MODEL: MALN MALN SPECIFICATIONS ES-8163 Rev.1 Page 1/4 https://www.m-system.co.jp/ Lightning Surge Protectors for Electronics Equipment M-RESTER ONE-PORT SURGE PROTECTOR BETWEEN NEUTRAL AND PROTECTIVE EARTH (class I) Functions & Features
- Designed to protect electronics equipment from direct lightning surges entering through power supply cable
- One-port surge protector according to IEC61643-1
- Connected between neutral and protective earth
- High discharge current capacity of 100 kA (10/350 μsec.)
- Protect against overvoltage between N and PE caused by earth fault Typical Applications
- Protection between N and PE of TT system
- Installation in service entrance switch gear [3.86] [2.52] mm [inch] 35 [1.38] MODEL: MALN–230
ORDERING INFORMATION
- Code number: MALN-230 OPERATIONAL VOLTAGE 230: 230 V AC
RELATED PRODUCTS
- Wiring bridge (model: CNB2)
- One-port surge protector for power supply use (model: MAL) ■ Coordination of surge protector (Class II) Unnecessary when this surge protector and the device to protect are adjacent (less than 10 m).
- One-port surge protector for power supply use (model: MAKF)
- One-port surge protector between N and PE (model: MAKN)
- Lightning surge protector for three-phase power supply (model: MAT2) GENERAL SPECIFICATIONS Degree of protection: IP20 Surge protection type: Voltage switching type one-port SPD (IEC 61643-1) Discharge element: Gas discharge tube Connection: Push-lock screw terminal (torque: 4.5 N·m) Applicable wire size: 8 - 35 mm2, stripped length 15 mm Housing material: Flame-resistant resin INSTALLATION Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: DIN rail Weight: 230 g (0.51 lb) PERFORMANCE Response time: ≤ 50 nsec. Maximum discharge current: 100 kA (10/350 μsec.) Surge protection: IEC 61643-1 Class I Uc (AC) (V) DISCHARGE VOLTAGE (V min) Up (V max) 255 400 4000 Uc = Maximum continuous operational voltage Up = Voltage protection level STANDARDS & APPROVALS EU conformity: Low Voltage Directive EN 61643-11 RoHS Directive
MODEL: MALN MALN SPECIFICATIONS ES-8163 Rev.1 Page 2/4 https://www.m-system.co.jp/ CONNECTION EXAMPLES SPD1 SPD1 SPD2 ACC1 ACC2 Protected device Circuit breaker G Circuit breaker Building Service entrance switch gear Equipotencial bonding terminal Switchgear Apparent energy meter (WHM) POWER (e.g.) Three phase/3-wire 220V AC SPD1 Class I Surge Protector Class II Surge Protector ACCESSORY MAL-230x SPD2 MALN-230 SPD3 MAKF-240x SPD4 MAKN-220x SPD5 MAT2-2404xx ACC1 CNB2-5 ACC2 CNB-3 *1. The circuit breaker's rating current must be of 150 A, and the rated interrupting capacity selected must be the grater between 30 kA or the highest amount of current that could be available in the circuit. For monitoring the operation of the circuit breaker we recommend also using the alarm switch (AL). *2. The use of RCD with time-delay overcurrent protection is recommended upon to prevent unnecessary operation with surge current (Recommended sensitivity current rating: 30mA) *3. Install an MCCB for backup saving of class II surge protector. Refer to the data sheets of the class II surge protector for details. *4. If the service entrance switchgear and switchgear or protective device wiring distance is more than 10 m, install the class II surge protector on the power supply downstream. Class II surge protector is the combination of SPD3 and SPD4 or SPD5 SPD3 SPD3 SPD4 SPD5 *1, *2 (N) INSTALLATION EXAMPLES: Three phase/3-wire (delta connection) TT Systems Lightning is a natural phenomenon and this unit could receive surges exceeding the discharge withstand current rating. Then, there is a possibility of burning out and result in short-circuits because of exceeding the processing capacity. Upon to save a backup, the circuit breaker must be installed on the power supply side of the surge protector. Molded-case circuit breaker (MCCB) or residual current circuit breaker with overcurrent protection (RCD) can be used. Generator or transformer Class II Surge Protector *4Class II Surge ProtectorClass I Surge Protector Circuit breaker Circuit breaker
MODEL: MALN MALN SPECIFICATIONS ES-8163 Rev.1 Page 3/4 https://www.m-system.co.jp/ POWER (e.g.) SPD1 MAL-230xSingle-phase /3-wire 220/110V AC SPD2 MALN-230 ACC CNB2-5 Single-phase /2-wire Single-phase /3-wire POWER (e.g.) SPD1 MAL-230x MAL-230x SPD2 MALN-230 MALN-230 ACC CNB2-4 CNB2-4 Protected device ACC L N G SPD1 SPD2 SPD2 Protected device G NL1 ACC SPD1 SPD1 POWER (e.g.) SPD1 Three-phase/3-wire 220V AC MAL-230x SPD2 MALN-230 ACC CNB2-5 Three-phase /3-wire (delta connection) Three-phase /4-wire (star connection) (N) SPD2 Protected device SPD2 G ACC SPD1 SPD1 POWER (e.g.) SPD1 MAL-400A MAL-230x SPD2 MALN-230 MALN-230 ACC CNB2-7 CNB2-7 N Protected device G ACC SPD1 SPD1 SPD1 Generator or transformer Generator or transformer Generator or transformer Generator or transformer Circuit breaker Circuit breaker Circuit breaker Circuit breaker Single-phase/2-wire 220V AC Single-phase/2-wire 110V AC Three-phase/4-wire 220V AC Three-phase/4-wire 400V AC Three-phase /3-wire (V connection) Three-phase /4-wire (V connection) SPD2 POWER (e.g.) SPD1 Three-phase/4-wire 220V AC MAL-230x SPD2 MALN-230 ACC CNB2-7 Protected device G ACC SPD1 SPD1 SPD1 N L3 *1. Wiring only for three-phase/4-wire Generator or transformer Circuit breaker ■ CONNECTION EXAMPLES BY POWER SYSTEMS
MODEL: MALN MALN SPECIFICATIONS ES-8163 Rev.1 Page 4/4 https://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch] 64 [2.52] DIN RAIL ADAPTOR DIN RAIL ADAPTOR MARKING LABELS MARKING LABELS SPECIFICATIONS (2 [.08]) DIN RAIL 35mm wide 45 [1.77] DIN RAIL N-PE TERMINAL PE TERMINAL WIRING BRIDGE (model: CNB2) WIRING INLET • When mounting, no extra space is needed between units. SCHEMATIC CIRCUITRY N PE Discharge Element Specifications are subject to change without notice.