MODEL: M2SED M2SED SPECIFICATIONS ES-5042 Rev.16 Page 1/4 http://www.m-system.co.jp/ Super-mini Signal Conditioners Mini-M Series DC ALARM (thumbwheel switch adjustment) Functions & Features

  • Provides SPDT relay outputs at preset DC input levels
  • Dual (Hi / Lo) trip
  • Thumbwheel switch setpoint adjustments
  • Enclosed relays
  • Relays can be powered 110 V DC Typical Applications
  • Annunciator
  • Various alarm applications 29.5 (1.16) (2.99) 124 (4.88) 3 1 4 4 mm (inch) MODEL: M2SED–[1]13–[2][3]

ORDERING INFORMATION

  • Code number: M2SED-[1]13-[2][3] Specify a code from below for each of [1] through [3]. (e.g. M2SED-613-P/CE/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01) Note: Must be used with its socket. NOT installable to a multi-unit installation base. (e.g. model: M2BS-16) [1] INPUT Current A: 4 – 20 mA DC (Input resistance 250 Ω) Voltage 4: 0 – 10 V DC (Input resistance 1 MΩ min.) 5: 0 – 5 V DC (Input resistance 1 MΩ min.) 6: 1 – 5 V DC (Input resistance 1 MΩ min.) SETPOINT 1 OUTPUT 1: Hi (coil energized at alarm) SETPOINT 2 OUTPUT 3: Lo (coil energized at alarm) [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) (90 – 264 V for UL) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) R2: 11 – 27 V DC (Operational voltage range 11 – 27 V, ripple 10 %p-p max.) (Select ‘/N’ for ‘Standards & Approvals’ code.) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.) (110 V ±10 % for UL) [3] OPTIONS (multiple selections) Standards & Approvals (must be specified) /N: Without CE or UL /CE: CE marking /UL: UL approval, CE marking Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating (UL not available) TERMINAL SCREW MATERIAL /S01: Stainless steel (UL not available) GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3 screw terminals (torque 0.8 N·m) Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output to power Setpoint adjustments: Thumbwheel switches (front); 0 – 99 % independently; 1 % increments Hysteresis (deadband): 1 ± 0.3 % Front LEDs: Red light turns on when the coil is energized. INPUT SPECIFICATIONS ■ DC Current: Shunt resistor attached to the input terminals (0.5 W)

MODEL: M2SED M2SED SPECIFICATIONS ES-5042 Rev.16 Page 2/4 http://www.m-system.co.jp/ OUTPUT SPECIFICATIONS ■ Relay Contact:

100 V AC @5 A (cos ø = 1)

120 V AC @5 A (cos ø = 1)

240 V AC @2.5 A (cos ø = 1)

30 V DC @5 A (resistive load)

Maximum switching voltage: 250 V AC or 125 V DC Maximum switching power: 600 VA or 150 W Minimum load: 5 V DC @10 mA Mechanical life: 5 × 107 cycles 0 50 100 ▲ Input (%) Setpoint 2 Setpoint 1 Output 1 (5–7)ON Output 2 (3–9)ON (3–6)ON (5–8)ON Alarm Trip Operation Terminal No. in parentheses Trip Operation in Power Failure: Terminals 3 – 9 and 5 – 8 turn on. INSTALLATION Power Consumption

  • AC: Approx. 3 VA at 100 V Approx. 4 VA at 200 V Approx. 5 VA at 264 V
  • DC: Approx. 3 W Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Installation Base (model: M2BS) is not adaptable. Weight: 150 g (0.33 lb) PERFORMANCE in percentage of span Setpoint accuracy: ±0.5 % Trip point repeatability: ±0.05 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: 0.5 ± 0.2 sec. (0 – 100 % at 90 % setpoint) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output to power to ground) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (output) Installation Category II (power) Pollution Degree 2 Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) RoHS Directive EN 50581 Approval: UL/C-UL general safety requirements (UL 61010B-1, CAN/CSA-C22.2 No.1010-1)

MODEL: M2SED M2SED SPECIFICATIONS ES-5042 Rev.16 Page 3/4 http://www.m-system.co.jp/ FRONT VIEW 9 9 9 9 The front cover cannot be turned open by 180 deg. when there is no extra space between units. Output 1 Output 2 Output 1

  • Setpoint Adj.
  • Monitor LED Output 2 EXTERNAL DIMENSIONS unit: mm (inch) 8 7 10 11 123 21.5 (.85) 70.5 (2.78) 6 (.23) 59 (2.32) DIN RAIL 35mm wide [4 (.16)] 11–M3 SCREW 2–4.2x5 (.17x.20) MTG HOLE 6 (.24) deep 116.7 (4.59)
  • When mounting, no extra space is needed between units. TERMINAL ASSIGNMENTS unit: mm (inch) 8 7 10 11 INPUT RESISTOR (model: REM2) 19 (.75) Input shunt resistor attached for current input.

MODEL: M2SED M2SED SPECIFICATIONS ES-5042 Rev.16 Page 4/4 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Ry Ry Base Socket Comparator

1 Low Drift

  • Input shunt resistor attached for current input. 9 9THUMBWHEEL SWITCHES THUMBWHEEL SWITCHES 9 9 N.C. N.O. COM N.C. N.O. COM *INPUT R U(+) V(–) POWER LOAD LOAD U Inductive Load (Coil) Inductive Load (Coil) Varistor or CR Circuit Diode, Varistor or CR Circuit ■ Relay Protection
  • AC Powered • DC Powered Specifications are subject to change without notice.