 (4) 3000 (4)

84 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications Table 42 - Main Circuits 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Switching of 3-phase Motors; (50 Hz) Ambient temperature 60 °C (140 °F) AC-2, AC-3 Rated Operational Current, Ie 220-240V [A] 116 146 190 205 265 305 370 400 460 580 750 860 1060 — — — 380-400V [A] 116 146 190 205 265 305 370 400 460 580 750 860 1060 — — — 415V [A] 116 146 190 205 265 305 370 400 460 580 750 860 1060 — — — 4 4 0 V [ A ] 1 1 6 1 4 6 1 9 02 0 52 6 53 0 53 7 04 0 04 6 05 8 07 5 08 6 0 1 0 6 0 — — — 500V [A] 110 130 156 185 250 290 350 400 460 580 750 860 970 — — — 690V [A] 66 93 135 165 250 290 315 350 400 500 650 800 970 — — — 1000V [A] 46 60 85 100 113 131 141 155 200 250 300 375 400 — — — Rated Operational Power, P e 220-240V [kW] 37 45 55 55 75 90 110 110 132 160 220 250 315 — — — 380-400V [kW] 55 75 90 110 132 160 200 200 250 315 400 475 560 — — — 415V [kW] 55 75 90 110 132 160 200 220 250 355 425 500 630 — — — 440V [kW] 75 90 110 132 160 160 200 220 250 355 450 560 710 — — — 500V [kW] 75 90 110 132 160 200 250 250 315 400 530 630 710 — — — 690V [kW] 63 90 132 160 200 250 315 315 355 500 600 800 1000 — — — 1000V [kW] 55 75 110 132 160 185 200 220 280 355 400 555 600 — — — Load Carrying Capacity per UL/CSA General-purpose Current (enclosed) [A] 160 200 250 300 350 400 520 550 650 750 900 1350 1650 1210 2100 2700 Rated Operational Current and Power (enclosed), 3-Phase 200V [A] 92 120 150 177 221 285 359 359 414 552 692 954 1030 — — — 2 3 0 V [ A ] 1 0 41 3 01 5 41 9 22 4 83 1 23 6 0 3 6 0 4 8 0 6 0 47 2 29 5 4 1 0 3 0— — — 460V [A] 96 124 156 180 240 302 361 414 477 590 722 954 1030 — — — 575V [A] 99 125 144 192 242 289 336 382 472 578 672 944 1050 — — — 200V [Hp] 30 40 50 60 75 100 125 125 150 200 250 — — — — — 230V [Hp] 40 50 60 75 100 125 150 150 200 250 300 400 450 — — — 460V [Hp] 75 100 125 150 200 250 300 350 400 500 600 800 900 — — — 575V [Hp] 100 125 150 200 250 300 350 400 500 600 700 1000 1150 — — — Rated Current (enclosed), with 3 poles in series 6 0 0 V D C[ A ] ——————— 5 5 0 6 5 0 7 5 0 9 0 0 1 0 5 0 1 3 5 0 1 2 1 0 1 9 0 0 —

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 85 100-E/104-E, 100S-E/104S-E Contactors Specifications Table 43 - Main Circuits 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Switching of 3-phase Motors, (50Hz); Ambient temperature 60°C, AC-4 Rated Operational Current, Ie 2 3 0 V [ A ] 8 4 1 0 3 1 2 8 1 5 6 1 9 5 2 3 0 2 8 0 3 0 7 3 7 7 ——————— 2 4 0 V [ A ] 8 4 1 0 3 1 2 8 1 5 6 1 9 5 2 3 0 2 8 0 3 0 7 3 7 7 ——————— 4 0 0 V [ A ] 8 4 1 0 3 1 2 8 1 5 6 1 9 5 2 3 0 2 8 0 3 0 7 3 7 7 ——————— 4 1 5 V [ A ] 8 4 1 0 3 1 2 8 1 5 6 1 9 5 2 3 0 2 8 0 3 0 7 3 7 7 ——————— 5 0 0 V [ A ] 8 4 1 0 3 1 2 8 1 5 6 1 9 5 2 3 0 2 8 0 3 0 7 3 7 7 ——————— 6 9 0 V [ A ] 6 6 8 0 9 3 1 0 4 1 5 3 1 6 2 1 8 8 3 3 4 3 5 0 ——————— 1 0 0 0 V [ A ] 4 0 4 8 7 2 8 5 9 0 9 5 1 0 0 1 4 1 1 5 5 ——————— Rated Operational Power, Pe 2 3 0 V [ k W ] 2 5 3 2 4 0 5 0 5 5 7 5 9 0 9 0 1 1 0 ——————— 2 4 0 V [ k W ] 2 5 3 2 4 0 5 0 6 3 7 5 9 0 1 0 0 1 2 5 ——————— 4 0 0 V [ k W ] 4 5 5 5 6 3 8 0 1 1 0 1 3 2 1 6 0 1 6 0 2 0 0 ——————— 4 1 5 V [ k W ] 4 5 5 5 6 3 9 0 1 1 0 1 3 2 1 6 0 1 6 0 2 2 0 ——————— 5 0 0 V [ k W ] 5 5 6 3 9 0 1 1 0 1 3 2 1 6 0 2 0 0 2 2 0 2 5 0 ——————— 6 9 0 V [ k W ] 6 3 7 5 9 0 1 0 0 1 5 0 1 6 0 1 8 5 3 1 5 3 3 5 ——————— 1 0 0 0 V [ k W ] 5 5 6 3 1 0 0 1 1 0 1 2 5 1 3 2 1 3 2 2 0 0 2 2 0 ——————— AC-4 at approximately 200,000 operations Rated Operational Current, Ie 2 3 0 V [ A ] 3 8 3 8 4 9 5 5 7 3 8 9 1 0 0 1 1 8 1 3 5 ——————— 2 4 0 V [ A ] 3 8 3 8 4 9 5 5 7 3 8 9 1 0 0 1 1 8 1 3 5 ——————— 4 0 0 / 4 1 5 V [ A ] 3 8 3 8 4 9 5 5 7 3 8 9 1 0 0 1 1 8 1 3 5 ——————— 5 0 0 V [ A ] 3 3 3 3 3 7 4 4 5 3 5 9 6 8 7 8 8 9 ——————— 6 9 0 V [ A ] 3 3 3 3 3 7 4 4 5 3 5 9 6 8 7 8 8 9 ——————— Rated Operational Power, Pe 2 3 0 V [ k W ] 1 1 1 11 31 5 2 2 2 5 3 0 3 7 4 0 ——————— 2 4 0 V [ k W ] 1 1 1 11 51 5 2 2 2 5 3 2 3 7 4 5 ——————— 4 0 0 V [ k W ] 2 0 2 0 2 5 3 0 4 0 5 0 5 5 6 3 7 5——————— 4 1 5 V [ k W ] 2 0 2 0 2 5 3 0 4 0 5 0 5 5 6 3 7 5——————— 5 0 0 V [ k W ] 2 2 2 2 2 5 3 0 3 7 4 0 4 5 5 5 6 3 ——————— 6 9 0 V [ k W ] 3 0 3 0 3 2 4 0 5 0 5 5 6 3 7 5 8 0 ——————— M a x . s w i t c h i n g f r e q u e n c y O p s / h 1 5 0 1 5 0 1 5 0 1 5 0 1 5 0 1 5 0 1 5 0 6 0 6 0 ——————— Wye-Delta (60 Hz) Rated Operational Power, P e 2 0 0 V [ H p ] 5 0 6 0 7 5 1 0 0 1 2 5 1 5 0 2 0 0 2 0 0 2 5 0 ——————— 230V [Hp] 60 75 100 125 150 200 250 250 350 450 500 — — — — — 460V [Hp] 125 150 200 250 350 450 500 500 600 800 — — — — — — 575V [Hp] 150 200 250 300 450 500 600 600 700 1000 — — — — — —

86 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications Table 44 - Main Circuits 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 UL/CSA Elevator Duty Rated Operational Current, Ie 2 0 0 V [ A ] 5 4 5 4 7 7 9 9 1 2 5 1 4 9 1 5 6 ————————— 2 3 0 V [ A ] 5 4 5 4 7 7 9 9 1 2 5 1 4 9 1 5 6 ————————— 4 6 0 V [ A ] 5 4 5 4 7 7 9 9 1 2 5 1 4 9 1 5 6 ————————— 5 7 5 V [ A ] 5 4 5 4 7 7 9 9 1 2 5 1 4 9 1 5 6 ————————— Rated Operational Power, P e 2 0 0 V [ H p ] 1 51 5 2 0 3 0 4 0 4 0 5 0 ————————— 2 3 0 V [ H p ] 2 0 2 0 2 5 3 0 4 0 5 0 6 0 ————————— 4 6 0 V [ H p ] 4 0 4 0 6 0 7 5 1 0 0 1 0 0 1 2 5 ————————— 5 7 5 V [ H p ] 5 0 5 0 7 5 1 0 0 1 2 5 1 5 0 1 5 0 ————————— UL/CSA HVAC Applications Definite purpose rating (3-phase) F L A 6 0 0 V [ A ] 1 1 6 1 6 0 2 0 0 2 5 0 3 0 0 3 5 0 5 2 0 ————————— LRA 2 3 0 V [ A ] 7 0 0 9 6 0 1 2 0 0 1 5 0 0 1 8 0 0 2 1 0 0 3 1 2 0 ————————— 4 6 0 V [ A ] 5 8 0 8 0 0 1 0 0 0 1 2 5 0 1 5 0 0 1 7 5 0 2 6 0 0 ————————— 5 7 5 V [ A ] 4 7 0 6 4 0 8 0 0 1 0 0 0 1 2 0 0 1 4 0 0 2 0 8 0 ————————— A C r e s i s t a n c e h e a t i n g 6 0 0 V [ A ] 1 6 0 2 0 0 2 5 0 3 0 0 4 0 0 4 5 0 5 2 0 ————————— Star-Delta Starting (50 Hz) Rated Operational Current, I e ≤ 230V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 — — — ≤ 240V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 — — — 400V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 — — — 415V [A] 200 252 329 355 458 528 640 692 796 1004 1299 1489 1835 — — — 500V [A] 190 225 233 285 433 502 545 692 796 1004 1299 1385 1680 — — — 690V [A] 112 161 233 285 433 502 545 606 692 866 1125 1385 1680 — — — 1 0 0 0 V [ A ] — 1 0 3 1 4 7 1 7 3 1 7 3 1 7 3 1 7 3 2 6 8 3 4 6 4 3 3 5 1 9 ————— Rated Operational Power, P e 230V (1) (1) Power ratings at 50 Hz: Preferred values according to IEC 60947-4-1 [kW] 55 75 90 110 132 160 200 200 250 315 400 500 560 — — — 240V (1) [kW] 55 75 110 110 132 160 200 200 250 315 400 500 630 — — — 400V (1) [kW] 110 132 160 200 250 250 355 400 400 560 710 800 1000 — — — 415V (1) [kW] 110 132 160 200 250 315 355 400 400 560 800 900 1100 — — — 500V (1) [kW] 132 160 160 200 315 355 355 500 500 710 800 1000 1300 — — — 690V (1) [kW] 90 132 200 250 400 500 500 560 710 800 1100 1400 1700 — — — 1000V (1) [ k W ] — 1 3 2 2 0 0 2 5 0 2 5 0 2 5 0 2 5 0 3 5 5 5 0 0 6 3 0 7 1 0 —————

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 87 100-E/104-E, 100S-E/104S-E Contactors Specifications Table 45 - Main Circuits 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Switching of Power Transformers, AC-6a (50 Hz) n = 30 ≥ 230V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 — — ≥ 240V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 — — ≥ 400V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 — — ≥ 415V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 — — ≥ 500V [A] 70 79 111 115 143 143 165 200 252 263 286 — — 362 — — ≥ 690V [A] 70 79 111 115 143 143 165 200 252 263 286 — — 362 — — Apparent Power 230V [kVA] 28 31 44 46 57 57 66 80 100 105 114 171 209 144 — — 240V [kVA] 29 33 46 48 59 59 69 83 105 109 119 179 218 150 — — 400V [kVA] 48 55 77 80 99 99 114 139 175 182 198 298 363 251 — — 415V [kVA] 50 56 79 82 102 102 117 142 179 187 203 305 372 257 — — 500V [kVA] 61 68 96 100 124 124 143 173 218 228 248 — — 314 — — 690V [kVA] 84 94 133 137 171 171 197 239 301 314 342 — — 433 — — n = 20 ≥ 690V [A] 105 119 167 173 215 215 248 300 378 395 429 — — 543 — — n = 15 ≥ 690V [A] 140 158 222 230 286 286 330 400 504 526 572 — — 724 — — n = 30 ≥ 660V [A] 70 79 111 115 143 143 165 200 252 263 286 430 524 362 — — Apparent Power 2 0 0 V [ k V A ] 2 42 73 84 05 05 05 76 98 79 19 9 1 4 9 1 8 2 1 2 5— — 208V [kVA] 25 28 40 41 52 52 59 72 91 95 103 155 189 130 — — 240V [kVA] 29 33 46 48 59 59 69 83 105 109 119 179 218 150 — — 480V [kVA] 58 66 92 96 119 119 137 166 210 219 238 357 436 301 — — 600V [kVA] 73 82 115 120 149 149 171 208 262 273 297 447 545 376 — — 660V [kVA] 80 90 127 131 163 163 189 229 288 301 327 492 599 414 — — n = 20 ≥ 660V [A] 105 119 167 173 215 215 248 300 378 395 429 645 786 543 — — Apparent Power 200V [kVA] 36 41 58 60 74 74 86 104 131 137 149 223 272 188 — — 208V [kVA] 38 43 60 62 77 77 89 108 136 142 155 232 283 196 — — 240V [kVA] 44 49 69 72 89 89 103 125 157 164 178 268 327 226 — — 480V [kVA] 87 99 139 144 179 179 206 249 314 328 357 536 653 451 — — 600V [kVA] 109 124 174 180 223 223 258 312 393 410 446 670 817 564 — — 660V [kVA] 120 136 191 198 246 246 284 343 432 452 490 737 899 621 — — n = 15 ≥ 660V [A] 140 158 222 230 286 286 330 400 504 526 572 860 1048 724 — — Apparent Power 200V [kVA] 48 55 77 80 99 99 114 139 175 182 198 298 363 251 — — 208V [kVA] 50 57 80 83 103 103 119 144 182 190 206 310 378 261 — — 240V [kVA] 58 66 92 96 119 119 137 166 210 219 238 357 436 301 — — 480V [kVA] 116 131 185 191 238 238 274 333 419 437 476 715 871 602 — — 600V [kVA] 145 164 231 239 297 297 343 416 524 547 594 894 1089 752 — — 660V [kVA] 160 181 254 263 327 327 377 457 576 601 654 983 1198 828 — — Inrush Current Rated transformer current = n

88 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications Table 46 - Main Circuits 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Switching of 3-phase Capacitors, AC-6b (50 Hz) Single capacitor 40 °C 230V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 — — — 240V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 — — — 400V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 — — — 415V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 — — — 500V [kVAR] 83 110 140 160 180 210 240 260 325 350 490 550 600 — — — 690V [kVAR] 80 110 135 170 200 240 280 300 325 440 600 650 800 — — — 1 0 0 0 V [ k V A R ] — 1 0 0 1 4 0 1 5 0 1 5 5 1 6 0 1 7 0 2 5 0 3 0 0 3 5 0 4 5 0 ————— Single capacitor 55 °C 230V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 — — — 240V [kVAR] 40 50 60 75 85 100 110 120 140 170 220 250 300 — — — 400V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 — — — 415V [kVAR] 75 90 110 130 145 165 200 210 240 285 400 450 500 — — — 500V [kVAR] 83 110 140 160 180 210 240 260 325 350 490 550 600 — — — 690V [kVAR] 80 110 135 170 200 240 280 300 325 440 600 650 800 — — — 1 0 0 0 V [ k V A R ] — 1 0 0 1 4 0 1 5 0 1 5 5 1 6 0 1 7 0 2 5 0 3 0 0 3 5 0 4 5 0 ————— Single capacitor 70 °C 230V [kVAR] 35 42 45 57 70 85 100 105 120 160 190 230 280 — — — 240V [kVAR] 35 42 45 57 70 85 100 105 120 160 190 230 280 — — — 400V [kVAR] 65 74 83 105 135 155 180 195 225 275 370 430 480 — — — 415V [kVAR] 65 74 83 105 135 155 180 195 225 275 370 430 480 — — — 500V [kVAR] 78 96 102 130 165 196 220 241 300 340 435 530 570 — — — 690V [kVAR] 75 110 135 160 200 240 260 300 325 440 600 630 750 — — — 1 0 0 0 V [ k V A R ] — 9 5 1 2 0 1 3 0 1 4 0 1 5 0 1 6 0 2 2 0 2 7 0 3 0 0 4 0 0 —————

60 Hz Single Capacitor (cULus)

40 °C 208V [kVAR] 33 41 50 67 83 100 125 119 142 178 214 — 346 — — — 240V [kVAR] 38 48 57 77 95 115 144 137 164 205 247 — 398 — — — 480V [kVAR] 75 100 125 150 200 250 300 274 329 411 494 — 832 — — — 600V [kVAR] 100 125 150 200 250 300 350 343 410 514 618 — 1040 — — — Switching of Lamps Gas discharge lamps AC-5a open [A] 116 146 190 205 265 305 370 400 460 580 750 877 1072 812 1332 1722 U L B a l l a s t R a t i n g s [ A ] 1 6 0 2 0 0 2 5 0 3 0 0 4 0 0 4 5 0 5 2 0 ————————— Filament AC-5b 230/ 240V [A] 116 146 190 205 265 305 370 400 460 580 750 877 1072 812 1332 1722

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 89 100-E/104-E, 100S-E/104S-E Contactors Specifications Table 47 - Main Circuits 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Switching of DC Loads—Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C 1 pole ≤ 72V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 9 0 V [ A ] 1 6 0 2 0 0 2 5 0 3 5 0 4 0 0 5 0 0 5 2 0 ————————— 1 0 0 V [ A ]—— 2 5 0 3 5 0 4 0 0 5 0 0 5 2 0 ————————— 110V [A] — — — — 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 2 poles in series ≤ 72V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 110V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 1 7 5 V [ A ] 1 6 0 2 0 0 2 5 0 3 5 0 4 0 0 5 0 0 5 2 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 2 0 0 V[ A ]—— 2 5 0 3 5 0 4 0 0 5 0 0 5 2 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 2 2 0 V[ A ]———— 4 0 0 5 0 0 5 2 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 3 poles in series ≤ 72V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 110V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 175V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 220V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 260V [A] 160 200 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 300V [A] — — 250 350 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 340V [A] — — — — 400 500 520 600 700 800 1050 1350 1650 1250 2050 — 6 0 0 V[ A ]——————— 6 0 0 7 0 0 8 0 0 1 0 5 0 1 3 5 0 1 6 5 0 1 2 5 0 2 0 5 0 — 8 5 0 V[ A ]————————— 8 0 0 1 0 5 0 1 3 5 0 1 6 5 0 1 2 5 0 2 0 5 0 — Shunt-wound Motors—Starting, reverse current breaking, reversing, stepping DC-3, 60 °C (L/R ≤ 2 ms) 3 poles in series 2 4 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 4 8 / 6 0 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 1 1 0 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 2 2 0 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— Series-wound Motors—Starting, reverse current breaking, reversing, stepping DC-5, 60 °C (L/R ≤ 7.5 ms) 3 poles in series 2 4 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 4 8 / 6 0 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 1 1 0 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— 2 2 0 V [ A ] 1 4 5 1 6 0 2 5 0 2 7 5 3 5 0 4 0 0 4 5 0 6 0 0 7 0 0 8 0 0 1 0 5 0 ————— Short Time Withstand ICW

90 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications 40 °C 1 s [A] 1300 1460 1900 2050 2650 3050 3700 4600 4600 7000 7000 10000 12000 8000 12000 12000 10 s [A] 928 1168 1520 1640 2120 2440 2960 4400 4400 6400 6400 8000 10000 7200 10000 10000 30 s [A] 536 674 878 947 1224 1409 1709 3100 3100 4500 4500 6000 7500 5200 7500 7500 1 min [A] 379 477 621 670 865 996 1208 2500 2 500 3500 3500 4500 5500 4000 5500 5500 15 min [A] 160 225 275 350 400 500 600 840 840 1300 1300 1600 2200 1500 2200 2800 Resistance and Power Dissipation Power dissipation per pole at I e AC-1, 400V [W] 12 23 15 25 32 50 72 30 42 32 50 80 80 80 125 200 Power dissipation per pole at Ie AC-3/ 400V [ W ] 6 1 0 7 8 1 41 92 71 62 1 1 72 8 5 0 5 0— — — Total power dissipation at: I Maximum Switching Frequency AC-1 ops / hr 300 300 60 300 60 15 AC-3 ops / hr 300 300 60 — — — AC-2, AC-4 ops / hr 150 60 60 — — — Weight AC/DC (Electronic) with bar connections kg (lbs.) 1.50 (3.3) 1.50 (3.3) (6.6) (6.6) 4.64 (10.2) 4.64 (10.2) 4.64 (10.2) (26.4) (26.4) (33) (33) (74.8) (77) (35.2) (77) (99) with built-in cable clamps kg (lbs.) 1.75 (3.85) 1.75 Table 47 - Main Circuits (Continued) 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 91 100-E/104-E, 100S-E/104S-E Contactors Specifications Table 48 - Short-circuit Current Ratings 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating) Per IEC 60947-4-1 DIN Fuses - gG 100 kA Available Fault Current Type "2" (400V) [A] 250 250 315 315 400 500 630 630 630 800 800 1000 1250 — — — 80 kA Available Fault Current Type "2" (690V) [A] 160 200 315 315 400 425 500 500 630 800 800 1000 1600 — — — MCCB 70 kA Available Fault Current Type "2" (400V) [A] 160 160 320 320 400 630 630 630 630 800 1000 1600 1600 — — — Short Circuit Current Rating (Max. Fuse or Circuit Breaker Rating) Per UL 60947 and CSA 22.2 No. 14 (contactor and fuses or circuit breaker only) UL Class RK5 Fuses 10 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] 2 5 0 2 5 0 4 0 0 4 0 0 ———————————— UL Class L Fuses 18 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] ———— 8 0 0 8 0 0 8 0 0 1 0 0 0 ———————— 30 kA Available Fault Current 85 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] ——————————— 1 6 0 0 2 0 0 0 ——— UL Class J and CSA HRCI-J Fuses 100 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] 2 5 0 2 5 0 4 0 0 4 0 0 6 0 0 6 0 0 6 0 0 6 0 0 6 0 0 ——————— T y p e 2 C o m b i n a t i o n ( 6 0 0 V ) [ A ] 2 0 0 2 0 0 4 0 0 4 0 0 6 0 0 6 0 0 6 0 0 6 0 0 6 0 0 ——————— UL Class L Fuses 100 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] ——————— 8 0 0 8 0 0 1 2 0 0 1 2 0 0 —— 1 6 0 0 —— T y p e 2 C o m b i n a t i o n ( 6 0 0 V ) [ A ] ————————— 1 2 0 0 1 2 0 0 ————— UL Inverse- Time Circuit Breaker 42 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 4 8 0 V ) [ A ] ————————— 1 2 0 0 1 2 0 0 2 0 0 0 2 0 0 0 ——— 65 kA Available Fault Current T y p e 2 C o m b i n a t i o n ( 4 8 0 V ) [ A ] 2 5 0 2 5 0 4 0 0 4 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 ————— 84 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 4 8 0 V ) [ A ] ——————— 8 0 0 8 0 0 ——————— 89 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 4 8 0 V ) [ A ] ————————— 8 0 0 8 0 0 ————— 100 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 4 8 0 V ) [ A ] 2 5 0 2 5 0 4 0 0 4 0 0 8 0 0 8 0 0 8 0 0 ————————— 25 kA Available Fault Current T y p e 2 C o m b i n a t i o n ( 6 0 0 V ) [ A ] 2 5 0 2 5 0 —————————————— 35 kA Available Fault Current T y p e 2 C o m b i n a t i o n ( 6 0 0 V ) [ A ] —— 4 0 0 4 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 ————— 42 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] ———— 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 8 0 0 ————— 50 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] 2 5 0 2 5 0 —————————————— 65 kA Available Fault Current T y p e 1 C o m b i n a t i o n ( 6 0 0 V ) [ A ] —— 4 0 0 4 0 0 4 0 0 4 0 0 4 0 0 —————————

92 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications Table 49 - Coil Data 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Operating Limits 50/60 Hz pick-up [x Us] 0.85…1.1 dropout [x Us] 0.55 DC control pick-up [x Us] 0.80…1.1 dropout [x Us] 0.55 24…60V AC pick-up [VA] 225 165 475 — — — — — hold-in [VA] 5.5 6 8.5 — — — — — 48…130V AC pick-up [VA] 170 175 340 1215 1100 — 1100 — hold-in [VA] 4 4 17 12 12 — 12 — 100…250V AC pick-up [VA] 130 220 385 955 880 2450 880 2450 h o l d - i n [ V A ] 6 7 1 7 . 5 1 2 1 2 4 81 24 8 250…500V AC pick-up [VA] 205 185 420 950 985 — 985 — hold-in [VA] 16 16 21 12 12 — 12 — 24…60V DC pick-up [W] 210 205 400 900 785 — 785 — — 48…130V DC pick-up [W] 130 130 360 1150 1020 — 1020 — — 100…250V DC pick-up [W] 135 190 410 895 880 2290 880 2290 hold-in [W] 3 2.5 4.5 5 5 20.5 5 20.5 250…500V DC pick-up [W] 205 190 600 885 910 — 910 — — PLC Interface 10 mA @ 24V DC Operating Times AC or DC closing delay [ms] 20…55 25…60 30… 60 50…120 50…120 50…80 50…120 50…80 opening delay [ms] 40…70 45…80 45…80 33…70 33…70 35…55 33…70 35…55 With PLC Interface closing delay [ms] 20…31 25…45 25… 45 40…60 40…90 40…65 40…90 40…65 opening delay [ms] 24…34 25…45 25… 45 10…30 10…30 10…30 10…30 10…30

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 93 100-E/104-E, 100S-E/104S-E Contactors Specifications Conductors Table 50 - Cross Sections, Screw Type Terminals 100/104-E, 100S/104S-E 9 12 16 26 30 38 40 52 65 80 96 Conductor Cross Sections—Main Contacts Terminal Type (1) (1) Pozidriv No. 2 / Blade No. 3 screw (2) (2) Pozidriv No. 2 / Blade No. 4 screw (3) (3) Hexagonal socket screw 1 conductor [mm2] 1…6 1…6 1…6 2.5…10 2.5…10 2.5 …10 6…35 6…35 6…35 6…70 6…70 2 conductors [mm2] 1…6 1…6 1…6 2.5…10 2.5…10 2.5 …10 6…35 6…35 6…35 6…50 6…50 Cross Section per UL/CSA [AWG] 16…10 16…10 16…10 14…8 14…8 14…8 10…2 10…2 10…2 6…1 6…1 Recommended torque [lb•in] 13 13 13 22 22 22 35 35 35 53 53 Conductor Cross Sections- Coil and Auxiliary Contact Terminal Type (1) Cross Section per UL/CSA [AWG] 18…14 18…14 18…14 18…14 18…14 18…14 18…14 18…14 18…14 18…14 18…14 R e c o m m e n d e d t o r q u e [ l b • i n ] 1 11 11 11 11 11 11 11 11 11 1 1 1 Table 51 - Cross Sections, Screw Type Terminals 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 Main Terminals Conductor Cross Sections — Main Contacts (Terminal type) (1) conductor [mm2] 10…95 10…150 16…185 — — — — — Clamp Type 100-ECL146 100-ETL205 100-ETL370 — — — — — Recommended torque [N•m] 8 34 42 — — — — — (2) conductors [mm2] 10…95 — 16…500 70…240 70…240 120…240 70…300 — — Clamp Type 100-ECL146 — 100-ETL370B 100-ETL580 100-ETL750 100-ETL860 100-ETL1060 — — Recommended torque [N•m] 8 — 42 31 43 43 57 — — (3) conductors [mm2] — — — — 70…500 120…500 70…750 70…240 — Clamp Type — — — — 100-ETL750 100-ETL860 100-ETL1060 100-ETL750 — Recommended torque [N•m] — — — — 43 43 57 43 — (4) conductors [mm2] — ——— — 1 2 0 … 5 0 0 7 0 … 7 5 0 — — Clamp Type — — — — — 100-ETL860 100-ETL1060 — — Recommended torque [N•m] — — — — — 43 57 — — (6) conductors [mm2] — ——— — — 7 0 … 7 5 0 — — ETL1060B —— Ø 6.5 3 Ø 8.5 17.5 5 Ø 10.5 19.5 14.3 5 Ø 10.5 6Ø 6.5 22.5 Ø 6.5 22.5 6Ø 12.5 Ø 13 10 30 17 8Ø 13 25 15.5 (AF2050) 10 (AF2650) 25 Ø 13 4040 17

94 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Specifications L max. [mm] 22 24 32 47 50 100 50 100 Ø min. [mm] 6 8 10 10 12 12 12 12 Recommended torque [N•m] 9 18 28 35 45 45 45 45 Cross section per UL/CSA Clamp Type 100-ECL146 100-ETL205 100-ETL370 — — — — — — Recommended torque [lb•in] 80 300 375 — — — — — — Clamp Type 100-ECL146 — 100-ETL370B 100-ETL580 100-ETL750 100-ETL860 100-ETL1060 100-ETL750 — Recommended torque [lb•in] 80 — 375 275 375 375 500 375 — Clamp Type — — — — 100-ETL750 100-ETL860 100-ETL1060 100-ETL750 — Recommended torque [lb•in] — — — — 375 375 500 375 — Clamp Type — — — — — 100-ETL860 100-ETL1060 — — Recommended torque [lb•in] — — — — — 375 500 — — (6) conductors [AWG] — — — — — — 1/0…750 (1) —— ETL1060B —— Recommended torque [lb•in] — — — — — — 500 — — Recommended torque [lb•in] 80 160 248 310 398 398 398 398 Conductor Cross Sections — Coil and Auxiliary Contact Terminals (Terminal Type) (1) conductor [mm 2] 0.75…2.5 (2) conductors [mm2] 0.75…2.5 (1) conductor [mm2] 1…4 (2) conductors [mm2] 1…4 Recommended torque [N•m] 1…1.2 Cross section per UL/CSA [AWG] 18…14 Recommended torque [lb•in] 8.9…10.6 (1) MCM Table 51 - Cross Sections, Screw Type Terminals (Continued) 100/104-E, 100S-E 116 146 190 205 265 305 370 400 460 580 750 860 1060 1260 2050 2650 L Ø L Ø

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 95 100-E/104-E, 100S-E/104S-E Contactors Specifications Auxiliary Contacts Table 52 - Auxiliary Contacts Auxiliary contact for 100/104-E, 100S-E Internal 100-E09…E16 Standard 100-EF/ESA* Severe Appl. 100-ES*B/B3 Severe Appl. 100-ES*B/B3 Standard 100-ES1/2* Standard 100-ES3/4* Low Power 100-ES*-B* Switching of AC Loads Rated Insulation voltage Ui 690V 690V 250V 250V 690V 690V 250V Rated operational voltage Ue 690V 690V 125V 250V 690V 690V 125V Rated impulse withstand voltage Uimp 6kV 6kV — — 6kV 6kV 1.5kV AC-12 Ith at 40 °C [A] 16 16 0.1 2 16 16 0.1 AC-14 at rated voltage of AC-15 at rated voltage of 2 4 V [ A ] 66 —266— 42/48V [A] 6 6 — 2 6 6 — 120V [A] 6 6 — 2 6 6 — 2 3 0 V [ A ] 44—2 44— 2 4 0 V [ A ] 44—2 44— 400V [A] 3 3 — — 3 3 — 415V [A] 3 3 — — 3 3 — 500V [A] 2 2 — — 2 2 — 690V [A] 2 2 — — 2 2 — Switching of DC Loads DC-12 L/R< 1 ms resistive loads at DC-14 L/R< 15 ms inductive loads with economy resistor in series at DC-13 switching electromagnets at 24V DC [A] 6 6 — — 3 6 — 110V DC [A] 0.55 0.55 — — 0.55 0.55 — 4 4 0 V D C [ A ] 0 . 1 3 0 . 1 3 ————— Fuse gG Short-circuit protection with no welding of contacts per IEC 60947-5-2 [A] 10 10 0.1 10 10 10 0.1 [A] 10 10 0.1 10 10 10 0.1 Protective Separation per IEC 60947-1, Annex N Min. switching capacity at 12V IEC 60947-5-4 [mA] 3 3 — — 50 50 — Min. switching capacity at 3V IEC 60947-5-4 [mA] — — — 1 — — 1 Load Carrying Capacity per UL/CSA Rated voltage AC [V] 600 600 125 250 600 600 125 Continuous rating 40 °C [A] 10 10 0.1 2 10 10 0.1 Switching capacity AC A600 A 600 — — A 600 A 600 — Rated voltage DC [V] 600 600 110 220 250 250 125 Switching capacity DC Q600 Q 600 — — P 600 Q 300 —

96 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves Life-Load Curves 3-pole Contactors — Electrical Durability Figure 27 - Electrical durability for AC-1 utilization category - Ue ≤ 690V Switching non-inductive or slightly inductive loads. The breaking current Ic for AC-1 is equal to the rated operational current of the load. Ambient temperature (see page 83) and maximum electrical switching frequency (see page 90). Cat. Nos. 100-E860, -E1060: The electrical durability at the rated current is 50,000 operating cycles. 1 35 79 1 35 79 1 5 9 1 35 79 1 35 79 1 35 79 1 5 9 0.1 0.2 0.3 0.5 10 100 10002 3 5 20 30 50 200 300 500 E116 E146E190 E205E265E305E370 E400E460 E580E750E09 E12 E16 E26 E30, E38 E40 E52 E65 E80, E96 26.5 Millions of operating cycles Breaking current Ic [A]

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 97 100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves Figure 28 - Electrical durability for AC-3 utilization category - Ue ≤ 440V Switching cage motors: starting and switching off running motors. The breaking current Ic for AC-3 is equal to the rated operational current Ie (Ie = motor full load current). For ambient temperature (see page 83) and maximum electrical switching frequency (see page 90). Cat. Nos. 100-E860, -E1060: The electrical durability at the rated current is 50,000 operating cycles. Millions of operating cycles Breaking current Ic [A] 10 100 10002 3 5 20 30 50 200 300 500 0.2 0.3 0.5 1 35 79 1 35 79 1 35 79 1 35 79 1 5 9 1 5 9 1 35 79 1 35 79 E400E460 E580 E750E116 E190E205 E305E370E265E146E09 E12 E16 E26 E30, E38 E52 E65 E80, E96E40 1.8

98 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves Figure 29 - Electrical durability for AC-3 utilization category - 440V < Ue ≤ 690V Switching cage motors: starting and switching off running motors. The breaking current Ic for AC-3 is equal to the rated operational current Ie (Ie = motor full load current). For ambient temperature (see page 83) and maximum electrical switching frequency (see page 90). Cat. Nos. 100-E860, -E1060: The electrical durability at the rated current is 50,000 operating cycles. Millions of operating cycles Breaking current Ic [A] 1 35 79 1 35 79 1 5 9 1 35 79 1 35 79 1 35 79 1 35 79 1 35 79 10 100 10002 3 5 20 30 50 200 300 500 0.2 0.3 0.5 E116 E146 E190E205E265E305 E370E400E460 E580E750 1.5 140 E09 E12E16 E30, E38 E65 E80, E96E52E26 E40

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 99 100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves Figure 30 - Electrical durability for AC-2 or AC-4 utilization category - Ue ≤ 440V Switching cage motors: starting, reverse operation and step-by-step operation. The breaking current Ic is equal to 2.5 x Ie for AC-2 and 6 x Ie for AC-4, keeping in mind that Ie is the motor rated operational current (Ie = motor full-load current). For maximum electrical switching frequency (see page 90). Millions of operating cycles Breaking current Ic [A] 30001000100102 3 5 20 30 50 200 300 500 2000 5000 0.1 0.005 0.01 0.02 0.03 0.05 0.3 0.2 0.5 1 35 79 1 35 79 1 35 79 1 35 79 1 35 79 E400E460E580E750E116, E146 E205E265E190 E305E370E09 E12 E16 E30, E38 E65 E80, E96E52E26 E40

100 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Life-Load Curves Figure 31 - Electrical durability for AC-2 or AC-4 utilization category - 440V < Ue ≤ 690V Switching cage motors: starting, reverse operation and step-by-step operation. The breaking current Ic is equal to 2.5 x Ie for AC-2 and 6 x Ie for AC-4, keeping in mind that Ie is the motor rated operational current (Ie = motor full load current). For maximum electrical switching frequency (see page 90). Millions of operating cycles Breaking current Ic [A] 1 35 79 1 35 79 0.1 0.005 0.01 0.02 0.03 0.05 0.2 0.3 0.5 50001000100102 3 5 20 30 50 200 300 500 2000 3000 1 35 79 1 35 79 E116 E190E146 E205E265E305E370E400E460E580E750E09 E12 E16 E30 E65 E80, E96E52E26 E40E38

102 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions Figure 39 - 104-E09…104-E16 Reversing Contactors with Cat. No. 100-EMCA02 Mechanical and Electrical Interlock Figure 40 - Drilling Template for 9…16 A Contactors 26…38 A Contactors Figure 41 - 100-E26…100-E38 3-Pole Contactors with Standard Coils Figure 42 - 100-E26…100-E38 4-Pole Contactors with Standard Coils Figure 43 - 100-E26…100-E38 3-Pole Contactors with Low- consumption Coils Figure 44 - 100-E26…100-E38 4-Pole Contactors with Low- consumption Coils (1.69) 90 (3.54) 35 mm EN/IEC 60715 71 (2.80) 5.5 (0.22) (0.39) 91.5 (3.60) 102.5 (4.04) Non reversing contactors Reversing contactors 35 (1.38) ø 4.2 (0.17) 2 x M4 8…32 UNC (2.36) 5 (0.20) 5 (0.20) (2.76) (2.76) 5 (0.20) 2 x M4 8…32 UNC 80 (3.15) (2.36) (3.15) (0.24) 45 (1.77) 35 mm EN/IEC 60715 86 (3.39) 80 (3.15) 5.5 (0.22) 5.5 (0.22) (0.39) For contactors with QJ coils, add 20 mm (0.79 in.) to the depth (3.15) (0.24) 45 (1.77) 35 mm EN/IEC 60715 101 (3.98) 96 (3.74) 5.5 (0.22) 5.5 (0.22) (0.39) For contactors with QJ coils, add 20 mm (0.79 in.) to the depth (3.15) (0.24) 45 (1.77) 35 mm EN/IEC 60715 86 (3.39) 80 (3.15) 5.5 (0.22) 5.5 (0.22) (0.39) For contactors with QJ coils, add 20 mm (0.79 in.) to the depth (3.15) (0.24) 45 (1.77) 35 mm EN/IEC 60715 101 (3.98) 96 (3.74) 5.5 (0.22) 5.5 (0.22) (0.39) For contactors with QJ coils, add 20 mm (0.79 in.) to the depth

104 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions Figure 52 - 100-E26…100-E38 4-Pole Contactors with Low- consumption Coils and Side-mounted Auxiliary Contact Figure 53 - 104-E26…104-E38 Reversing Contactors with Cat. No. 100-EMCA02 Mechanical and Electrical Interlock Figure 54 - Drilling Template for 26…38 A Contactors 40…65 A Contactors Figure 55 - 100-E40…100-E65 3-Pole Contactors Figure 56 - 100-E40…100- E65 3-Pole Contactors with Front- mounted Auxiliary Contact For contactors with QJ coils, add 20 mm (0.79 in.) to the depth (3.15) (0.24) 45 (1.77) 35 mm EN/IEC 60715 96 (3.74) 5.5 (0.22) 5.5 (0.22) (0.39) 101 (3.98) (0.47) 69.4 (2.73) 91.5 (3.60) 90 (3.54) 111.5 (4.39) 80 (3.15) 5.5 (0.22) 5.5 (0.22) (0.39) 35 mm EN/IEC 60715 (1.69) Non reversing contactors Reversing contactors 35 (1.38) ø 4.2 (0.17) 2 x M4 8…32 UNC 60(2.36) 5 (0.20) 5 (0.20) 70(2.76) 70(2.76) 5 (0.20) 2 x M4 8…32 UNC 80 (3.15) 60(2.36) 119.5 (4.70) (0.24) 55 (2.17) 35 mm EN/IEC 60715 111 (4.37) 5.5 (0.22) (0.39) (0.28) (1.69) 119.5 (4.70) (0.24) 55 (2.17) 35 mm EN/IEC 60715 111 (4.37) 5.5 (0.22) (0.39) (0.28) 136 (5.35) (2-Pole auxiliary contact) 144 (5.67) (4-Pole auxiliary contact)

106 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions 80…96 A Contactors Figure 64 - 100-E80…100-E96 3-Pole Contactors Figure 65 - 100-E80…100-E96 3-Pole Contactors with Front- mounted Auxiliary Contact Figure 66 - 100-E80…100-E96 3-Pole Contactors with Side- mounted Auxiliary Contact Figure 67 - 104-E80…104-E96 Reversing 3-Pole Contactors Figure 68 - Drilling Template for 80…96 A 3-Pole Contactors Figure 69 - 100-E80 4-Pole Contactors Figure 70 - 100-E80 4-Pole Contactors with Front-mounted Auxiliary Contact (0.24) 70 (2.76) 35 mm EN/IEC 60715 7 (0.28) 5.5 (0.22) (0.39) 119.5 (4.70) 116 (4.57) (0.24) 70 (2.76) 35 mm EN/IEC 60715 7 (0.28) 5.5 (0.22) (0.39) 119.5 (4.70) 116 (4.57) (1.69) 149 (5.87) (4-Pole auxiliary contact) (0.24) 70 (2.76) 35 mm EN/IEC 60715 7 (0.28) 5.5 (0.22) (0.39) 119.5 (4.70) 116 (4.57) (0.47) 69.4 (2.73) (0.24) 140 (5.51) 35 mm EN/IEC 60715 7 (0.28) 5.5 (0.22) (0.39) 119.5 (4.70) 116 (4.57) Non reversing contactors Reversing contactors ø 6.4 (0.25) 130 (5.12) 110(4.33) 100(3.94) 5 (0.20) 4.6(0.18) M61/4…20 UNC60 (2.36) 110(4.33) 100(3.94) 5 (0.20) 4.6(0.18) 2 x M6 1/4…20 UNC ø 6.4 (0.25) (0.24) 90 (3.54) 35 mm EN/IEC 60715 7 (0.28) 5.5 (0.22) (0.39) 119.5 (4.70) 116 (4.57) (1.69) 149 (5.87) (4-Pole auxiliary contact) (0.24) 90 (3.54) 35 mm EN/IEC 60715 7 (0.28) 5.5 (0.22) (0.39) 119.5 (4.70) 116 (4.57)

108 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions Figure 78 - 100-E190, 100-E205 Contactors Figure 79 - 100-E190E, 100-E205E Contactors with PLC Input Figure 80 - 104-E190, 104-E205 Reversing Contactors with Cat. No. 100-EM… Mechanical Interlock Figure 81 - Drilling Template for 190…205 A 3-Pole Contactors Figure 82 - 100-E265…100-E370 Contactors Figure 83 - 100-E265E…100-E370E Contactors with PLC Input 105 (4.13) ø 8.5 (0.33) (1.38) 196 (7.72) (0.39) 152 (5.98) 83.5 (3.29) 35.5 (1.40) (0.20)29.5 (1.16) 105 (4.13) ø 8.5 (0.33) (1.38) 196 (7.72) (0.39) 83.5 (3.29) 35.5 (1.40) (0.20)29.5 (1.16) 169.5 (6.67) 196 (7.73) Non reversing contactors Reversing contactors 35 (1.36) M5 (10…24 UNC ) 165 (6.50) 35 (1.36) 6 x M5 (10…24 UNC ) 165 (6.50) 35 (1.36)70 (2.76) 140 (5.51) 19.5 (0.77) ø 10.5 (0.41) 43.75 (1.72) 180 (7.09) 94.7 (3.73) 225 (8.86) 35.5 (1.40) (0.20)33.4 (1.31) (0.39) 140 (5.51) 19.5 (0.77) ø 10.5 (0.41) 43.75 (1.72) 94.7 (3.73) 225 (8.86) 35.5 (1.40) (0.20)33.4 (1.31) (0.39) 195.5 (7.70)

110 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions Figure 87 - 100-E580…100-E750 Contactors with PLC Input Figure 88 - 100-E1260 Contactors with PLC Input 72 (2.83) 210 (8.27) (1.57) 22.5 (0.89) 11.5 (0.45) 273 (10.75) ø 12.5 (0.49)ø 6.5 (0.26) 242 (9.53) 48.5 (1.91) (0.24) 283 (11.14) 72 (2.83) 249 (9.8) M6 (1/4-20 UNC) 347 (13.7) 50 (1.97) 72 (2.83) 72 (2.83) 210 (8.27) 344 (13.54) 313 (12.32) 263 (10.35) 72 (2.83) ø 7 (0.28) ø 7 (0.28) 249 (9.8) 242 (9.53) 46.5 (18.3) 8 (0.31) 72 (2.83) 249 (9.8) M6 (1/4-20 UNC)

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 111 100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions Figure 89 - 100-E860, 100-E1060, 100-E2050, 100-E2650 Contactors with PLC Input (1.57) E2050, E2650 (1.57) ø 13 (0.51) (3.15) ø 9 (0.35) B 438 (17.24) A 312 (12.3) C 244 (9.61) 101 (3.98) 40 (1.57) (1.06) 30 (1.18) 17 (0.67) 40 (1.57) 17 (0.67) 10 (0.39) E860, E1060 13 (0.51) 136 (5.35) 136 (5.35) M8 (5/16-18 UMC) 312 (12.28) E860, E1060, E2050 E2650 A 392 (15.43 422 (16.61

112 Rockwell Automation Publication 100-TD013J-EN-P - April 2021

100-E/104-E, 100S-E/104S-E Contactors Approximate Dimensions Notes:

Rockwell Automation Publication 100-TD013J-EN-P - April 2021 113 IEC Contactor Specifications Technical Data Additional Resources These documents contain additional information concerning related products from Rockwell Automation. You can view or download publications at rok.auto/literature. Resource Description Rockwell Automation Global SCCR Tool, rok.auto/sccr Provides coordinated high-fault branch circuit solutions for motor starters, soft starters, and component drives. UL Standards Listing for Industrial Control Products, publication CMPNTS-SR002 Assists original equipment manufacturers (OEMs) with construction of panels, to help ensure that they conform to the requirements of Underwriters Laboratories. American Standards, Configurations, and Ratings: Introduction to Motor Circuit Design, publication IC-AT001 Provides an overview of American motor circuit design based on methods that are outlined in the NEC. Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications, publication IC-TD002 Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies. Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control, publication SGI-1.1 Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in the form of individual devices or packaged assemblies incorporating solid-state components. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.

Publication 100-TD013J-EN-P - April 2021 Rockwell Automation Support Use these resources to access support information. Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature Product Compatibility and Download Center (PCDC) Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/pcdc Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, FactoryTalk, Rockwell Automation are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur