MAT2 MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 5
Technical content
MODEL: MAT2 MAT2 SPECIFICATIONS ES-8149 Rev.12 Page 1/5 https://www.m-system.co.jp/ Lightning Surge Protectors for Electronics Equipment M-RESTER LIGHTNING SURGE PROTECTOR FOR THREE-PHASE POWER SUPPLY Functions & Features
- Connected in parallel between the power and earth lines regardless of load current
- Applicable to single phase 2/3-wire and threephase 3/4- wire system
- High discharge current capacity 20 kA or 40 kA (8/20 μs)
- Degraded head element is automatically separated from the power lines by the incorporated thermal breaker, and the LED lamp (turns off) and the relay contact alerts the failure status.
- Complies with IEC 61643-1 Class II Typical Applications
- Low-voltage distribution board
- Combination with installation for large load current 50 [1.97] mm [inch] [3.86] 60 [2.36] MODEL: MAT2–[1][2][3][4]
ORDERING INFORMATION
- Code number: MAT2-[1][2][3][4] Specify a code from below for each of [1] through [4]. (e.g. MAT2-2403MY) [1] OPERATIONAL VOLTAGE 240: 240 V AC 440: 440 V AC [2] POWER SYSTEM 3: Single-phase 2/3-wire, Three-phase 3-wire (Select ‘240’ for ‘Operational voltage’ code.) 4: Single-phase 2/3-wire, Three-phase 3/4-wire [3] MAXIMUM DISCHARGE CURRENT M: 20kA (8/20 μsec.) H: 40kA (8/20 μsec.) [4] ALARM OUTPUT A: With Y: Without GENERAL SPECIFICATIONS Construction: Standalone; terminal access at the front Degree of protection: IP20 (If the solderless terminals are covered with insulation tubes.) Surge protection type: Voltage limiting type one-port SPD Connection Line: M5 screw terminal (torque: 2.5 N·m) Alarm output: Tension clamp Applicable wire size Line: See the drawing below. Alarm output: 0.13 to 1.5 mm2, stripped length 8 mm Screw terminal Line: Nickel-plated steel Alarm output: Tin-plated copper alloy Housing material: Flame-resistant resin (black) Alarm output: SPDT relay contact trips when the thermal breaker operates. OUTPUT TERMINAL A1 – C Normal: Open Failure or power off: Close OUTPUT TERMINAL A2 – C Normal: Close Failure or power off: Open Rated load:
250 V AC @1 A (resistive load)
24 V DC @1 A (resistive load)
Safety function: Thermal breaker incorporated Monitor LED: Green LED turns on during normal condition and turns off during failure condition, power off or the thermal breaker operating. F d : M5 use B ≤ 13.0 mm F ≥ 7.0 mm (F ≥ 8.2 mm for sharing terminals) T ≤ 1.8 mm
- Applicable Solderless Terminal Size diameter d BT
MODEL: MAT2 MAT2 SPECIFICATIONS ES-8149 Rev.12 Page 2/5 https://www.m-system.co.jp/ INSTALLATION Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: DIN Rail Weight: 300 g (0.66 lb) PERFORMANCE Response time: ≤ 3 nanoseconds (≤ 20 nanoseconds for N to PE) Insulation resistance: ≥ 100 MΩ with 500 V DC (line to alarm output) Dielectric strength: 2000 V AC @1 minute (line to alarm output) Surge protection: IEC 61643-1 Class II EN 61643-11 Class II MODEL MAX. CONTINUOUS OPERATING VOLTAGE (Uc) DISCHARGE VOLTAGE (Vmin) VOLTAGE PROTECTION LEVEL (Up) OPERATIONAL VOLTAGE RANGE *1 (50 / 60Hz) MAT2-240 Between lines: 240V AC N to PE: 320V AC Between lines: 400V N to PE: 550V 1500V 1-phase/2-wire, 3-phase/3-wire: 90 – 240V AC 1-phase/3-wire: 90 / 180 – 120 / 240V AC 3-phase/4-wire: 170 – 240V AC MAT2-440 Between lines: 440V AC N to PE: 320V AC Between lines: 780V N to PE: 550V 2500V 1-phase/2-wire, 3-phase/3-wire: 240 – 440V AC 1-phase/3-wire: 200 / 400 – 220 / 440V AC 3-phase/4-wire: 350 – 440V AC MODEL MAX. LEAKAGE CURRENT @Uc ALARM OUTPUT WITH WITHOUT MAT2-240 Line to Line 1 to 2 28mA *2 6mA *3 Other sections 2mA 2mA N to PE 10µA 10µA MAT2-440 Line to Line 1 to 2 22mA 6mA Other sections 2mA 2mA N to PE 10µA 10µA *1 . MAT2 is operational as an SPD despite the voltage less than the minimum. However, the functions of the monitor LED and the alarm output are not guaranteed. *2. Approx. 12mA @100V AC *3. Approx. 3mA @100V AC MODEL MAX. DISCHARGE CURRENT (Imax) NOMINAL DISCHARGE CURRENT (In) MAT2-xM 20kA (8/20µsec) 10kA (8/20µsec) MAT2-xH 40kA (8/20µsec) 20kA (8/20µsec) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61643-11 RoHS Directive
MODEL: MAT2 MAT2 SPECIFICATIONS ES-8149 Rev.12 Page 3/5 https://www.m-system.co.jp/ CONNECTION EXAMPLES *1. The circuit breaker must be installed. Molded-case circuit breaker (MCCB) or residual current circuit breaker with overcurrent protection (RCD) can be used. The rated interrupting capacity of the circuit breaker must be greater than the highest amount of current that could be available in the circuit. Install MCCB (rated current 20 – 30A) that has element for each phase. Or RCD with time-delay overcurrent protection is recommended. Recommended sensitivity current rating: 30mA *2. Cable length between the branch point and the earthing: 0.5 meters or less recommended *3. The protected device's metal enclosure must be cross-wired to the earth terminal of the MAT2. If the protected device has no earth terminal, earth only the MAT2. *4. In order to protect an electronic circuit such as measuring equipment or communication equipment, we recommend to use surge protectors which have serial impedance incorporated such as M-System's models MAX, MMA, MAH. EDEB 1) : Protective device of the switchgear 2) : Circuit breaker 3) : Main earth terminal or busbar 4) : MAT2 5) : Earth conductor 5)a and/or 5)b 6) : Protected device EB : Main's earth electrode ED : Switchgear's earth electrode 5)a 5)b N PE N Residual Current Circuit Breaker PE N ■ INSTALLATION EXAMPLES: Three-phase 4-wire connection
MODEL: MAT2 MAT2 SPECIFICATIONS ES-8149 Rev.12 Page 4/5 https://www.m-system.co.jp/ POWER SYSTEM Power System (example) SPD Single-phase/2-wire 220V AC MAT2 –240x Single-phase/2-wire 110V AC MAT2 –240x SPD Single-phase/2-wire 220V AC MAT2 –4404x Single-phase/2-wire 110V AC MAT2 –240x Single-phase/3-wire 400/200V AC MAT2 –4404x Single-phase/3-wire 220/110V AC MAT2 –240x SPD Single-phase/2-wire Generator or transformer Generator or transformer SPD MAT2–4 404x MAT2–240x Three phase/3-wire (delta connection) (N) Protected device G PE N A1 C A2 SPD Alarm output Circuit breaker *1. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, connect between terminal 2 and N of the MAT2. *2. For TT system, in order to ensure safe failure mode at TOV due to earth fault on high-voltage systems, install a four-pole (three-pole plus neutral) circuit breaker. *3. For 440V AC three-phase/3-wire system, use a residual current circuit breaker with overcurrent protection. *4. For single-phase/2-wire system, connect lines to terminal 1 and 2 of the MAT2. For single-phase/3-wire system, connect the neutral line to terminal 2 of the MAT2. Three-phase/4-wire 400V AC MAT2 –4404x Three-phase/4-wire 220V AC MAT2–2404x Protected device G PE N A1 C A2 SPD Alarm output Circuit breaker N Power System (example) Power System (example) Power System (example) CONNECTION EXAMPLE CONNECTION EXAMPLE POWER SYSTEM Three-phase/3-wire 400V AC Three-phase/3-wire 220V AC Three-phase/4-wire (star connection) Single-phase/2-wire (three-phase delta connection earthed in the middle of phases) Generator or transformer (N) Protected device G PE N A1 C A2 SPD Alarm output Circuit breaker Generator or transformer N Protected device G PE N A1 C A2 SPD Alarm output Circuit breaker Single-phase/3-wire ■ ALARM OUTPUT When the alarm output is to be transmitted remotely via outdoor cables, a surge protector for the signal line is required. ■ CONNECTION EXAMPLES BY POWER SYSTEMS Abnormal voltages appearing in case of a light load or a fault earth loop must be within the maximum continuous operational voltage when selecting the MAT2 models.
MODEL: MAT2 MAT2 SPECIFICATIONS ES-8149 Rev.12 Page 5/5 https://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch] 45° (WIRE INSERTION ANGLE) DIN RAIL 35mm wide (3.4 [.13]) 60 [2.36] 80 [3.15] * Open/close type. ** Only for ‘Alarm output’ code ‘A’. 5–M5 SCREW TERMINAL COVER* MONITOR LED SPECIFICATION ALARM OUTPUT ** TERMINAL 1 [.04] 98 [3.86] 50 [1.97] 15 [.59] 15 [.59] 15 [.59] 80 [3.15] 12.5 [.49] C 1 2 N PE SCHEMATIC CIRCUITRY PE A2 C A1 N ѳ Monitor LED ѳ: Thermal breaker Note: Terminals C, A1 & A2 are available for ‘Alarm output’ code ‘A.’ The schematic shows the relay contact status of a thermal trip or power off. Alarm Output Circuit ѳ ѳ ѳ U U U U Specifications are subject to change without notice.