MODEL: MSP5 MSP5 SPECIFICATIONS ES-4845 Rev.14 Page 1/6 http://www.m-system.co.jp/ Final Control Elements MINI-TOP ELECTRONIC ACTUATOR (linear type) Functions & Features
- Small-size control valve actuator
- 1/1000 high resolution
- Seal-spring incorporated for both directions; usable with three-way valves
- Easy adjustment: electronic limiter at the valve open & closed positions
- Overload protection
- Various power inputs
- Manual operation function option available Typical Applications
- Actuator for automatic control valve in pilotplants
- Air-conditioning in buildings or plants
- Micro-flow control for pharmaceutical injection
- For small-size control valves
ORDERING INFORMATION
- Code number: MSP5-[1][2][3][4][5]-[6][7][8][9] Specify a code from below for each of [1] through [9]. (e.g. MSP5-371LT-ACR/S/Q)
- Special input range (for codes Z and 0)
- Specify the specification for option code /Q (e.g. /SET) [1] STROKE 1: 5 to 10 mm (.20” to .39”) 3: 10 to 20 mm (.39” to .79”) [2] OPERATION TIME, THRUST 3: 5 sec. / 10 mm, 150 N 4: 9 sec. / 10 mm, 300 N 7: 18 sec. / 10 mm, 700 N [3] OUTPUT STEM TYPE 6: M6 female thread, 0.75 pitch 8: M8 female thread, 1.0 pitch 1: M10 female thread, 1.25 pitch D: M6 female thread, 1.0 pitch E: M8 female thread, 1.25 pitch F: M10 female thread, 1.5 pitch [4] SEQUENTIAL CONTROL SIGNALS L: Full-open/-closed signal F: Forced open/close signal B: Full-open/-closed and forced open/close signals (Select 'With Terminal Box.') 0: Without [5] TERMINAL BOX T: With 0: Without [6] INPUT Current A: 4 – 20 mA DC (Input resistance 250 Ω) Z: Specify current (See INPUT SPECIFICATIONS) Voltage 6: 1 – 5 V DC (Input resistance approx. 1 MΩ) 0: Specify voltage (See INPUT SPECIFICATIONS) [7] CE MARKING C: With 0: Without [8] POWER INPUT AC Power K3: 100 – 120 V AC (Operational voltage range 90 – 132 V, 47 – 66 Hz) (Not selectable for CE) L3: 200 – 240 V AC (Operational voltage range 180 – 264 V, 47 – 66 Hz) (Not selectable for CE) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [9] OPTIONS (multiple selections) Manual Operation Function blank: Without /S: With (Not available when DC power is selected.) Other Options blank: none
MODEL: MSP5 MSP5 SPECIFICATIONS ES-4845 Rev.14 Page 2/6 http://www.m-system.co.jp/ /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-4854) GENERAL SPECIFICATIONS Degree of protection: IP66 Action: Direct or reverse; field selectable with DIP switches (factory set to “reverse”) (In “reverse” action with upright mount, the output stem goes up with an input signal increase.) Operation at abnormally low input: go up, go down or stop; moving direction when upright mount, field selectable with DIP switches (factory set to “go down”) Detectable input drop level: -16 ±2.5 % Electrical connection
- Without terminal box Wiring conduit: G 1/2 female; cable connector with 1 meter wire (0.5 mm2) provided
- Terminal box Wiring conduit: G 1/2 female (two) Terminal screws: M3 pillar terminal (Sequential control signal suffix code B) M3 chromated steel (other terminal box types) (torque 0.5 N·m) Housing material: Diecast aluminum Drive: Stepping motor Insulation class: E Position detection: Potentiometer Deadband: 0.1 – 4.5 % adjustable (factory set to 1.5 %) Restarting timer: 0 – 10 sec. adjustable (factory set to 1.5 sec.) Isolation: AC power to signal Zero adjustment: 0 – 25 % Span adjustment: 50 - 100 % Protective functions: Overload protection Power indicator: Green LED turns on with power supplied. Input indicator: Green LED turns on with normal input Status indicator LED: Red light blinks in 2 sec. intervals in normal operations; blinks in 0.5 sec. intervals when a foreign object is detected mechanically caught inside. Manual operation: Optional
- MSP5-x3: 27 turns/mm
- MSP5-x4: 54 turns/mm
- MSP5-x7: 112 turns/mm INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated (250 Ω) ■ DC Voltage: 1 – 5 V DC or specific range within 0 – 5 V DC, minimum span 1 V (For a current input, convert the current to a voltage with 250 Ω) Input resistance: Approx. 1 MΩ ■ Forced open/close signal: Dry contact inputs to command to go up and go down Rating: 5 V DC @ 2.5 mA (go up and go down when upright mount) OUTPUT SPECIFICATIONS ■ Operation Time & Torque (at rated power voltage) (Model: Operation Time: Thrust) MSP5-x3: 5 sec. / 10 mm: 150 N (33.5 lbf) MSP5-x4: 9 sec. / 10 mm: 300 N (67 lbf) MSP5-x7: 18 sec. / 10 mm: 700 N (157 lbf) ■ DC Voltage: 1 – 5 V DC (not isolated) With “direct” action, 5 – 1 V DC position output is provided proportionally to 4 – 20 mA DC (1 – 5 V DC) input. Load resistance: ≥ 5 kΩ ■ Full-open / -closed signals: Limit switch contact Rating: 125 V AC @ 0.75 A (cos ø = 1) 30 V DC @ 0.6 A (resistive load) Mechanical life: 3 × 107 cycles Maximum operation frequency: 60 cycles/min. INSTALLATION Power consumption
- AC: Approx. 25 VA
- DC: Approx. 0.6 A Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 85 %RH (non-condensing) Vibration: 0.5 G (4.9 m/s2) max. Mounting position: All directions Do not mount the actuator with its output stem or cable connector on the upside if the actuator is to be exposed to dripping water. Weight
- DC powered: 1.2 kg (2.65 lb)
- AC powered: 1.4 kg (3.09 lb) Add 0.7 kg (1.54 lb) for the terminal box. PERFORMANCE Resolution: 1/1000 or 0.015 mm, whichever is greater, with 0.1 % deadband setting Insulation resistance
- AC powered: ≥ 100 MΩ with 500 V DC (signal or metallic housing to power) ≥ 100 MΩ with 100 V DC
MODEL: MSP5 MSP5 SPECIFICATIONS ES-4845 Rev.14 Page 3/6 http://www.m-system.co.jp/ (signal to metallic housing)
- DC powered: ≥ 100 MΩ with 100 V DC (signal or power to metallic housing) Dielectric strength
- AC powered: 1500 V AC @ 1 minute (signal or metallic housing to power)
100 V AC @ 1 minute
(signal to metallic housing)
- DC powered: 100 V AC @ 1 minute (signal or power to metallic housing) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (Full-open/-closed signal) Pollution Degree 2 Full-open/-closed signal to other, power or metallic housing: Reinforced insulation (125 V) RoHS Directive EN 50581 TERMINOLOGY
- Overload (Lock) Protection The Mini-Top Series is equipped with a protection circuit against overload caused by for example the valve catching an alien substance. When an overload is detected, the Mini-Top stops supplying power to the motor and the status LED blinks in 0.5 sec. intervals. The protection is reset automatically with applying opposite- direction input signal or turning the power off and restarting.
- Restarting Timer The Mini-Top Series is equipped with a timer circuit which gives an interval period (0 – 10 seconds) between stop- restart actions to prevent the motor and other internal components from overheating. It is recommended to set a long restarting time when the ambient temperature and/or the temperature of flow material is high.
- Electronic Limiter This model is equipped with electronic limiters in order to prevent mechanical locks when the input goes below 0 % or above 100 %. Limiters are set at approx. -1.5 % for the full-closed side, approx. 101.5 % for the full-open side.
- Seal-Spring The Mini-top Series incorporates a seal-spring to maintain the sealing pressure when the valve is fully closed. The standard spring has 0.5 – 1 mm (.02” – .04”) flexibility to facilitate the full-closed adjustment.
MODEL: MSP5 MSP5 SPECIFICATIONS ES-4845 Rev.14 Page 4/6 http://www.m-system.co.jp/ TERMINAL CONNECTIONS black (1) + (U) – (V) COM1 COM2 COM1 white (2) red (3) green (4) yellow (5) blue (6) gray (7) brown (8) (1) to (8): Terminal No. of terminal box. Full-open/-closed signals and forced open/close signals are optional. POWER INPUT POSITION OUTPUT (1 – 5V DC) FULL-OPEN or FULL-CLOSED SIGNAL (output stem)goes up (output stem)goes down + (U) – (V) COM1 COM2 POWER INPUT POSITION OUTPUT (1 – 5V DC) FULL-OPEN or FULL-CLOSED SIGNAL (output stem)goes up (output stem)goes down COM1 FORCED OPEN/CLOSE SIGNAL FORCED OPEN/ CLOSE SIGNAL (output stem)goes up (output stem)goes down (output stem)goes up (output stem)goes down
- With Both Full-open/closed Signal and Forced Open/Close Signal EXTERNAL DIMENSIONS unit: mm (inch) CABLE CONNECTOR w/1 meter (3.28 ft) LEADWIRE20 (.79) 90 (3.54) [130 (5.12)] (1.97) max. 98 (3.86) 46 (1.81) dia. 4–M5 10 (.39) deep 31 (1.22) 2 (.08) 36 –0.1 dia. 66 (2.60) dia. M (See the stem size table) YOKE CONNECTION [ ] for AC power supply *40 (1.57) max. with 5 – 10 mm stroke YOKE SURFACE 7 (.3) 124 (4.9) dia. (Wrench turning space) With the manual operation OUTPUT STEM HOLE SIZE M CODE DIA. PITCH DEPTH 6 M 6 0.75 8 M 8 1.0 1 M10 1.25 15 D M 6 1.0 E M 8 1.25 F M10 1.5
MODEL: MSP5 MSP5 SPECIFICATIONS ES-4845 Rev.14 Page 5/6 http://www.m-system.co.jp/ 67 (2.64)85 (3.35) 34 (1.34) 50 * (1.97) max. 46 (1.81) dia. 4–M5 10 (.39) deep 31 (1.22) 2 (.08) 36 –0.1 dia. 66 (2.60) dia. M (See the stem size table) YOKE CONNECTION [ ] for AC power supply *40 (1.57) max. with 5 – 10 mm stroke YOKE SURFACE 20 (.79) 7.5 (.30) 2–G 1/2 CONDUIT 32.5 (1.28) Cable connector or leadwires not provided with terminal box. 7 (.3) 124 (4.9) dia. (Wrench turning space) With the manual operation OUTPUT STEM HOLE SIZE M CODE DIA. PITCH DEPTH 6 M 6 0.75 8 M 8 1.0 1 M10 1.25 15 D M 6 1.0 E M 8 1.25 F M10 1.5 ■ TERMINAL BOX TYPE SCHEMATIC CIRCUITRY Hi / Lo Limiter Motor Control Logic Motor Driver Position Detector RESTART TIMER DEADBAND ADJ. Switching Regulator COM1 + (U) – (V) Power Circuit SZ Position Output Input Circuit INPUT 4 – 20mA DC (1 – 5V DC) COM1 FORCED OPEN/ CLOSE SIGNAL POSITION OUTPUT 1 – 5V DC POWER Limit Switch MODE SELECTOR POWER FUSE INPUT STATUS Full-open/-closed signals and forced open/close signals are optional. Disregard the switching regulator circuit for DC power input. Output stem goes up Output stem goes down MOTOR POT COM2 FULL-OPEN or FULL-CLOSED SIGNAL With Manual Operation Function
MODEL: MSP5 MSP5 SPECIFICATIONS ES-4845 Rev.14 Page 6/6 http://www.m-system.co.jp/ Specifications are subject to change without notice.