Energy Management and Building Automation > Energy Management and Metering > Power and Multifunction Meters > IME Power and Multifunction Meters > IME Multifunction Meters > Nemo D4-LE NEMO D4-LE PULSE MFD4411 Catalogue No:
- Quick and easy to install
- Compact modern design
- High accuracy monitoring and measurement to IEC 62053-21
- Easy to read and configure
- Options for remote communication Representative Photo Only (actual product may vary based on configuration selections) NEMO D4-LE PULSE SPECIFICATIONS Component Type Metering Meter Type(s) Measurement parameters Display Technology Details, Display Number of DIN Modules Refresh Time Details, Input(s) Input Frequency, Nom Digital Meter Multifunction 1, 3-phase multifunction meter VL-L VL-N A Ah Admd Amaxdmd Hz PF W VA VAR Wdmd VAdmd VARdmd Wmaxdmd Varmaxdmd VAmaxdmd kWh kVARh h Voltage sequence diagnostics LCD Backlit. 8 DGT energy, 4 DGT instantaneous. Different pages of measurement display with manual scanning. Automatic engineering units display according to the set VT and CT ratios. 1.2 s Input 1-Phase Voltage: Line - Neutral. Input 3-Phase Voltage: Line - Line. Up to 50th Harmonic. 50 Hz Page 1 of 310 October 2022,1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com MFD4411 DatasheetNHP Electrical Engineering Products
Energy Management and Building Automation > Energy Management and Metering > Power and Multifunction Meters > IME Power and Multifunction Meters > IME Multifunction Meters > Nemo D4-LE NEMO D4-LE PULSE MFD4411 Catalogue No: Input Frequency, Max Input Frequency, Min Accuracy, Voltage Accuracy, Current Accuracy, Frequency Isn, Secondary Current, Rated Isn, Secondary Current, Max Input current (A) Input Voltage, 1ph, min (rms) Input Voltage, 1ph, max (rms) Input Voltage, 3ph, min (rms) Input Voltage, 3ph, max (rms) Number of Outputs Output Type Accuracy Class, Active Accuracy Class, kWh, IEC 61557-12 Accuracy Class, kVARh, IEC 61557-12 Accuracy Class, Reactive Power Dissipation, Max Current, Overload Capacity, Continuous Current, Overload Capacity, 0.5s Ui, Rated Insulation Voltage Mounting Pollution Degree Configuration Method Connection Method Password Protection Material, Body / Housing Operating Temperature, Min Operating Temperature, Max Storage Temperature, Min Storage Temperature, Max Humidity Type Installation Category Terminal Type IP Rating, Front IP Rating, Terminals Insulation Class Width Height Depth Weight Standards Compliance 63 Hz 47 Hz 0.5 +/- % 0.5 +/- % 0.2 +/- Hz 5 A
6 A max
30 V AC min (rms)
260 V AC max (rms)
50 V AC min (rms)
450 V AC max (rms)
0.5
0.5 IEC 61557-12
1 IEC 61557-12
6.8 W 0.006 kA 0.1 kA
300 V (rms)
PC (Polycarbonate) material -5 °C min 55 °C max -25 °C min 70 °C max Short-Term Condensation III Screw Terminal(s) IP52 IP20 III 70 mm 89.5 mm 65.6 mm 0.285 kg EN 62053-21 IEC 62053-21 EN 62053-23 EN 61010-1 EN 61000-6-3 EN 61000-6-2 EN 60715 EN 60529 DIN 43880 Page 2 of 310 October 2022,1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com MFD4411 DatasheetNHP Electrical Engineering Products
Energy Management and Building Automation > Energy Management and Metering > Power and Multifunction Meters > IME Power and Multifunction Meters > IME Multifunction Meters > Nemo D4-LE NEMO D4-LE PULSE MFD4411 Catalogue No: REFERENCES Installation Guide: - User Manual: - Manufacturer Datasheet: - Manufacturer Catalogue & Product Selection: - Supplier Declaration of Conformity: - IECEx Certificate - Page 3 of 310 October 2022,1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com MFD4411 DatasheetNHP Electrical Engineering Products