MODEL: M80YS M80YS SPECIFICATIONS ES-5397 Rev.0 Page 1/2 http://www.m-system.co.jp/ Super-mini Signal Conditioners M80 Series OUTPUT ISOLATOR Functions & Features
- Converts DC input into isolated standardized process signal
- Isolates between analog output channels of a PLC
- Achieves space-saving and easy maintenance with Multi- channel Installation Base mm (inch) 14.0 (.55) 39.2 (1.54) 51.8 (2.04) MODEL: M80YS-6[1]-R
ORDERING INFORMATION
- Code number: M80YS-6[1]-R Specify a code from below for [1]. (e.g. M80YS-66-R) INPUT Voltage 6: 1 – 5 V DC (Input resistance 1 MΩ min.) [1] OUTPUT Current A: 4 – 20 mA DC (Load resistance 600 Ω max.) D: 0 – 20 mA DC (Load resistance 600 Ω max.) Voltage 4: 0 - 10 V DC (Load resistance 5000 Ω min.) 5: 0 – 5 V DC (Load resistance 2500 Ω min.) 6: 1 – 5 V DC (Load resistance 2500 Ω min.) 4W: -10 – +10 V DC (Load resistance 5000 Ω min.) POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
RELATED PRODUCTS
- Installation Base (model: M80BSx) This unit must be mounted on a dedicated base. GENERAL SPECIFICATIONS Construction: Plug-in Housing material: Flame-resistant resin (gray) Power supply: Via the Installation Base terminals (model: M80BSx) Isolation: Input to output to power Zero adjustment: -5 to +5 % (front) Span adjustment: 95 to 105 % (front) INPUT SPECIFICATIONS ■ DC Voltage Input resistance: 1 MΩ min. (10 kΩ min. in power failure) INSTALLATION Current consumption: Approx. 50 mA Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 5 to 95 %RH (non-condensing) Mounting: Multi-channnel Installation Base (model: M80BSx) Weight: 20 g (0.71 oz) PERFORMANCE in percentage of span Accuracy: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: ≤ 15 msec. (0 – 90 %) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1000 V AC @1 minute (input to output to power to ground) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581
MODEL: M80YS M80YS SPECIFICATIONS ES-5397 Rev.0 Page 2/2 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS unit: mm (inch) 14.0 (.55) 39.2 (1.54) SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM SZ Low Drift Amplifier INPUT Isolation Output Driver 1 OUTPUT POWER Note: Use shielded cables for I/O wiring. Installation Base A B C ɹ ɹ ɹ ɹ ɹ ɹ Specifications are subject to change without notice.