M2XM2 MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

MODEL: M2XM2 M2XM2 SPECIFICATIONS ES-5093 Rev.10 Page 1/4 http://www.m-system.co.jp/ Super-mini Signal Conditioners Mini-M Series POTENTIOMETER TRANSMITTER (PC programmable) Functions & Features

  • Provides a DC output proportional to a potentiometer or slidewire position input
  • PC programmable
  • Potentiometer’s zero/span points can be captured by on- site calibrations Typical Applications
  • Tank levels
  • Positions: Compensating non-linear signal from the linking mechanism of a position detector Model 23 (.91) (2.99) mm (inch) 124 (4.88) MODEL: M2XM2–1[1]–[2][3]

ORDERING INFORMATION

  • Code number: M2XM2-1[1]-[2][3] Specify a code from below for each [1] through [3]. (e.g. M2XM2-1Z1-R/CE/Q)
  • Input range (e.g. 0 – 500 Ω)
  • Output range (e.g. 4 – 20 mA DC)
  • Specify the specification for option code /Q (e.g. /C01/S01/SET) INPUT POTENTIOMETER 1: Total resistance 100 Ω – 10 kΩ (Configurator software is used to change input range (total resistance).) [1] OUTPUT Current Z1: Range 0 – 20 mA DC Voltage V1: Range -2.5 – +2.5 V DC V2: Range -10 – +10 V DC (Configurator software is used to change output over the described range of the selected suffix code. For changing out of this range, set the Output Range Selectors inside the unit before software adjustment.) [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) (90 – 264 V for UL) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.) (110 V ±10 % for UL) [3] OPTIONS (multiple selections) Standards & Approvals (must be specified) /N: Without CE or UL /CE: CE marking /UL: UL approval, CE marking Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating (UL not available) TERMINAL SCREW MATERIAL /S01: Stainless steel (UL not available) EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-5093)

RELATED PRODUCTS

  • PC configurator software (model: JXCON) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

MODEL: M2XM2 M2XM2 SPECIFICATIONS ES-5093 Rev.10 Page 2/4 http://www.m-system.co.jp/ GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3 screw terminals (torque 0.8 N·m) Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output to power Overrange output: Approx. -15 to +115 % (Negative current output is not provided.) Manual zero adjustments: -5 to +5 % (factory setting: 0 %) Manual span adjustments: 95 to 105 % (factory setting: 100 %) Programming: Downloaded from PC; linearization (100 points), input range (total resistance), output range, zero and span, simulating output, etc. Burnout: Upscale standard; downscale or no burnout optional by programming Status indicator LED: Blinking patterns indicate different operating status of the transmitter. Configurator connection: 2.5 dia. miniature jack; RS-232-C level INPUT SPECIFICATIONS

  • Potentiometer: 100 Ω – 10 kΩ Range : Minimum span 0 – 100 Ω : 2.5 Ω 0 – 300 Ω : 3.0 Ω 0 – 1000 Ω : 10 Ω 0 – 10 kΩ : 10 Ω Excitation: ≤ 0.5 V DC at 1000 Ω If not specified, default value is 1000 Ω. OUTPUT SPECIFICATIONS ■ DC Current Operational range: 0 – 24 mA DC Output range: 0 – 20 mA DC Minimum span: 1 mA Offset: Lower range can be any specific value within the output range provided that the minimum span is maintained. Load resistance: Output drive 15 V max. (e.g. 4 – 20 mA: 750 Ω [15 V ÷ 20 mA]) If not specified, the output range is 4 – 20 mA DC. ■ DC Voltage Code V1 (narrow spans) Operational range: -3 – +3 V DC Output range: -2.5 – +2.5 V DC Minimum span: 250 mV Code V2 (wide spans) Operational range: -11.5 – +11.5 V DC Output range: -10 – +10 V DC Minimum span: 1 V Offset: Lower range can be any specific value within the output range provided that the minimum span is maintained. Load resistance: Output drive 1 mA max. If not specified, the output range is shown below. V1: 0 – 1 V DC V2: 1 – 5 V DC INSTALLATION Power Consumption
  • AC: Approx. 3 VA at 100 V Approx. 4 VA at 200 V Approx. 5 VA at 264 V
  • DC: Approx. 2 W Operating temperature: -30 to +60°C (-22 to +140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 120 g (0.26 lb) PERFORMANCE in percentage of span Accuracy: Input accuracy + output accuracy Inversely proportional to the span. Input accuracy: (% of max. input range) (Range) 0 – 1000 Ω : ±0.01 % Output accuracy: ±0.04 % of max. output range Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span at -5 to +55°C [23 to 131°F] Response time: ≤ 0.9 sec. (0 – 90 %) Burnout response time: ≤ 30 sec. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output to power to ground) CALCULATION EXAMPLES OF OVERALL ACCURACY [Example] Input Type 0 – 1000 Ω, Input Range 250 – 750 Ω ,Output Type 0 – 20 mA, Output Range 4 – 20 mA Max. Input Range (1000 Ω) ÷ Span (500 Ω) × 0.01 % = 0.02 % Max. Output Range (20 mA) ÷ Span (16 mA) × 0.04 % = 0.05 % Overall accuracy = 0.02 % + 0.05 % = ±0.07 %

MODEL: M2XM2 M2XM2 SPECIFICATIONS ES-5093 Rev.10 Page 3/4 http://www.m-system.co.jp/ STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2 Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) RoHS Directive EN 50581 Approval: UL/C-UL nonincendive Class I, Division 2, Groups A, B, C, and D (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213) UL/C-UL general safety requirements (UL 61010-1, CAN/CSA-C22.2 No.61010-1) EXTERNAL VIEW UP/DOWN Switches The front cover cannot be turned open by 180 deg. when there is no extra space between units. Configurator Jack ■ FRONT VIEW (with cover open)Status Indicator LED Zero/Span Selector Top: SPAN Middle: OFF Bottom: ZERO ■ LEFT SIDE VIEW (with cover removed) Output Range Selectors [e.g.] Output code V1 O N 2 O SW2 ATT SW3 SW6 SW4 SW7 IV I V Refer to the instruction manual for detailed procedures. EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 21.5 (.85) 70.5 (2.78) 6 (.23) 59 (2.32) DIN RAIL 35mm wide [4 (.16)] 8–M3 SCREW 72 (2.83) 23 (.91) 2–4.2x5 (.17x.20) MTG HOLE 6 (.24) deep 116.7 (4.59)

  • When mounting, no extra space is needed between units. 14 13 4 (.16)

MODEL: M2XM2 M2XM2 SPECIFICATIONS ES-5093 Rev.10 Page 4/4 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Isolation Base Socket Low Drift Amplifier & Burnout Output Driver OUTPUT Digital Computation ZERO/SPAN SELECTOR UP/DOWN SWITCHES CONFIGURATOR JACK U(+) V(–) POWER STATUS POTENTIOMETER max. min. OUTPUT RANGE SELECTORS Specifications are subject to change without notice.