ME64 BURKERT | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 11

Technical content

Visit product website  DATA SHEET Type ME63  Industrial Ethernet gate- way, IP65/ IP67/ IP69k Type 8653  AirLINE Field - the valve island optimised for process automation Type 8691  Control head for de- centralised automation of ELEMENT process valves Type 8012  Flowmeter with paddle wheel for continuous flow measurement Type 8032  Flowmeter/Threshold detector with paddle wheel Standard | EU | en | 202212 | 03 I/O modules IP65/ IP67/ IP69k

  • Configurable I/O module for up to 16 digital input signals For use in environments requiring a high degree of protection Integrated diagnostic possibilities such as wire break, short circuit detection M12 L-Power port for the additional power supply (up to 32 A) for devices close to the process Up to four inputs can be used as frequency inputs Bürkert I/O modules (In/Out) Type ME64 for extending the Industrial Ethernet gateway Type ME63 are designed to capture the switching signals of various sensors. The further processing of these input signals, e.g. by Ethernet pro- tocol to a higher field level, is configured via the gateway. The 16DI module (16 digital inputs) can be used for the feedback from switches (limit switches, position switches, etc.). The captured signals are connected and transmitted to the gateway via a CANopen-based bus. Together with valve island compo- nents, such as Type 8653 AirLINE Field (pneumatic control of process valves) or process valve controls such as Type 8691, ME64 can be used to capture and evaluate feedback locally within waterproof environments. Via the central configuration management of the gateway, Type ME64, as the client, can be simply replaced with a new module, if required. Electronic modules Type ME63 and Type ME64 are part of the Bürkert EDIP (Efficient Device Integra- tion Platform) concept. They facilitate the integration of field level devices (e.g. valves or sensors) in the higher control level. The modules complement Bürkert EDIP systems. Product variants described in the data sheet may differ from the product presentation and description. Type descriptionCan be combined with Type ME64 © Christian Bürkert GmbH & Co. KG, Subject to alteration

2 | 11 Visit product website  Table of contents 1. General technical data 3 1.2. 16DI Module: digital input (DI) 2. Dimensions 4 3. Device/Process connections 5 Connection details Pin assignment 4. Product design and assembly 6 5. Product accessories 7 5.2. Bürkert Communicator Software 6. Networking and combination with other Bürkert products 8

Ordering information

7.2. Bürkert product filter 7.3. Ordering chart 7.4. Ordering chart accessories

3 | 11 Visit product website  1. General technical data 1.1. I/O-Module Product properties Dimensions Detailed information can be found in chapter “2. Dimensions” on page 4 Weight 400 g Material Body PC (Polycarbonate) Status display RGB-LED based on NAMUR NE107, Status LEDs per channel Approvals and Certificates Approval CE EU conformity UKCA UK conformity UL cULus listed1.) SPS IEC 61131 - 2 EMC EN 61000 Environment and installation Ambient temperature - °C…+ Storage temperature - °C…+ Degree of protection IP65, IP67 and IP69k acc. to EN 60529 / IEC 60529 (with cables connected and with protective caps on unused connections) Height above sea level Max. 2000 m 1.) Available for version 1, in preparation for version 2 1.2. 16DI Module: digital input (DI) Product properties Operating voltage 24 V DC + %/- Power consumption of the module 4.12 W Digital Input Electric version 2-wire sensor, 3-wire sensor, mechanical limit switches Diagnostics Open circuit detection with 2-wire sensors, short-circuit detection with 3-wire sensors Electrical connection 8x M12, A-coded, socket, 5 pin (X1-X8) Switching threshold VOFF = 0…5 V VON = 10…30 V Input current for VON, typ. 24 V DC Max. 5.7 mA per channel Input type Type1 and Type3 acc. to IEC 61132 Number of frequency inputs Up to 4 (Version 1), 8 (Version 2) Frequency input Max. up to 2.5 kHz Input impedance > 4 kOhm Sampling time/Sampling frequency 1 ms…4 s / 0.25 Hz…1 kHz Max. sensor power supply 16x 125 mA

4 | 11 Visit product website  2. Dimensions 2.1. 16DI Module Type ME64 Note: Dimensions in mm {a } { a } { a } 210 65 18

5 | 11 Visit product website  3. Device/Process connections 3.1. 16DI Module Type ME64 Connection details Note: Switch the power supply from X03 to X4 via the switch located on the side under the cover. X01 X02 X03 X04 Connec- tion Channel Description X12.)3.) 1 and 2 M12-A, socket, 2DI and 24 V DC max. 4 A, 2 multifunctional inputs1.) X2 to X4 3 to 8 M12-A, socket, 2DI and 24 V DC max. 4 A, 2 digital inputs X52.) 9 and 10 M12-A, socket, 2DI and 24 V DC max. 4 A, 2 multifunctional inputs1.) X6 to X83.) 11 to 16 M12-A, socket, 2DI and 24 V DC max. 4 A, 2 digital inputs X01 (IN) – M12-D, plug, büS/CANopen IN, for connection of büS/ CANopen network, input power aux (power supply up to 4 A) X02 (OUT) – M12-D, socket, büS/CANopen OUT, for the integration of further büS/CANopen device, output power aux (up to 4 A) X03 (IN) – M12-L, plug, power IN, max. 32 A, for the power supply (Power 1 and Power 2) X04 (OUT) – M12-L, socket, power OUT, max. 32 A, for the supply of further devices 1.) Variants of a multifunction input: digital input, pulse counter, frequency input, flow rate input, flow rate totalizer input 2.) Version 1: X1 and X5 with 2 multifunction inputs 3.) Version 2: X1 to X8 with 1 digital input and 1 multifunction input Pin assignment Note: The L-coded M12 connection (X03, X04) is designed for connecting 2 power supplies (Power 1, Power 2), each up to max. 16 A. Both supplies are routed separately on the module. Power 1 supplies the connections X1-X4 (as well as the internal electronics of the module), Power 2 supplies the connections X5-X8 X1 X8 Pin Pin assignment Function 453 2 1 1 24 V Power supply

2 IN B Digital input channel B

3 GND Power supply mass

4 IN A Digital input channel A

5 FE Shield

X01 (IN), X02 (OUT) Pin Pin assignment Function X01 1 2 X02 453 2 1

1 CAN_GND Shield

3 GND Power supply GND

4 CAN_H büS/CANopen communication

5 CAN_L büS/CANopen communication

X03 (IN), X04 (OUT) Pin Pin assignment Function X03 2 3 X04 3 2 1 24 V Power supply Power 1

2 GND Power supply Power 1, earthed

3 GND Power supply Power 2. earthed 4 24 V Power supply Power 2

6 | 11 Visit product website  Circuit diagram: GND DI x 24 V 2-wire 3-wire Switch 4. Product design and assembly 4.1. Product features Function: Connection of digital input signals, 2 DI and operating voltage on each M12, A-coded Switch: Switching from X03 to X01 for the power supply Communication: Integration in network, büS/CANopen and operating voltage via M12, A-coded Power supply: M12, L-coded

7 | 11 Visit product website  5. Product accessories 5.1. EDIP – Efficient Device Integration Platform EDIP is the new Bürkert device platform that will standardize the operation, communication and interfaces of many process devices (e.g. sensors, mass flow controllers). Thanks to EDIP, devices can be intelligently networked and operated with the standardized software, the Bürkert Communicator. The backbone and connecting link of EDIP is a digital interface that complies with the CANopen standard and can always be used in a manner compatible with it. EDIP offers the user the following advantages: Interoperability - guaranteed by the uniform interface Comfortable operation and display concept Faster and simplified commissioning Modularity - allows the devices to be adapted to individual customer requirements Easy transfer and fusion of device settings 5.2. Bürkert Communicator Software Note: To install the software, click here Part of Bürkert’s new EDIP program (Efficient Device Integration Platform) is the Bürkert Communicator. This software can be run un- der MS-Windows and it is available on Bürkert’s website for free. The Bürkert Communicator allows convenient system configuration and parametrisation of all connected field devices. An accessory part, the büS stick serves as the interface between computer and process instruments (see “7.4. Ordering chart accessories” on page 10 The Communicator allows: Diagnostics Parametrization Registration and storage of process data Graphical monitoring of the process data To update firmware of the büS device connected Guided re-calibration

8 | 11 Visit product website  6. Networking and combination with other Bürkert products Ethernet IN ME63 Gateway module Connection to feedback module Type ME64 via büS ME64 I/O-Modul Ethernet OUT Power OUTPower IN Connected büS network Connected büS network Short description of the illustrated example: Connection of 8 feedback signals (max. 16), via stub line to X1-X8 on ME64 Integration in büS-/CANopen network via X01 and X02 By connecting the büS-/CANopen network to a gateway type ME63, all signals are accessible via an Ethernet connection.

9 | 11 Visit product website  7. Ordering information 7.1. Bürkert eShop – Easy ordering and quick delivery Bürkert eShop – Easy ordering and fast delivery You want to find your desired Bürkert product or spare part quickly and order directly? Our online shop is available for you 24/7. Sign up and enjoy all the benefits. Order online now 7.2. Bürkert product filter Bürkert product filter – Get quickly to the right product You want to select products comfortably based on your technical requirements? Use the Bürkert product filter and find suitable articles for your application quickly and easily. Try out our product filter 7.3. Ordering chart Article Article no. 16x digital Inputs, 16DI Module (ME64) 346856 

10 | 11 Visit product website  7.4. Ordering chart accessories Article Article no. Gateway Industrial Ethernet ME63 346845  Passive distributor Type ME66 (Version 2, with separate power supply via X03) 20028654  büS cable extension, M12, 0.1 m 772492  büS cable extension, M12, 0.2 m 772402  büS cable extension, M12, 0.5 m 772403  büS cable extension, M12, 1 m 772404  büS cable extension, M12, 3 m 772405  M12-socket, straight (A-coded)1.) 772416  M12-plug, straight (A-coded)1.) 772417  M12-socket, angled (A-coded)1.) 772418  M12-plug, angled (A-coded)1.) 772419  Y distributor 772420  Y distributor for connecting two separately powered segments of a büS network 772421  Terminating resistor, 120 Ohm, M12 plug 772424  Terminating resistor, 120 Ohm, M12 socket 772425  Power supply unit Type 1573 for DIN rail, 100…240 V AC/24 V DC, 1.25 A, NEC Class 2 (UL 1310) 772438  Power supply unit Type 1573 for DIN rail, 100…240 V AC/24 V DC, 1 A, NEC Class 2 (UL 1310) 772361  Power supply unit Type 1573 for DIN rail, 100…240 V AC/24 V DC, 2 A, NEC Class 2 (UL 1310) 772362  Power supply uni Type 1573 for DIN rail, 100…240 V AC/24 V DC, 4 A 772363  büS-Stick Set 1 (incl. cable (M12), stick with integrated terminating resistor, power supply and software) 772426  büS-Stick Set 2 (incl. cable (M12)), stick with integrated terminating resistor 772551  Software Bürkert Communicator LINK 1.) For space reasons, the individual M12 connectors may not be suitable for simultaneous use on the same side of a Y distributor. In this case, please use a commercially available moulded cable.

Bürkert – Close to You Austria Belgium Czech Republic Denmark Finland France Germany Italy Netherlands Norway Poland Spain Sweden Switzerland Turkey United Kingdom China Hong Kong India Japan Korea Malaysia Philippines Singapore Taiwan South Africa Russia United Arab Emirates Brazil Uruguay Canada USA Australia New Zealand Credits, © and concept: Christian Bürkert GmbH & Co. KG | Photographs: Marc Eggimann Fotografie - 4051 Basel | Scanner GmbH - Werbeagentur Künzelsau -

74653 Künzelsau

www.burkert.com