MODEL: MAT3 MAT3 SPECIFICATIONS ES-8164 Rev.3 Page 1/5 http://www.m-system.co.jp/ Lightning Surge Protectors for Electronics Equipment M-RESTER LIGHTNING SURGE PROTECTOR FOR THREE-PHASE POWER SUPPLY Functions & Features

  • Connected in parallel between the power and earth lines regardless of load current
  • Applicable to single phase 2/3-wire and threephase 3/4- wire system
  • High discharge current capacity 20 kA or 40 kA (8/20 μs)
  • Degraded head element is automatically separated from the power lines by the incorporated thermal breaker, and the LED lamp (turns off) and the relay contact alerts the failure status.
  • Complies with IEC 61643-11 Class II Typical Applications
  • Low-voltage distribution board
  • Combination with installation for large load current 50 (1.97) mm (inch) (3.86) 60 (2.36) MODEL: MAT3–240[1]M[2]

ORDERING INFORMATION

  • Code number: MAT3-240[1]M[2] Specify a code from below for each of [1] and [2]. (e.g. MAT3-2403MY) OPERATIONAL VOLTAGE 240: 240 V AC [1] POWER SYSTEM 3: Single-phase 2/3-wire, Three-phase 3-wire 4: Single-phase 2/3-wire, Three-phase 3/4-wire MAXIMUM DISCHARGE CURRENT M: 20kA (8/20 μsec.) [2] ALARM OUTPUT A: With Y: Without GENERAL SPECIFICATIONS Construction: Standalone; terminal access at the front Degree of protection: IP20 (If the solderless terminals are covered with insulation tubes.) Surge protection type: Voltage limiting type one-port SPD Connection Line: M5 screw terminal (torque: 2.5 N·m) Alarm output: Tension clamp Applicable wire size Line: See the drawing below. Alarm output: 0.13 to 1.5 mm2, stripped length 8 mm Screw terminal Line: Nickel-plated steel Alarm output: Tin-plated copper alloy Housing material: Flame-resistant resin (black) Alarm output: SPDT relay contact trips when the thermal breaker operates. OUTPUT TERMINAL A1 – C Normal: Open Failure or power off: Close OUTPUT TERMINAL A2 – C Normal: Close Failure or power off: Open Rated load:

250 V AC @1 A (resistive load)

24 V DC @1 A (resistive load)

Safety function: Thermal breaker incorporated Monitor LED: Green LED turns on during normal condition and turns off during failure condition, power off or the thermal breaker operating. F d : M5 use B ≤ 13.0 mm F ≥ 7.0 mm (F ≥ 8.2 mm for sharing terminals) T ≤ 1.8 mm

  • Applicable Solderless Terminal Size diameter d BT INSTALLATION Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 5 to 95 %RH (non-condensing) Mounting: DIN Rail Weight: 300 g (0.66 lb)

MODEL: MAT3 MAT3 SPECIFICATIONS ES-8164 Rev.3 Page 2/5 http://www.m-system.co.jp/ PERFORMANCE Response time: ≤ 3 nanoseconds (≤ 20 nanoseconds for N to PE) Insulation resistance: ≥ 100 MΩ with 500 V DC (line to alarm output) Dielectric strength: 2000 V AC @1 minute (line to alarm output) Surge protection: IEC 61643-11 Class II EN 61643-11 Class II MODEL MAX. CONTINUOUS OPERATING VOLTAGE (Uc) DISCHARGE VOLTAGE (Vmin) VOLTAGE PROTECTION LEVEL (Up) OPERATIONAL VOLTAGE RANGE *1 (50 / 60Hz) MAT3-240 Between lines: 240 V AC N to PE: 320 V AC Between lines: 400V N to PE: 680V 1500 1-phase/2-wire, 3-phase/3-wire: 90 – 240V AC 1-phase/3-wire: 90 / 180 – 120 / 240V AC 3-phase/4-wire: 170 – 240V AC MODEL MAX. LEAKAGE CURRENT @Uc ALARM OUTPUT WITH WITHOUT MAT3-240 Line to Line 1 to 2 28mA *2 6mA *3 Other sections 2mA 2mA N to PE 10µA 10µA *1 . MAT3 is operational as an SPD despite the voltage less than the minimum. However, the functions of the monitor LED and the alarm output are not guaranteed. *2. Approx. 12mA @100V AC *3. Approx. 3mA @100V AC MODEL MAX. DISCHARGE CURRENT (Imax) NOMINAL DISCHARGE CURRENT (In) MAT3-240xMx 20kA (8/20µsec) 10kA (8/20µsec) STANDARDS & APPROVALS EU conformity: Low Voltage Directive EN 61643-11 RoHS Directive EN 50581

MODEL: MAT3 MAT3 SPECIFICATIONS ES-8164 Rev.3 Page 3/5 http://www.m-system.co.jp/ CONNECTION EXAMPLES EDEB 5)a 5)b N PE N PE N ■ INSTALLATION EXAMPLES: Three-phase 4-wire connection *1. The circuit breaker or the fuse as disconnectors must be installed. Molded-case circuit breaker (MCCB) or residual current circuit breaker with overcurrent protection (RCD) can be used. The rated interrupting capacity of the circuit breaker must be greater than the highest amount of current that could be available in the circuit. Install MCCB (rated current 20 – 30A) that has element for each phase. Or RCD with protection from nuisance tripping against transit voltages type or time-delay overcurrent protection type is recommended. Recommended sensitivity current rating: 30mA *2. Cable length between the branch point and the earthing: 0.5 meters or less recommended *3. The protected device's metal enclosure must be cross-wired to the earth terminal of the MAT3. If the protected device has no earth terminal, earth only the MAT3. *4. In order to protect an electronic circuit such as measuring equipment or communication equipment, we recommend to use surge protectors which have serial impedance incorporated such as M-System's models MAX, MMA, MAH. 1) : Protective device of the switchgear 2) : Circuit breaker 3) : Main earth terminal or busbar 4) : MAT3 5) : Earth conductor 5)a and/or 5)b 6) : Protected device EB : Main's earth electrode ED : Switchgear's earth electrode Residual Current Circuit Breaker

MODEL: MAT3 MAT3 SPECIFICATIONS ES-8164 Rev.3 Page 4/5 http://www.m-system.co.jp/ Power Power Power Power SPD1 PE N PE N C SPD1 N N C SPD1 PE N C SPD1 PE N C SPD1 ■ ALARM OUTPUT When the alarm output is to be transmitted remotely via outdoor cables, a surge protector for the signal line is required. POWER SYSTEM POWER SYSTEM Single-phase/2-wire Three phase/3-wire (delta connection) (N) Alarm output Alarm output Alarm output Protected device G Protected device G Circuit breaker (N) Circuit breaker CONNECTION CONNECTION EXAMPLE EXAMPLE Power System (example) Single-phase/2-wire 220V AC MAT3 –240xMx Single-phase/2-wire 110V AC MAT3 –240xMx SPD1 MAT3–240xMx Power System (example) SPD1Power System (example) SPD1Power System (example) Three-phase/3-wire 220V AC Three-phase/4-wire (star connection) Single-phase/2-wire (three-phase delta connection earthed in the middle of phases) Single-phase/3-wire Circuit breaker Single-phase/2-wire 110V AC MAT3 –240xMx Single-phase/3-wire 220/110V AC MAT3 –240xMx Three-phase/4-wire 220V AC MAT3–2404Mx *1. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, connect between terminal 2 and N of the MAT3. *2. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, install a four-pole (three-pole plus neutral) circuit breaker. *3. For single-phase/2-wire system, connect lines to terminal 1 and 2 of the MAT3. For single-phase/3-wire system, connect the neutral line to terminal 2 of the MAT3. Protected device G Protected device G Circuit breaker *2 Alarm output ■ CONNECTION EXAMPLES BY POWER SYSTEMS Abnormal voltages appearing in case of a light load or a fault earth loop must be within the maximum continuous operational voltage when selecting the MAT3 models.

MODEL: MAT3 MAT3 SPECIFICATIONS ES-8164 Rev.3 Page 5/5 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 45° (WIRE INSERTION ANGLE) DIN RAIL 35mm wide [3.4 (.13)] 60 (2.36) 80 (3.15) * Open/close type. ** Only for ‘Alarm output’ code ‘A’. 5–M5 SCREW TERMINAL COVER* MONITOR LED SPECIFICATION ALARM OUTPUT ** TERMINAL 1 (.04) 98 (3.86) 50 (1.97) 15 (.59) 15 (.59) 15 (.59) 80 (3.15) 12.5 (.49) C 1 2 N PE SCHEMATIC CIRCUITRY PE N ѳ ѳ ѳѳ Monitor LED ѳ: Thermal breaker Note: Terminals C, A1 & A2 are available for ‘Alarm output’ code ‘A.’ The schematic shows the relay contact status of a thermal trip or power off. Alarm Output Circuit A2 C A1 U U U U Specifications are subject to change without notice.