MODEL: M8YC M8YC SPECIFICATIONS ES-5459 Rev.7 Page 1/2 http://www.m-system.co.jp/ Dual Output Super-mini Signal Conditioners Pico-M Series CONTROL OUTPUT ISOLATOR Functions & Features

  • Providing an isolated DC output at the Installation Base terminals
  • Detecting opencircuit at the output loop
  • Space-saving, easy-to-maintain, multi-channel installation base MODEL: M8YC-AA-R[1]

ORDERING INFORMATION

  • Code number: M8YC-AA-R[1] Specify a code from below for [1]. (e.g. M8YC-AA-R/Q)
  • Specify the specification for option code /Q (e.g. /C01 /V01) INPUT Current A: 4 – 20 mA DC (Input resistance 250 Ω) OUTPUT Current A: 4 – 20 mA DC (Load resistance 550 Ω max.) POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [1] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating ADJUSTMENT /V01: Multi-turn fine adjustment

RELATED PRODUCTS

  • Installation Base or Single Mount Base Socket (model: M8BSx) This unit must be mounted on dedicated base or socket except Model M8BS2 base. (The opencircuit detection is canceled, when mounted on M8BS-1-1.) GENERAL SPECIFICATIONS Construction: Plug-in Mounting screw: M3 screw (torque 0.3 N·m) Housing material: Flame-resistant resin (black) Power supply: Via the Installation Base terminals (model: M8BSx) (Model M8BS2 is not usable for the M8YC.) Isolation: Input to output to power Zero adjustment: -2 to +2 % (front) Span adjustment: 98 to 102 % (front) Opencircuit detection: input current 0 mA when the output loop is open. INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated OUTPUT SPECIFICATIONS The output goes below 0 % when the input loop is open. INSTALLATION Current consumption: Approx. 50 mA Operating temperature: 0 to 55°C (32 to 131°F) Operating humidity: 30 to 95 %RH (non-condensing) Mounting: Installation Base (model: M8BSx) (Model M8BS2 is not usable for the M8YC.) Weight: 70 g (2.5 oz) PERFORMANCE in percentage of span Accuracy: ±0.1 % Temp. coefficient: ±0.02 %/°C (±0.01 %/°F) Response time: ≤ 15 msec. (0 – 90 %) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength:

1500 V AC @1 minute(input or power to output to ground)

500 V AC @1 minute(input to power)

SWC test: ANSI/IEEE-C37.90.1-1989

MODEL: M8YC M8YC SPECIFICATIONS ES-5459 Rev.7 Page 2/2 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS unit: mm (inch) I/O PINS 17.5(.69) 48 (1.89) 75 (2.95) 83 (3.27) SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Isolation Installation Base Low Drift Amplifier OUTPUT SZ D A B C POWER Output Driver Opencircuit Detector+ INPUT *Use the terminals 6 – 7 for input. The terminals 8 – 9 can be used but the opencircuit detection is canceled. 250Њ Specifications are subject to change without notice.