MPHLS MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 5
Technical content
MODEL: MPHLS MPHLS SPECIFICATIONS ES-4391 Rev.3 Page 1/5 https://www.m-system.co.jp/ Remote I/O MP Series HLS MASTER MODULE (For MP2200/MP2300/MP3300 series use) MODEL: MPHLS-01
ORDERING INFORMATION
- Code number: MPHLS-01 I/O TYPE 01: HLS function module 1 FUNCTIONS & FEATURES HLS Master Module is optional module for MP2200/MP2300/MP3300 series machine controllers made by YASKAWA Electric Corp. operating as master unit to connect analog I/O and discrete I/O with HLS(Hi-speed Link System). HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
RELATED PRODUCTS
- MP2200/MP2300 series machine controller (YASKAWA Electric Corp.) Ver.2.84 or later Software for programming device: MPE720 Ver.6.36 or later OR Ver.7.22 or later
- MP3300 series machine controller (YASKAWA Electric Corp.) Ver.1.12 or later Software for programming device: MPE720 Ver.7.28 or later GENERAL SPECIFICATIONS Terminating resistor: Built-in 100Ω Current Consumption (at 5 V DC): 160 mA HLS COMMUNICATION Communication mode*: Full-duplex or half-duplex Transmission distance*: 12 Mbps: 100 meters (328 ft)
6 Mbps: 200 meters (656 ft)
3 Mbps: 300 meters (984 ft)
Number of slaves*: 1 - 63 Hop count*: 0 - 7 hop * Configured with MPE720. Refer to the instruction manual for details. Network cable shield cable: ZHY262PS and ZHT262PS (Shinko Seisen Industry Co., Ltd.) Dual-shield cable: ZHY262PBA (Shinko Seisen Industry Co., Ltd.) Status indicator: RUN, CHK1, CHK2 (Refer to the instruction manual for details.) INSTALLATION Operating temperature: 0 to 55°C (32 to 131°F) Storage temperature: -25 to +85°C (-13 to 185°F) Operating humidity: 30 to 95 %RH (non-condensing) Storage humidity: 5 to 95 % RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: MP2200/MP2300/MP3300 Series Weight: 70 g (2.5 oz) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @1 minute (Internal circuit to HLS) STANDARDS & APPROVALS Refer to the manuals to comply with the standards. EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive
MODEL: MPHLS MPHLS SPECIFICATIONS ES-4391 Rev.3 Page 2/5 https://www.m-system.co.jp/ EXTERNAL VIEW Status Indicator LED Communication Connector CONNECTION DIAGRAMS 1. NC No connection 2. NC No connection 3. TXD+ Network (Slave, transmission +) 4. TXD– Network (Slave, transmission –) 5. RXD+ Network (Master, transmission+) 6. RXD– Network (Master, transmission–) 7. NC No connection 8. SLD1 Shield ˙ Recommended cable connector: TM21P-88P (Hirose Electric) (Not included in the package) Full-duplex communication Half-duplex communication 1. NC No connection 2. NC No connection 3. TR+ Network (+) 4. TR– Network (–) 5. NC No connection 6. NC No connection 7. NC No connection 8. SLD1 Shield Max. number of slave station HLS1-1 port: 32, HLS1-2 port: 31
MODEL: MPHLS MPHLS SPECIFICATIONS ES-4391 Rev.3 Page 3/5 https://www.m-system.co.jp/ MPHLS SLAVE UNIT SLAVE UNIT TerminatorTerminator MPHLS SLAVE UNIT SLAVE UNIT Terminator Set the terminator on the last terminal of slave unit. This HLS master module includes internal termiator. Terminator Full-duplex communication Half-duplex communication ■SLAVE UNIT WIRING 1 NC 2 NC
3 RXD+
4 RXD–
5 TXD+
TXD– RXD+ RXD– FG (SLD) TXD+ TXD– RXD+ RXD– FG (SLD)
6 TXD–
8 SLD
3 TR+
4 TR–
TR– FG (SLD) TR+ TR– FG (SLD) 6 NC 7 NC EXTERNAL DIMENSIONS unit: mm [inch] 132 [5.20] *Recommended cable connector: TM21P-88P (Hirose Electric)
MODEL: MPHLS MPHLS SPECIFICATIONS ES-4391 Rev.3 Page 4/5 https://www.m-system.co.jp/ SCHEMATIC CIRCUITRY Control Circuit Comm. Circuit Comm. Circuit Comm. Circuit Comm. Circuit Power Circuit INTERNAL BUS INTERNAL POWER *SLD NC NC NC RXD+ (TR+) RXD–(TR–) TXD+ (NC) TXD–(NC) HLS1 *SLD FG NC NC NC RXD+ (TR+) RXD–(TR–) TXD+ (NC) TXD–(NC) HLS2 *SLD is connected to FG terminal of the MP2200 / MP2300/MP3300 series machine controllers. Isolation Isolation CONNECTOR SYSTEM DESCRIPTIONS MP2310 24V DC POWER YASKAWA Electric INTEGRATED ENGINEERING TOOL MPE720 YASKAWA Electric MP2200/MP2300/MP3300 SERIES MACHINE CONTROLLER MPHLS-01HLS Slave HLS Slave HLS Slave Remote I/OɹR7F4DH, R7HL Remote I/OɹR7F4DH, R7HL HLS Slave Rt Max. number of connections: 32 Rt: Terminator HLS Slave HLS Slave HLS Slave HLS Slave Rt Rt Rt HLS HLS Max. number of connections: 31 Note: For MP3200, the MPHLS is available to use by attaching MP2000 option base unit.
MODEL: MPHLS MPHLS SPECIFICATIONS ES-4391 Rev.3 Page 5/5 https://www.m-system.co.jp/ Specifications are subject to change without notice.